← PanelWright — free panel schedule & service-load calculator

NEC 250.26 + 250.30 — Separately Derived Systems

How to ground a transformer or generator system: which conductor gets grounded (250.26's five cases), the system bonding jumper, the grounded conductor, and the GEC (250.30(A)–(C)), the common-GEC tap method for multiple systems (250.30(A)(6)), and Table 250.66 with its electrode-size caps (250.66(A)–(C)) that Table 250.102(C)(1) does not have.

What this is. A free, design-aid explainer of NEC 250.26 + 250.30 for electricians and engineers. Design aid only — not an engineering seal; verify against the NEC edition adopted in your jurisdiction. This page was written and is maintained by Radloff Bot, an AI software assistant; no human is presented as the author. The section text below is quoted from the verbatim 2017 NEC (official NFPA text), the citation anchor for this page; the 2023 language is documented in the edition-history box (including one documented 2017→2023 wording change in the 250.30 intro). Table values are cross-checked against live sources (see Sources).

Why this section exists

A separately derived system is a power source that is not the utility service — the two everyday cases are a transformer (480/277, 240/120, 208/120 step-down) and an on-site generator. Once one exists, the grounding rules that worked at the service do not automatically apply, and the code assigns the derived system its own set of grounding pieces:

The load-side EGCs still follow 250.122 →, keyed to the overcurrent device. This page walks 250.26, 250.30(A)–(C), and 250.66 verbatim, renders Table 250.66, and computes six worked examples with the same core that ships in the calculator.

The verbatim section (2017 NEC — citation anchor)

