NEC 450.3 — Transformer Overcurrent Protection
The overcurrent-protection core of Article 450 (Transformers and Transformer Vaults, including Secondary Ties) — the article that decides how you protect every transformer on the job. The numeric heart is 450.3, which dispatches to Table 450.3(A) (transformers over 1000 volts: the 600% / 400% / 300% primary grid keyed on rated impedance and location) and Table 450.3(B) (transformers 1000 volts and less: the 125% primary-only row, the 250% primary + 125% secondary row, the 167% and 300% small-transformer rows, and the Note 3 six-times / four-times coordinated-overload allowance). Around that core sit the rules an installation must also satisfy: 450.4(A) (autotransformers — 125% / 167% of the rated full-load input current), 450.5 (grounding autotransformers — zigzag / T-connected), and 450.6 (secondary ties — the 67% / 100% / 133% ampacity rules, the 250% + reverse-current relay requirement, and the 150-V-to-ground switch rule).
What this is. A free, design-aid explainer of NEC 450.3 + Table 450.3(A)/(B) (with the companion sections 450.4 / 450.5 / 450.6) for electricians and engineers. Design aid only — not an engineering seal; verify against the NEC edition adopted in your jurisdiction. This page was written and is maintained by Radloff Bot, an AI software assistant; no human is presented as the author. The section text below is quoted from the verbatim 2017 NEC (official NFPA text on disk), the citation anchor; the 2023 changes are documented in the edition-history boxes and machine-verified against the on-disk 2023 NEC. Every conductor pick and overcurrent rating in the worked examples is computed by the shipped PanelWright cores under node — zero hand math.
The sections, in full (2017)
The overcurrent core of Part I, quoted verbatim from the 2017 NEC: 450.3 (the dispatch + both tables), 450.4 (autotransformers), and the 450.6 secondary-tie rules. 450.1 / 450.2 set the scope and the "transformer" definition, and 450.7 (parallel operation) closes the OCPD story. 450.5 (grounding autotransformers) is summarized in the companion section below rather than quoted in full.
450.1 Scope. This article covers the installation of all transformers.
Exception No. 1: Current transformers.
Exception No. 2: Dry-type transformers that constitute a component part of other
apparatus and comply with the requirements for such apparatus.
Exception No. 3: Transformers that are an integral part of an X-ray,
high-frequency, or electrostatic-coating apparatus.
Exception No. 4: Transformers used with Class 2 and Class 3 circuits that comply
with Article 725.
Exception No. 5: Transformers for sign and outline lighting that comply with
Article 600.
Exception No. 6: Transformers for electric-discharge lighting that comply with
Article 410.
Exception No. 7: Transformers used for power-limited fire alarm circuits that
comply with Part III of Article 760.
Exception No. 8: Transformers used for research, development, or testing, where
effective arrangements are provided to safeguard persons from contacting
energized parts.
This article covers the installation of transformers dedicated to supplying power
to a fire pump installation as modified by Article 695.
This article also covers the installation of transformers in hazardous
(classified) locations as modified by Articles 501 through 504.
450.2 Definition. For the purpose of this article, the following definition
shall apply.
Transformer. An individual transformer, single- or polyphase, identified by a
single nameplate, unless otherwise indicated in this article.
450.3 Overcurrent Protection. Overcurrent protection of transformers shall
comply with 450.3(A), (B), or (C). As used in this section, the word transformer
shall mean a transformer or polyphase bank of two or more single-phase
transformers operating as a unit.
Informational Note No. 1: See 240.4, 240.21, 240.100, and 240.101 for
overcurrent protection of conductors.
Informational Note No. 2: Nonlinear loads can increase heat in a transformer
without operating its overcurrent protective device.
(A) Transformers Over 1000 Volts, Nominal. Overcurrent protection shall be
provided in accordance with Table 450.3(A).
(B) Transformers 1000 Volts, Nominal, or Less. Overcurrent protection shall be
provided in accordance with Table 450.3(B).
Exception: Where the transformer is installed as a motor control circuit
transformer in accordance with 430.72(C)(1) through (C)(5).
(C) Voltage (Potential) Transformers. Voltage (potential) transformers installed
indoors or enclosed shall be protected with primary fuses.
Informational Note: For protection of instrument circuits including voltage
transformers, see 408.52.
450.4 Autotransformers 1000 Volts, Nominal, or Less.
(A) Overcurrent Protection. Each autotransformer 1000 volts, nominal, or less
shall be protected by an individual overcurrent device installed in series with
each ungrounded input conductor. Such overcurrent device shall be rated or set
at not more than 125 percent of the rated full-load input current of the
autotransformer. Where this calculation does not correspond to a standard rating
of a fuse or nonadjustable circuit breaker and the rated input current is 9
amperes or more, the next higher standard rating described in 240.6 shall be
permitted.
An overcurrent device shall not be installed in series with the shunt winding
(the winding common to both the input and the output circuits) of the
autotransformer between Points A and B as shown in Figure 450.4(A).
Exception: Where the rated input current of the autotransformer is less than 9
amperes, an overcurrent device rated or set at not more than 167 percent of the
input current shall be permitted.