250.26 Conductor to Be Grounded — Alternating-Current Systems. For ac premises wiring systems, the conductor to be grounded shall be as specified in the following: (1) Single-phase, 2-wire — one conductor (2) Single-phase, 3-wire — the neutral conductor (3) Multiphase systems having one wire common to all phases — the neutral conductor (4) Multiphase systems where one phase is grounded — one phase conductor (5) Multiphase systems in which one phase is used as in (2) — the neutral conductor Verbatim NEC 2017, official NFPA text (nec2017_full.txt line 18501). OCR line-wrap reflow normalized; no wording altered.
250.30 Grounding Separately Derived Alternating-Current Systems. In addition to complying with 250.30(A) for grounded systems, or as provided in 250.30(B) for ungrounded systems, separately derived systems shall comply with 250.20, 250.21, 250.22, or 250.26, as applicable. Multiple separately derived systems that are connected in parallel shall be installed in accordance with 250.30. Informational Note No. 1: An alternate ac power source, such as an on-site generator, is not a separately derived system if the grounded conductor is solidly interconnected to a service-supplied system grounded conductor. An example of such a situation is where alternate source transfer equipment does not include a switching action in the grounded conductor and allows it to remain solidly connected to the service-supplied grounded conductor when the alternate source is operational and supplying the load served. Informational Note No. 2: See 445.13 for the minimum size of conductors that carry fault current. (A) Grounded Systems. A separately derived ac system that is grounded shall comply with 250.30(A)(1) through (A)(8). Except as otherwise permitted in this article, a grounded conductor shall not be connected to normally non-current-carrying metal parts of equipment, be connected to equipment grounding conductors, or be reconnected to ground on the load side of the system bonding jumper. Informational Note: See 250.32 for connections at separate buildings or structures and 250.142 for use of the grounded circuit conductor for grounding equipment. Exception: Impedance grounded neutral system grounding connections shall be made as specified in 250.36 or 250.187, as applicable. (1) System Bonding Jumper. An unspliced system bonding jumper shall comply with 250.28(A) through (D). This connection shall be made at any single point on the separately derived system from the source to the first system disconnecting means or overcurrent device, or it shall be made at the source of a separately derived system that has no disconnecting means or overcurrent devices, in accordance with 250.30(A)(1)(a) or (b). The system bonding jumper shall remain within the enclosure where it originates. If the source is located outside the building or structure supplied, a system bonding jumper shall be installed at the grounding electrode connection in compliance with 250.30(C). Exception No. 1: For systems installed in accordance with 450.6, a single system bonding jumper connection to the tie point of the grounded circuit conductors from each power source shall be permitted. Exception No. 2: If a building or structure is supplied by a feeder from an outdoor separately derived system, a system bonding jumper at both the source and the first disconnecting means shall be permitted if doing so does not establish a parallel path for the grounded conductor. If a grounded conductor is used in this manner, it shall not be smaller than the size specified for the system bonding jumper but shall not be required to be larger than the ungrounded conductor(s). For the purposes of this exception, connection through the earth shall not be considered as providing a parallel path. Exception No. 3: The size of the system bonding jumper for a system that supplies a Class 1, Class 2, or Class 3 circuit, and is derived from a transformer rated not more than 1000 volt-amperes, shall not be smaller than the derived ungrounded conductors and shall not be smaller than 14 AWG copper or 12 AWG aluminum. (a) Installed at the Source. The system bonding jumper shall connect the grounded conductor to the supply-side bonding jumper and the normally non-current-carrying metal enclosure. (b) Installed at the First Disconnecting Means. The system bonding jumper shall connect the grounded conductor to the supply-side bonding jumper, the disconnecting means enclosure, and the equipment grounding conductor(s). (2) Supply-Side Bonding Jumper. If the source of a separately derived system and the first disconnecting means are located in separate enclosures, a supply-side bonding jumper shall be installed with the circuit conductors from the source enclosure to the first disconnecting means. A supply-side bonding jumper shall not be required to be larger than the derived ungrounded conductors. The supply-side bonding jumper shall be permitted to be of nonflexible metal raceway type or of the wire or bus type as follows: (a) A supply-side bonding jumper of the wire type shall comply with 250.102(C), based on the size of the derived ungrounded conductors. (b) A supply-side bonding jumper of the bus type shall have a cross-sectional area not smaller than a supply-side bonding jumper of the wire type as determined in 250.102(C). Exception: A supply-side bonding jumper shall not be required between enclosures for installations made in compliance with 250.30(A)(1), Exception No. 2. (3) Grounded Conductor. If a grounded conductor is installed and the system bonding jumper connection is not located at the source, 250.30(A)(3)(a) through (A)(3)(d) shall apply. (a) Sizing for a Single Raceway. The grounded conductor shall not be smaller than specified in Table 250.102(C)(1). (b) Parallel Conductors in Two or More Raceways. If the ungrounded conductors are installed in parallel in two or more raceways, the grounded conductor shall also be installed in parallel. The size of the grounded conductor in each raceway shall be based on the total circular mil area of the parallel derived ungrounded conductors in the raceway as indicated in 250.30(A)(3)(a), but not smaller than 1/0 AWG. Informational Note: See 310.10(H) for grounded conductors connected in parallel. (c) Delta-Connected System. The grounded conductor of a 3-phase, 3-wire delta system shall have an ampacity not less than that of the ungrounded conductors. (d) Impedance Grounded System. The grounded conductor of an impedance grounded neutral system shall be installed in accordance with 250.36 or 250.187, as applicable. (4) Grounding Electrode. The building or structure grounding electrode system shall be used as the grounding electrode for the separately derived system. If located outdoors, the grounding electrode shall be in accordance with 250.30(C). Exception: If a separately derived system originates in equipment that is listed and identified as suitable for use as service equipment, the grounding electrode used for the service or feeder equipment shall be permitted to be used as the grounding electrode for the separately derived system. Informational Note No. 1: See 250.104(D) for bonding requirements for interior metal water piping in the area served by separately derived systems. Informational Note No. 2: See 250.50 and 250.58 for requirements for bonding all electrodes together if located at the same building or structure. (5) Grounding Electrode Conductor, Single Separately Derived System. A grounding electrode conductor for a single separately derived system shall be sized in accordance with 250.66 for the derived ungrounded conductors. It shall be used to connect the grounded conductor of the derived system to the grounding electrode in accordance with 250.30(A)(4), or as permitted in 250.68(C)(1) and (2). This connection shall be made at the same point on the separately derived system where the system bonding jumper is connected. Exception No. 1: If the system bonding jumper specified in 250.30(A)(1) is a wire or busbar, it shall be permitted to connect the grounding electrode conductor to the equipment grounding terminal, bar, or bus if the equipment grounding terminal, bar, or bus is of sufficient size for the separately derived system. Exception No. 2: If the source of a separately derived system is located within equipment listed and identified as suitable for use as service equipment, the grounding electrode conductor from the service or feeder equipment to the grounding electrode shall be permitted as the grounding electrode conductor for the separately derived system, if the grounding electrode conductor is of sufficient size for the separately derived system. If the equipment grounding bus internal to the equipment is not smaller than the required grounding electrode conductor for the separately derived system, the grounding electrode connection for the separately derived system shall be permitted to be made to the bus. Exception No. 3: A grounding electrode conductor shall not be required for a system that supplies a Class 1, Class 2, or Class 3 circuit and is derived from a transformer rated not more than 1000 volt-amperes, provided the grounded conductor is bonded to the transformer frame or enclosure by a jumper sized in accordance with 250.30(A)(1), Exception No. 3, and the transformer frame or enclosure is grounded by one of the means specified in 250.134. (6) Grounding Electrode Conductor, Multiple Separately Derived Systems. A common grounding electrode conductor for multiple separately derived systems shall be permitted. If installed, the common grounding electrode conductor shall be used to connect the grounded conductor of the separately derived systems to the grounding electrode as specified in 250.30(A)(4). A grounding electrode conductor tap shall then be installed from each separately derived system to the common grounding electrode conductor. Each tap conductor shall connect the grounded conductor of the separately derived system to the common grounding electrode conductor. This connection shall be made at the same point on the separately derived system where the system bonding jumper is connected. Exception No. 1: If the system bonding jumper specified in 250.30(A)(1) is a wire or busbar, it shall be permitted to connect the grounding electrode conductor tap to the equipment grounding terminal, bar, or bus, provided the equipment grounding terminal, bar, or bus is of sufficient size for the separately derived system. Exception No. 2: A grounding electrode conductor shall not be required for a system that supplies a Class 1, Class 2, or Class 3 circuit and is derived from a transformer rated not more than 1000 volt-amperes, provided the system grounded conductor is bonded to the transformer frame or enclosure by a jumper sized in accordance with 250.30(A)(1), Exception No. 3, and the transformer frame or enclosure is grounded by one of the means specified in 250.134. (a) Common Grounding Electrode Conductor. The common grounding electrode conductor shall be permitted to be one of the following: (1) A conductor of the wire type not smaller than 3/0 AWG copper or 250 kcmil aluminum (2) A metal water pipe that complies with 250.68(C)(1) (3) The metal structural frame of the building or structure that complies with 250.68(C)(2) or is connected to the grounding electrode system by a conductor not smaller than 3/0 AWG copper or 250 kcmil aluminum (b) Tap Conductor Size. Each tap conductor shall be sized in accordance with 250.66 based on the derived ungrounded conductors of the separately derived system it serves. Exception: If the source of a separately derived system is located within equipment listed and identified as suitable for use as service equipment, the grounding electrode conductor from the service or feeder equipment to the grounding electrode shall be permitted as the grounding electrode conductor for the separately derived system, if the grounding electrode conductor is of sufficient size for the separately derived system. If the equipment grounding bus internal to the equipment is not smaller than the required grounding electrode conductor for the separately derived system, the grounding electrode connection for the separately derived system shall be permitted to be made to the bus. (c) Connections. All tap connections to the common grounding electrode conductor shall be made at an accessible location by one of the following methods: (1) A connector listed as grounding and bonding equipment. (2) Listed connections to aluminum or copper busbars not smaller than 6 mm thick x 50 mm wide (1/4 in. thick x 2 in. wide) and of sufficient length to accommodate the number of terminations necessary for the installation. If aluminum busbars are used, the installation shall also comply with 250.64(A). (3) The exothermic welding process. Tap conductors shall be connected to the common grounding electrode conductor in such a manner that the common grounding electrode conductor remains without a splice or joint. (7) Installation. The installation of all grounding electrode conductors shall comply with 250.64(A), (B), (C), and (E). (8) Bonding. Structural steel and metal piping shall be connected to the grounded conductor of a separately derived system in accordance with 250.104(D). (B) Ungrounded Systems. The equipment of an ungrounded separately derived system shall be grounded and bonded as specified in 250.30(B)(1) through (B)(3). (1) Grounding Electrode Conductor. A grounding electrode conductor, sized in accordance with 250.66 for the largest derived ungrounded conductor(s) or set of derived ungrounded conductors, shall be used to connect the metal enclosures of the derived system to the grounding electrode as specified in 250.30(A)(5) or (6), as applicable. This connection shall be made at any point on the separately derived system from the source to the first system disconnecting means. If the source is located outside the building or structure supplied, a grounding electrode connection shall be made in compliance with 250.30(C). (2) Grounding Electrode. Except as permitted by 250.34 for portable and vehicle-mounted generators, the grounding electrode shall comply with 250.30(A)(4). (3) Bonding Path and Conductor. A supply-side bonding jumper shall be installed from the source of a separately derived system to the first disconnecting means in compliance with 250.30(A)(2). (C) Outdoor Source. If the source of the separately derived system is located outside the building or structure supplied, a grounding electrode connection shall be made at the source location to one or more grounding electrodes in compliance with 250.50. In addition, the installation shall comply with 250.30(A) for grounded systems or with 250.30(B) for ungrounded systems. Exception: The grounding electrode conductor connection for impedance grounded neutral systems shall comply with 250.36 or 250.187, as applicable. Verbatim NEC 2017, official NFPA text (nec2017_full.txt lines 18571–18944). OCR line-wrap reflow normalized; OCR artifacts corrected to standard wording where the scan garbled them ("250,30"→"250.30", "shali/shail"→"shall", "ts"→"is", "a@", "vated"→"rated", "A connector"→"A connector", the (c)(2) inch conversion printed as a garbled "( in. thick x 2 in." = 1/4 in.) — the standard OCR class, disclosed; no other wording altered.
250.66 Size of Alternating-Current Grounding Electrode Conductor. The size of the grounding electrode conductor at the service, at each building or structure where supplied by a feeder(s) or branch circuit(s), or at a separately derived system of a grounded or ungrounded ac system shall not be less than given in Table 250.66, except as permitted in 250.66(A) through (C). (A) Connections to a Rod, Pipe, or Plate Electrode(s). If the grounding electrode conductor or bonding jumper connected to a single or multiple rod, pipe, or plate electrode(s), or any combination thereof, as described in 250.52(A)(5) or (A)(7), does not extend on to other types of electrodes that require a larger size conductor, the grounding electrode conductor shall not be required to be larger than 6 AWG copper wire or 4 AWG aluminum wire. (B) Connections to Concrete-Encased Electrodes. If the grounding electrode conductor or bonding jumper connected to a single or multiple concrete-encased electrode(s), as described in 250.52(A)(3), does not extend on to other types of electrodes that require a larger size of conductor, the grounding electrode conductor shall not be required to be larger than 4 AWG copper wire. (C) Connections to Ground Rings. If the grounding electrode conductor or bonding jumper connected to a ground ring, as described in 250.52(A)(4), does not extend on to other types of electrodes that require a larger size of conductor, the grounding electrode conductor shall not be required to be larger than the conductor used for the ground ring. Verbatim NEC 2017, official NFPA text (nec2017_full.txt lines 19859–19892). OCR line-wrap reflow normalized; no wording altered.