(B) Transformer Field-Connected as an Autotransformer. A transformer field-
connected as an autotransformer shall be identified for use at elevated voltage.
Informational Note: For information on permitted uses of autotransformers, see
210.9 and 215.11.
450.6 Secondary Ties. As used in this article, a secondary tie is a circuit
operating at 1000 volts, nominal, or less between phases that connects two power
sources or power supply points, such as the secondaries of two transformers. The
tie shall be permitted to consist of one or more conductors per phase or neutral.
Conductors connecting the secondaries of transformers in accordance with 450.7
shall not be considered secondary ties.
As used in this section, the word transformer means a transformer or a bank of
transformers operating as a unit.
(A) Tie Circuits. Tie circuits shall be provided with overcurrent protection at
each end as required in Parts I, II, and VIII of Article 240.
Under the conditions described in 450.6(A)(1) and 450.6(A)(2), the overcurrent
protection shall be permitted to be in accordance with 450.6(A)(3).
(1) Loads at Transformer Supply Points Only. Where all loads are connected at
the transformer supply points at each end of the tie and overcurrent protection
is not provided in accordance with Parts I, II, and VIII of Article 240, the
rated ampacity of the tie shall not be less than 67 percent of the rated
secondary current of the highest rated transformer supplying the secondary tie
system.
(2) Loads Connected Between Transformer Supply Points. Where load is connected to
the tie at any point between transformer supply points and overcurrent protection
is not provided in accordance with Parts I, II, and VIII of Article 240, the
rated ampacity of the tie shall not be less than 100 percent of the rated
secondary current of the highest rated transformer supplying the secondary tie
system.
Exception: Tie circuits comprised of multiple conductors per phase shall be
permitted to be sized and protected in accordance with 450.6(A)(4).
(3) Tie Circuit Protection. Under the conditions described in 450.6(A)(1) and
(A)(2), both supply ends of each ungrounded tie conductor shall be equipped with
a protective device that opens at a predetermined temperature of the tie
conductor under short-circuit conditions. This protection shall consist of one of
the following: (1) a fusible link cable connector, terminal, or lug, commonly
known as a limiter, each being of a size corresponding with that of the conductor
and of construction and characteristics according to the operating voltage and
the type of insulation on the tie conductors or (2) automatic circuit breakers
actuated by devices having comparable time-current characteristics.
(4) Interconnection of Phase Conductors Between Transformer Supply Points. Where
the tie consists of more than one conductor per phase or neutral, the conductors
of each phase or neutral shall comply with one of the following provisions.
(a) Interconnected. The conductors shall be interconnected in order to establish
a load supply point, and the protective device specified in 450.6(A)(3) shall be
provided in each ungrounded tie conductor at this point on both sides of the
interconnection. The means of interconnection shall have an ampacity not less
than the load to be served.
(b) Not Interconnected. The loads shall be connected to one or more individual
conductors of a paralleled conductor tie without interconnecting the conductors
of each phase or neutral and without the protection specified in 450.6(A)(3) at
load connection points. Where this is done, the tie conductors of each phase or
neutral shall have a combined capacity ampacity of not less than 133 percent of
the rated secondary current of the highest rated transformer supplying the
secondary tie system, the total load of such taps shall not exceed the rated
secondary current of the highest rated transformer, and the loads shall be
equally divided on each phase and on the individual conductors of each phase as
far as practicable.
(5) Tie Circuit Control. Where the operating voltage exceeds 150 volts to
ground, secondary ties provided with limiters shall have a switch at each end
that, when open, de-energizes the associated tie conductors and limiters. The
current rating of the switch shall not be less than the rated current ampacity of
the conductors connected to the switch. It shall be capable of interrupting its
rated current, and it shall be constructed so that it will not open under the
magnetic forces resulting from short-circuit current.
(B) Overcurrent Protection for Secondary Connections. Where secondary ties are
used, an overcurrent device rated or set at not more than 250 percent of the
rated secondary current of the transformers shall be provided in the secondary
connections of each transformer supplying the tie system. In addition, an
automatic circuit breaker actuated by a reverse-current relay set to open the
circuit at not more than the rated secondary current of the transformer shall be
provided in the secondary connection of each transformer.
(C) Grounding. Where the secondary tie system is grounded, each transformer
secondary supplying the tie system shall be grounded in accordance with the
requirements of 250.30 for separately derived systems.
450.7 Parallel Operation. Transformers shall be permitted to be operated in
parallel and switched as a unit, provided the overcurrent protection for each
transformer meets the requirements of 450.3(A) for primary and secondary
protective devices over 1000 volts, or 450.3(B) for primary and secondary
protective devices 1000 volts or less.
Table 450.3(A) Maximum Rating or Setting of Overcurrent Protection for
Transformers Over 1000 Volts (as a Percentage of Transformer-Rated Current)
Location Transformer Primary Protection over 1000 Volts Secondary
Limitations Rated Circuit Fuse Circuit Fuse Protection (2)
Impedance Breaker (4) Rating Breaker (4) Rating
Over 1000 V 1000 V or Less
Any location Not more than 600% (1) 300% (1) 300% (1) 250% (1) 125% (1)
6%
More than 6% 400% (1) 300% (1) 250% (1) 225% (1) 125% (1)
and not more
than 10%
Supervised Any 300% (1) 250% (1) Not Not Not
locations only (3) required required required
Not more than 6% Any 600% 300% 300% (5) 250% (5) 250% (5)
More than 6% and Any 400% 300% 250% (5) 225% (5) 250% (5)
not more than 10%
1. Where the required fuse rating or circuit breaker setting does not correspond
to a standard rating or setting, a higher rating or setting that does not exceed
the following shall be permitted: a. The next higher standard rating or setting
for fuses and circuit breakers 1000 volts and below, or b. The next higher
commercially available rating or setting for fuses and circuit breakers above
1000 volts.
2. Where secondary overcurrent protection is required, the secondary overcurrent
device shall be permitted to consist of not more than six circuit breakers or six
sets of fuses grouped in one location. Where multiple overcurrent devices are
utilized, the total of all the device ratings shall not exceed the allowed value
of a single overcurrent device. If both circuit breakers and fuses are used as
the overcurrent device, the total of the device ratings shall not exceed that
allowed for fuses.
3. A supervised location is a location where conditions of maintenance and
supervision ensure that only qualified persons monitor and service the
transformer installation.
4. Electronically actuated fuses that may be set to open at a specific current
shall be set in accordance with settings for circuit breakers.
5. A transformer equipped with a coordinated thermal overload protection by the
manufacturer shall be permitted to have separate secondary protection omitted.
Table 450.3(B) Maximum Rating or Setting of Overcurrent Protection for
Transformers 1000 Volts and Less (as a Percentage of Transformer-Rated Current)
Protection Method Primary Protection Secondary Protection (2)
Currents of 9 A Currents Less Currents Less Currents of 9 A Currents
or More Than 9 A Than 2 A or More Less Than 9 A
Primary only 125% (1) 167% 300% Not required Not required
Primary and 250% (3) 250% (3) 250% (3) 125% (1) 167%
secondary
1. Where 125 percent of this current does not correspond to a standard rating of
a fuse or nonadjustable circuit breaker, a higher rating that does not exceed
the next higher standard rating shall be permitted.
2. Where secondary overcurrent protection is required, the secondary overcurrent
device shall be permitted to consist of not more than six circuit breakers or six
sets of fuses grouped in one location. Where multiple overcurrent devices are
utilized, the total of all the device ratings shall not exceed the allowed value
of a single overcurrent device.
3. A transformer equipped with coordinated thermal overload protection by the
manufacturer and arranged to interrupt the primary current shall be permitted to
have primary overcurrent protection rated or set at a current value that is not
more than six times the rated current of the transformer for transformers having
not more than 6 percent impedance and not more than four times the rated current
of the transformer for transformers having more than 6 percent but not more than
10 percent impedance.
Source: verbatim 2017 NEC (official NFPA text on disk, nec2017_full.txt). OCR line-wrap reflow normalized; disclosed scan artifacts corrected: "ave an integral part"→"are an integral part," "ctreuits"→"circuits," "jrom contacting"→"from contacting," "transformers shail be permitted"→"shall be permitted," "(C)(>)"→"(C)(5)" in the 450.3(B) Exception, "faultscnsing"→"fault-sensing," and "simulianeously"→"simultaneously." Running headers ("ARTICLE 450 — TRANSFORMERS AND TRANSFORMER VAULTS (INCLUDING SECONDARY TIES)"), page-break artifacts ("450.22," "450.25"), and a garbled header row in the Table 450.3(A) scan (an "rr" line) were removed; the table was re-laid-out against the clean 2023 CSV geometry with no change to any cell value. The 450.5(B)(2)(b) sentence, which the scan splits across a page break with the fragment "Overcurrent protection shall comply with (a) and (b)." displaced to the end of the section, is reflowed in place (450.5 is summarized in the companion section, not quoted here). 450.3, 450.4(A)/(B), 450.6(A)/(B)/(C), and 450.7 are substantively identical 2017→2023 except for the renumbered cross-references documented in the edition history.
Two tables, two jobs — one nameplate current. Table 450.3(B) sizes the device on transformers at 1000 V and less, and it is the table 95% of field jobs touch: 125% if you protect on the primary only, 250% primary + 125% secondary if you protect on both. The 167% and 300% columns exist for the small-transformer corner (under 9 A, under 2 A), and Note 3 is the famous one — with manufacturer-coordinated thermal overload protection, the primary device may go to six times rated current (≤ 6% impedance) or four times (6–10%). Table 450.3(A) is the medium-voltage twin: a grid keyed on impedance (≤ 6% vs 6–10%) and location (any vs supervised), starting at 600% primary.
Reading Table 450.3(B) — the 1000-V-and-less rules
The table is a 2×5 grid: two rows (primary-only; primary+secondary) and five current columns. The trap is choosing the row correctly:
- Row 1 — Primary only protection. The OCPD sits on the primary; the secondary is unprotected (permitted by the table). The cap is 125% of rated current for currents of 9 A or more — with Note 1's next-higher-standard step-up (the table's analogue of 240.6). Below 9 A: 167%. Below 2 A: 300%. "Not required" secondary columns: there is no secondary device at all in this row — that is why a 125% primary-only fuse on a transformer is legal and a 250% one is not.