Table 250.66 — the full table

Grounding Electrode Conductor for Alternating-Current Systems — at the service, at each building/structure supplied by a feeder, or at a separately derived system (grounded or ungrounded).

Size of largest ungrounded service-entrance conductor (or equivalent area for parallel conductors) — copper (AWG/kcmil) — aluminum or copper-clad (AWG/kcmil) Size of GEC — copper (AWG/kcmil) Size of GEC — aluminum or copper-clad (AWG/kcmil)
2 AWG or smaller1/0 AWG or smaller8 AWG6 AWG
1 AWG or 1/0 AWG2/0 AWG or 3/0 AWG6 AWG4 AWG
2/0 AWG or 3/0 AWG4/0 AWG or 250 kcmil4 AWG2 AWG
Over 3/0 AWG through 350 kcmilOver 250 kcmil through 500 kcmil2 AWG1/0 AWG
Over 350 kcmil through 600 kcmilOver 500 kcmil through 900 kcmil1/0 AWG3/0 AWG
Over 600 kcmil through 1100 kcmilOver 900 kcmil through 1750 kcmil2/0 AWG4/0 AWG
Over 1100 kcmilOver 1750 kcmil3/0 AWG — CAPPED250 kcmil — CAPPED
Notes (2017, verbatim, OCR-normalized):
  1. If multiple sets of service-entrance conductors connect directly to a service drop, set of overhead service conductors, set of underground service conductors, or service lateral, the equivalent size of the largest service-entrance conductor shall be determined by the largest sum of the areas of the corresponding conductors of each set.
  2. Where there are no service-entrance conductors, the grounding electrode conductor size shall be determined by the equivalent size of the largest service-entrance conductor required for the load to be served.

*This table also applies to the derived conductors of separately derived ac systems. (See installation restrictions in 250.64(A).)

The electrode-size caps — 250.66(A)–(C)

Unlike Table 250.102(C)(1) (which has no electrode caps and keeps scaling via its 12.5% Note 1), Table 250.66's requirement is relaxed by electrode type — the GEC to a "small" electrode is never required to be bigger than the cap, even if the table says more:

Electrode (250.66)GEC never required larger thanCondition
(A) rod, pipe, or plate electrode (250.52(A)(5)/(A)(7))6 AWG Cu / 4 AWG Althe GEC does not extend on to other electrodes that require a larger size
(B) concrete-encased electrode (250.52(A)(3))4 AWG Cusame — and note there is no aluminum column: the cap is copper-only
(C) ground ring (250.52(A)(4))the ring conductor's sizesame

The "does not extend on to" language is the trap: if the 6 AWG GEC to your ground rod continues on to a concrete-encased electrode or building steel that needs the full table size, the whole run is sized to the furthest electrode — a rod-then-continue installation is not an escape hatch (the ELR 2017 record on 250.66(A) spells this out with exactly this example).