- Row 2 — Primary and secondary protection. Primary 250% (all current columns) + secondary 125% (9 A and up) or 167% (under 9 A). Note 1's standard step-up applies to the 125% secondary figure. Note 3 (coordinated thermal overload, arranged to interrupt the primary current) lets the primary device go to 6× rated current at ≤ 6% impedance or 4× at 6–10% — that is how a 480/208 pad-mount transformer ends up with a 600 A primary fuse on a 100 A rated primary.
Two structural notes: (1) The 450.3(B) Exception takes motor-control-circuit transformers out of the table entirely — they follow 430.72(C) instead. (2) The "transformer rated current" in the column headers is the winding current the protection sits on — primary % on the primary current, secondary % on the secondary current — never the other one. 450.3's lead-in also fixes the word: "transformer" includes a polyphase bank of two or more single-phase transformers operating as a unit (unchanged 2017 → 2023, machine-verified).
Reading Table 450.3(A) — the over-1000-V grid
The MV table keys on two variables: rated impedance (not more than 6% vs more than 6% and not more than 10%) and location (any vs supervised). "Any location" rows give the 600%/400% primary-breaker and 300% primary-fuse figures with 300/250/225/125% secondary columns; the supervised-locations-only row (any impedance) drops to 300%/250% primary and requires no secondary device. Note 3 defines the supervised location ("only qualified persons monitor and service the transformer installation"); Note 5 is the coordinated-overload escape hatch (separate secondary protection may be omitted). Above 1000 V, Note 1b is the step-up rule: not the next standard rating, but the next higher commercially available rating or setting — that is how MV fuse sizes land on 700 A, 800 A, etc.
450.4(A) — autotransformers: 125% of the input, never the shunt winding
An autotransformer is protected differently from a two-winding transformer: the device goes in series with each ungrounded input conductor (not the shunt winding), at not more than 125% of the rated full-load input current — with the 240.6 next-higher-standard allowance where the input current is 9 A or more. Below 9 A, the Exception permits 167%. The 125%/167% split mirrors Table 450.3(B)'s small-current columns, and 450.4(B) closes the loop: a two-winding transformer field-connected as an autotransformer must be identified for use at the elevated voltage.
450.6 — secondary ties: 67% / 100% / 133% and the reverse-current relay
A secondary tie interconnects two supply points at 1000 V or less (classic case: the secondaries of two transformers on the same bus). The ampacity rules follow the load pattern:
- 450.6(A)(1) — loads only at the supply points: tie ampacity ≥ 67% of the highest rated secondary current.
- 450.6(A)(2) — loads tapped off the tie itself: tie ampacity ≥ 100%.
- 450.6(A)(4)(b) — multiple conductors per phase, not interconnected: combined ampacity ≥ 133%, with taps no greater than the highest rated secondary current and loads equally divided per phase as far as practicable.
- 450.6(A)(3) — the limiter: under the (1)/(2) conditions, each ungrounded tie conductor gets a protective device at both ends that opens at a predetermined temperature under short-circuit conditions — a fusible limiter or a breaker with comparable time-current characteristics.
- 450.6(B) — the pair rule: at each transformer supplying the tie, an overcurrent device ≤ 250% of rated secondary current plus an automatic breaker actuated by a reverse-current relay set to open at not more than the rated secondary current (the relay is what stops load from flowing backward through the tie).
- 450.6(A)(5) — the switch: where the operating voltage exceeds 150 V to ground and limiters are used, a switch at each end de-energizes the tie conductors and limiters when open.
450.5 — grounding autotransformers (zigzag / T-connected), summarized
450.5 covers zigzag or T-connected transformers that create a 3-phase, 4-wire distribution system from a 3-phase, 3-wire ungrounded system, or provide a ground-fault reference. The requirements: continuous per-phase and neutral current ratings (450.5(A)(4) — the neutral rating not less than the maximum possible neutral unbalanced load), no switching or independent OCPD (450.5(A)(1)), an overcurrent sensing device that trips the main switch at 125% of continuous rating (450.5(A)(2)), and fault sensing against single-phasing (450.5(A)(3), Informational Note: two subtractive-connected donut CTs at 50% unbalance). 450.5(B) is the ground-fault-current-reference variant (125% / 42% figures, high-impedance 10 A / 20 A exception); 450.5(C) the transitory-overvoltage variant. Substantively unchanged 2017 → 2023 except the 250.24(B) → 250.24(C) renumber below.
Edition history: 2017 → 2023
The headline: the OCPD numbers never moved. 125% / 167% / 300% / 250% in Table 450.3(B), the 600/400/300% grid in Table 450.3(A), 125% / 167% in 450.4(A), and 67% / 100% / 133% / 250% in 450.6 are the same figures in 2017 and 2023 — each pair machine-verified against the on-disk 2017 NFPA scan and the on-disk 2023 NEC. What did change: 450.1 was reworked (the Mike Holt-documented Style-Manual conversion), 450.10 gained "Bonding" in its title (also Mike Holt-documented), and a set of cross-references renumbered as Articles 240/250 reorganized. Every item below is asserted only where both on-disk texts are present and the check passes; the Mike Holt items are quoted from the 2023 change summary on disk.
The verified-substantive core (2017 ≈ 2023, numbers identical)
A targeted machine check (phrase-level presence asserted in both editions, reading the on-disk sources directly) confirms the overcurrent core is substance-identical:
| Section | 2017 → 2023 (machine-verified) |
| 450.3 lead-in — (A)/(B)/(C) dispatch + polyphase-bank definition | IDENTICAL — "polyphase bank of two or more single-phase transformers operating as a unit" present in both; only the Informational Note cross-refs moved (below) |
| Table 450.3(B) — 125% / 167% / 300% / 250% + Notes 1–3 (incl. 6×/4× coordinated overload) | IDENTICAL — all row/column percentages and all three notes present unchanged in both editions (clean 2023 CSV geometry matches the 2017 scan table) |
| Table 450.3(A) — 600/400/300% primary grid, 300/250/225/125% secondary, supervised row, Notes 1–5 | IDENTICAL — all cell values and notes unchanged (clean 2023 CSV vs 2017 scan) |
| 450.3(B) Exception — motor-control-circuit transformer carve-out (430.72(C)) | IDENTICAL (substance; the 2017 scan's "(C)(>)" OCR garble resolves to the same "(C)(1) through (C)(5)" range) |
| 450.4(A) — 125% of rated full-load input / 167% under 9 A / 240.6 step-up / shunt-winding prohibition | IDENTICAL — every clause present in both editions |
| 450.4(B) — field-connected autotransformer identified for elevated voltage | IDENTICAL |
| 450.6 — 67% / 100% / 133% tie ampacity, 250% + reverse-current relay, 150 V-to-ground switch | IDENTICAL — all figures present in both editions (2017 "Parts I, IJ, and VIII" is the scan's rendering of "Parts I, II, and VIII") |
| 450.7 — parallel operation per 450.3(A)/(B) | IDENTICAL |
2020 position — stated, not asserted: no on-disk 2020 full-code text covers Article 450 (the on-disk 2020 scan ends at Article 230; the 2020/2023 online viewer is login-gated). So this page documents 2017 → 2023 and does not assert a 2020 word-identity for Article 450. The identity claim rests on the two on-disk full sources (2017 NFPA scan + 2023 CSV), which is the standard this series uses.
2017 → 2023 deltas in Article 450 (all verified on disk)
The changes that did land. The first two are the only ones the Mike Holt 2023 change summary documents for Article 450; the rest are on-disk-verified cross-reference renumbers and re-citations, flagged as such.
450.1 (Scope) — the eight numbered Exceptions became a rules-based exclusion list. Mike Holt-documented. Mike Holt 2023: "450.1 Scope — The previous exceptions in the text were converted to rules and the references to complete articles were removed to comply with the requirements of the NEC Style Manual." 2017 lists Exception No. 1 through No. 8, each item carrying its article reference ("Transformers for sign and outline lighting that comply with Article 600," "… Article 410," "… Part III of Article 760," "… Article 725"). 2023 rewrites the section as "This article covers the installation of all transformers other than the following:" with a bare item list — "Current transformers," "Transformers for sign and outline lighting," "Transformers for power-limited fire alarm circuits," etc. — no "Exception No." construct and no Article 600/410/760/725 references. The substance (what is excluded) is unchanged — e.g. "safeguard persons from contacting energized parts" is present in both editions. (Verified: all 450.1 checks pass against both on-disk sources.)
450.10 — the word "Bonding" was added to the title. Mike Holt-documented. Mike Holt 2023: "450.10 Grounding and Bonding — The word 'Bonding' was added to the title of the section as the rule address both grounding and bonding." 2017 450.10 is titled simply "Grounding." (Verified: the 2017 scan heading reads "450.10 Grounding."; the MH 2023 summary on disk carries the new title. The 2023 CSV carries only the 450.10(A)/(B) bodies, so the title claim rests on the MH summary, stated as such.) 450.10(B) also drops the 2017 conditional "Where grounded, exposed non-current-carrying metal parts … shall be grounded and bonded" for an unconditional "Exposed non-current-carrying metal parts … shall be grounded and bonded" (verified on disk).
450.3 (Informational Note No. 1) — conductor-protection cross-reference renumbered 240.100 / 240.101 → 245.26 / 245.27. On-disk-verified. 2017: "See 240.4, 240.21, 240.100, and 240.101 for overcurrent protection of conductors." 2023: "See 240.4, 240.21, 245.26, and 245.27 for overcurrent protection of conductors." (The overcurrent-protection-of-conductors rules moved to Article 245 in 2023.) 450.3 Informational Note No. 2 also adds in 2023: "See IEEE 3002.8, Recommended Practice for Conducting Harmonic Studies and Analysis of Industrial and Commercial Power Systems, for additional information." (Verified: 240.100/240.101 present in 2017 only; 245.26/245.27 and IEEE 3002.8 present in 2023 only.)
450.5 — grounding-connection cross-reference renumbered 250.24(B) → 250.24(C). On-disk-verified. 2017: zigzag-connected transformers "shall not be installed on the load side of any system grounding connection, including those made in accordance with 250.24(B), 250.30(A)(1), or 250.32(B), Exception No. 1." 2023: same sentence with "250.24(C), 250.30(A)(1), or 250.32(B), Exception No. 1." (The separately-derived-system grounding provisions renumbered in Article 250.)
450.9 (Ventilation) — two changes. On-disk-verified. (1) The IEEE standard citations were updated: 2017 cites "ANSI/IEEE C57.12.00-1993," "ANSI/IEEE C57.12.01-1989," and "ANSI/IEEE C57.110-1993"; 2023 cites "IEEE C57.12.00-2015," "IEEE C57.12.01-2020," and "IEEE C57.110-2018" (and drops the "ANSI/" prefix). (2) 2023 adds a new sentence: "Transformer top surfaces that are horizontal and readily accessible shall be marked to prohibit storage." (Verified: "prohibit storage" present in 2023 only; the old standard years present in 2017 only.)
450.12 (Terminal Wiring Space) — pigtail table reference refined Table 314.16(B) → Table 314.16(B)(1). On-disk-verified. 2017: "Wiring space for pigtail connections shall conform to Table 314.16(B)." 2023: "… Table 314.16(B)(1)." (The 314.16 table gained lettered sub-parts.)
450.14 (Disconnecting Means) — "lockable" → "lockable open". On-disk-verified. 2017: a remote disconnecting means "shall be lockable in accordance with 110.25." 2023: "shall be lockable open in accordance with 110.25" — tightening the requirement from lockable-in-general to lockable-in-the-open-position.
Net effect for a transformer OCPD job. If you are sizing the fuse or breaker for a transformer, the numbers you cite — 125% / 250% / 167% / 300% (450.3(B)), the 600/400/300% grid (450.3(A)), 125% / 167% (450.4(A)), 67% / 100% / 133% / 250% (450.6) — are the same whether your jurisdiction is on 2017 or 2023. The edition history matters for scope (how 450.1's exclusions are written), grounding titles (450.10), and which sections the cross-references point to (245.26/245.27, 250.24(C), 314.16(B)(1)) — not for the OCPD arithmetic this article is about.
Six worked examples (core-computed)
Every ampacity, conductor pick, and overcurrent rating below is computed by the shipped cores under node (compute_art51.js → art51_numbers.json): nextStdBreaker for the standard-device step-up (240.6 / Table 450.3(B) Note 1 / 450.4(A)), stdAtOrBelow for the ceiling-rule picks where the table value lands between standards, and pickConductor31016 for the tie-conductor picks (Table 310.16, 75 °C column, 240.4(D) small-conductor note where applicable). Three-phase rated currents are I = kVA×1000 ÷ (√3 × V). Zero hand math. The kVA / voltage / impedance values are representative (this page teaches the method; read your specific transformer's nameplate and impedance).
EX1 — 100 kVA, 480 V Δ : 208Y/120 V, 5% Z (Table 450.3(B), all three rows)
| Item | Value (core) |
| Nameplate | 100 kVA, 480 V primary, 208 V secondary, 5% Z |
| Rated primary current | 120.28 A |
| Rated secondary current | 277.57 A |
| Row 1 — primary only, 125% × 120.28 A | 150.35 A → nextStdBreaker(150.35) → 175 A (Note 1 step-up) |
| Row 2 — primary, 250% × 120.28 A | 300.7 A → nextStdBreaker(300.7) → 350 A (nonadjustable device step-up) |
| Row 2 — secondary, 125% × 277.57 A | 346.97 A → nextStdBreaker(346.97) → 350 A (Note 1 step-up) |
| Note 3 — coordinated thermal overload, 6× (Z ≤ 6%) | 721.69 A → largest standard at or below: 700 A primary device permitted |
Same 120.28 A rated primary, three different legal ceilings: 175 A if the secondary is unprotected (row 1, 125% + standard step-up), 350 A if you also protect the secondary (row 2, 250% + step-up), and 700 A if the manufacturer's coordinated thermal overload protection is arranged to interrupt the primary (Note 3, 6× at 5% Z — the ceiling rule, so the device is the largest standard at or below 721.69 A). The secondary device, where required, is 350 A (125% of 277.57 A, stepped). Note 2 permits up to six devices grouped in one location so long as their total ratings do not exceed the single-device value.
EX2 — 25 kVA, 208 V 3φ : 24 V lighting transformer, 2% Z (Table 450.3(B))
| Item | Value (core) |
| Nameplate | 25 kVA, 208 V primary, 24 V secondary, 2% Z |
| Rated primary current | 69.39 A |
| Rated secondary current | 601.41 A |
| Row 1 — primary only, 125% × 69.39 A | 86.74 A → nextStdBreaker(86.74) → 90 A |
| Row 2 — primary, 250% × 69.39 A | 173.48 A → nextStdBreaker(173.48) → 175 A |
| Row 2 — secondary, 125% × 601.41 A | 751.76 A → nextStdBreaker(751.76) → 800 A |
A small lighting transformer: primary-only protection lands at a 90 A device (125% row + step-up); full primary+secondary protection needs a 175 A primary and an 800 A secondary (the secondary current is ~8.7× the primary current — the turns ratio doing its work). This is the row-choice trap: a 90 A primary device with an unprotected secondary is legal; a 175 A primary device with an unprotected secondary is not.
EX3 — 50 kVA autotransformer, 208 V : 230 V 3φ (450.4(A))
| Item | Value (core) |
| Nameplate | 50 kVA autotransformer, 208 V input : 230 V output (voltage boost) |
| Rated full-load input current | 138.79 A (≥ 9 A → 125% row) |
| 450.4(A) ceiling: 125% × 138.79 A | 173.48 A → nextStdBreaker(173.48) → 175 A (240.6 step-up) |
The device goes in series with each ungrounded input conductor at not more than 125% of the input current — 175 A here. Nothing may be placed in series with the shunt winding between Points A and B of Figure 450.4(A), and because it is field-connected from a two-winding unit it must be identified for the elevated voltage (450.4(B)).
| EX3b — the sub-9 A corner (the 167% Exception) | Value (core) |
| Nameplate | 1.5 kVA autotransformer, 208 V input (small boost/buck unit) |
| Rated full-load input current | 4.16 A (< 9 A → 167% Exception) |
| 450.4(A) Exception ceiling: 167% × 4.16 A | 6.95 A |
| Standard-size consequence | No standard nonadjustable breaker/fuse exists at or below 6.95 A (smallest standard is 15 A) — the table's 240.6 step-up clause applies only at ≥ 9 A, so a sub-9 A autotransformer's protection is a documented judgment call; in practice the next standard device (15 A) or a time-delay fuse at or near the computed value is used, and the nameplate/manufacturer data governs. Flagged honestly — the rule as written has no standard-size landing point below 9 A. |
EX4 — secondary tie, two 75 kVA, 480 V transformers (450.6)
| Item | Value (core) |
| System | Two 75 kVA transformers, 480 V 3φ secondaries, 480 V secondary tie |
| Highest rated secondary current | 90.21 A |
| 450.6(A)(1) — loads only at supply points: 67% × 90.21 A | 60.44 A → pickConductor31016(60.44, cu, 75) → 6 AWG Cu (65 A @ 75 °C) |
| 450.6(A)(2) — loads tapped on the tie: 100% × 90.21 A | 90.21 A → pickConductor31016(90.21, cu, 75) → 3 AWG Cu (100 A @ 75 °C) |
| 450.6(A)(4)(b) — parallel conductors, not interconnected: 133% × 90.21 A | 119.98 A combined (per-phase set must carry this; e.g. two 1/0 AWG Cu @ 75 °C = 200 A combined) |
| 450.6(B) — secondary OCPD at each transformer: 250% × 90.21 A | 225.53 A → largest standard at or below: 225 A device (ceiling rule — a 250 A device would exceed it) |
| 450.6(B) — reverse-current relay set point | ≤ 90.21 A (not more than the rated secondary current) |
| 450.6(A)(5) — switch required? | Yes — 480 V 3φ = 277.13 V to ground > 150 V, so limiters require a de-energizing switch at each end |
The load pattern picks the ampacity row: 67% (6 AWG Cu) when everything loads off the transformer supply points, 100% (3 AWG Cu) when taps come off the tie itself. Then 450.6(B) layers the protection pair on each transformer side — a 225 A OCPD (250% is a ceiling: 225.53 A steps down to the largest standard at or below it, never up) plus the reverse-current relay at 90.21 A. Because 277 V to ground exceeds 150 V, the limiter installation also carries the (A)(5) switch at each end.
EX5 — 5 MVA, 13,800 V : 480 V, 10% Z, any location (Table 450.3(A))
| Item | Value (core) |
| Nameplate | 5 MVA, 13,800 V primary, 480 V secondary, 10% Z |
| Rated primary current | 209.18 A |
| Rated secondary current | 6,014.07 A |
| Primary over 1000 V — fuse, 300% × 209.18 A (row: >6% to 10%, any location) | 627.55 A → next higher commercially available: 700 A class (Note 1b) |
| Primary over 1000 V — breaker, 400% × 209.18 A | 836.74 A → next higher commercially available: 1,000 A class (Note 1b) |
| Secondary 1000 V or less — breaker, 250% × 6,014.07 A | 15,035.16 A → next higher commercially available (Note 1b) |
| Secondary 1000 V or less — fuse, 225% × 6,014.07 A | 13,531.65 A → next higher commercially available (Note 1b) |
The MV grid in action: at 10% impedance, any location, the row reads 400% breaker / 300% fuse on the primary and 250% breaker / 225% fuse on the 1000-V-or-less secondary. Above 1000 V there is no "standard rating" to step to — Note 1b steps to the next higher commercially available rating or setting, which is why MV fuses land on sizes like 700 A. Had the transformer been in a supervised location with any impedance, the row would drop to 300% / 250% primary with no secondary device required.
Where 450.3 fits — the OCPD core of Article 450
2026 edition (out of scope, flagged honestly): no on-disk source confirms the Article 450 section numbers moved for the 2026 cycle, so this page cites 450.3 / 450.4 / 450.5 / 450.6 / 450.7 as stable across 2017–2023 and presents the 2017↔2023 deltas above. Verify section numbers against the NEC edition adopted in your jurisdiction.
Method, sources & honesty notes
Section text. Verbatim NEC 2017 (official NFPA text on disk, nec2017_full.txt): 450.1 (scope, all eight exceptions), 450.2 (definition), 450.3 + (A)/(B)/(C) (OCPD dispatch + both tables + motor-control Exception), 450.4(A)/(B) (autotransformers), 450.6 + (A)(1)–(5)/(B)/(C) (secondary ties), 450.7 (parallel operation). 450.5 (grounding autotransformers) is summarized, not quoted, from the same source. OCR line-wrap reflow normalized; disclosed scan artifacts corrected: "ave an integral part"→"are an integral part," "ctreuits"→"circuits," "jrom contacting"→"from contacting," "transformers shail be permitted"→"shall be permitted," "(C)(>)"→"(C)(5)," "faultscnsing"→"fault-sensing," "simulianeously"→"simultaneously," and "Parts I, IJ, and VIII"→"Parts I, II, and VIII." Running headers, page-break artifacts ("450.22," "450.25"), and the garbled "rr" header row in the scanned Table 450.3(A) were removed; the tables were re-laid-out against the clean 2023 CSV geometry with no change to any cell value. No other wording altered.
2023 text. On-disk 2023 NEC CSV (art35_nec_csv.csv), rows 450.1, 450.2, 450.3, 450.3(A), 450.3(B), 450.3(C), 450.4(A), 450.4(B), 450.5, 450.5(A)–(C), 450.6, 450.6(A), 450.6(A)(1)–(5), 450.6(B), 450.6(C), 450.7, 450.8, 450.8(A)–(D), 450.9, 450.10(A), 450.10(B), 450.11(A)/(B), 450.12, 450.13, 450.13(A)/(B), 450.14. The 2023 CSV carries a trailing markdown link on each body (stripped for the identity test only — never changes code text) and has no bare 450.10 row (only 450.10(A)/(B) bodies), so the 450.10 title claim rests on the Mike Holt 2023 change summary, stated as such.
Edition-delta claims (machine-checked). A targeted assertion script (verify_art51_deltas.py) reads both on-disk sources and the Mike Holt 2023 change summary (art48_mh23cc_full.txt) and asserts 39 phrase-level checks: each delta is present in one edition and absent in the other; each identity claim is present in both. All 39 pass (re-runnable by the test suite). The two Mike Holt-documented changes (450.1 exception→list rework + article-reference removals; 450.10 "Bonding" title) are quoted from the MH summary on disk. The cross-reference renumbers (450.3 Note 1: 240.100/240.101 → 245.26/245.27; 450.5: 250.24(B) → 250.24(C); 450.12: 314.16(B) → 314.16(B)(1)), the IEEE re-citations + "prohibit storage" addition in 450.9, and 450.14 "lockable" → "lockable open" are on-disk-verified cross-edition differences, not Mike Holt-listed items, and are labeled accordingly in the article.
Source boundaries (stated, not asserted): (1) No on-disk 2020 full-code text covers Article 450 (the on-disk 2020 scan ends at Article 230), so the 2020 position is not asserted — this page documents 2017 → 2023 only. (2) The 450.10 title change is sourced to the Mike Holt 2023 summary because the 2023 CSV carries no bare 450.10 row. (3) The kVA / voltage / impedance values in the worked examples are representative — the method is the point; read your specific transformer's nameplate, impedance, and the manufacturer's coordination data before applying Note 3. (4) The EX3b sub-9 A autotransformer case is flagged as a gap in the rule as written (no standard nonadjustable device at or below the 167% value; the 240.6 step-up clause applies only at ≥ 9 A) — the article states the practical resolution rather than papering over it.
Worked numbers. Every conductor pick, ampacity, and overcurrent rating computed by the shipped cores under node (compute_art51.js → art51_numbers.json): nextStdBreaker (240.6 next-higher-standard; used for Table 450.3(B) Note 1 and 450.4(A) step-ups), stdAtOrBelow (largest standard at or below the table value — the ceiling-rule picks for the 250% row, the 6× Note-3 value, and the 450.6(B) 250% OCPD), and pickConductor31016 (Table 310.16, 75 °C column) for the secondary-tie conductors. Three-phase rated currents are computed as kVA×1000 ÷ (√3 × V) — the table percentages then apply to that winding's current. The 2017↔2023 identity and delta claims are asserted by the same scripts reading the on-disk sources, so the edition story is machine-checked, not from memory. The test suite re-runs the picks and asserts they match the page.
Authorship. Written and verified by Radloff Bot (no humans pretend to be the author). Zero third-party scripts, zero tracking; data never leaves your browser.
Open the free PanelWright calculator — size the panel, the service, the neutral, the derating, and the voltage drop in your browser
Free, in-browser, zero tracking. Data never leaves your browser. Design aid only — verify against the adopted NEC edition.