Edition history & the one documented change

Section titles verified on up.codes this session (fetched 2026-09-01): 250.26 "Conductor to Be Grounded — Alternating-Current Systems"; 250.30 "Grounding Separately Derived Alternating-Current Systems"; 250.66 "Size of Alternating-Current Grounding Electrode Conductor" (each confirmed for NFPA 70 2017/2020/2023).

The one documented 2017→2023 change — the 250.30 intro. 2017 (quoted verbatim above, on disk): "Multiple separately derived systems that are connected in parallel shall be installed in accordance with 250.30." 2023, quoted from the ELR change record (sectionID 1590, fetched this session): "Multiple power sources of the same type that are connected in parallel to form one system that supplies premises wiring shall be treated as a single separately derived system and shall be installed in accordance with 250.30." The 2023 record's companion quiz (option D: "Multiple power sources of the same type ... are considered as a single separately derived system") marks that reading as the 2023 correct answer. Everything else on this page checks out as unchanged:

Honesty: the on-disk 2020 full-code scan ends at Article 230 (no 2017→2020 word-diff claimed); the up.codes 2023 viewer body is account-gated, so the 2023 posture rests on the five ELR change records above + the zing2 table cross-check. The 2026 NEC renumber of Article 250 is flagged; this page cites 2017–2023 numbering.

Six worked examples (every number from the shipped core)

EX1 — the everyday case: 50 kVA, 3-phase 120/240 V transformer

ItemValue (core)
Transformer50 kVA, 3∅, 240 V wye (120/240 V derived)
Secondary full-load current50,000 VA ÷ (√3 × 208 V) = 138.8 A
Derived ungrounded conductors (310.16 @ 75 °C)pickConductor31016(139, 'cu', 75) = 1/0 Cu (150 A; 2/0 not needed — 150 A ≥ 138.8 A)
Table row (1/0 Cu)"1 AWG or 1/0 AWG"
Grounded conductor (250.30(A)(3)(a) → Table 250.102(C)(1))6 AWG Cu / 4 AWG Al
System bonding jumper (250.28(D)(1) → Table 250.102(C)(1))6 AWG Cu / 4 AWG Al
GEC (250.30(A)(5) → Table 250.66)6 AWG Cu / 4 AWG Al
Resultthree different conductors, three different sections, ONE row — 1/0 derived ungrounded → 6 AWG Cu everywhere (Tables 250.102(C)(1) and 250.66 agree on the first six rows)

EX2 — the electrode cap bites: 100 kVA, 3-phase 480/277 V, ground rod only

ItemValue (core)
Transformer100 kVA, 3∅, 480/277 V wye
Secondary full-load current100,000 VA ÷ (√3 × 277 V) = 208.4 A
Derived ungrounded conductors (310.16 @ 75 °C)pickConductor31016(209, 'cu', 75) = 4/0 Cu (230 A; 3/0 = 200 A is not enough)
Table row (4/0 Cu = 211,600 cmil)"Over 3/0 AWG through 350 kcmil"
GEC per Table 250.662 AWG Cu / 1/0 AWG Al
GEC required, electrode = ground rod only (250.66(A))6 AWG Cu / 4 AWG Al — the cap governs
Resulttable says 2 AWG Cu; the rod-only electrode caps the REQUIREMENT at 6 AWG Cu — the biggest "free size" in Article 250 (2 AWG is still legal, just not required)

EX3 — same transformer, concrete-encased (Ufer) electrode

ItemValue (core)
Setupsame 100 kVA 480/277 V (EX2), Ufer electrode in the foundation
Table row"Over 3/0 through 350 kcmil" → 2 AWG Cu
GEC required (250.66(B))4 AWG Cu — the cap (no aluminum column; copper-only cap)
Resultif the GEC also runs on to a water pipe or structural steel that needs the full table size, the "does not extend on to" condition fails and the cap no longer applies — full 2 AWG Cu for the run

EX4 — ungrounded system (250.30(B)): 25 kVA, 3-phase 240 V delta

ItemValue (core)
Transformer25 kVA, 3∅, 240 V delta — no grounded conductor
Secondary full-load current25,000 VA ÷ (√3 × 240 V) = 60.1 A
Largest derived ungrounded conductor (310.16 @ 75 °C)pickConductor31016(61, 'cu', 75) = 6 AWG Cu (65 A; 8 AWG = 50 A is not enough)
System bonding jumper / grounded conductornone — the system is ungrounded
GEC (250.30(B)(1) → Table 250.66, "2 AWG or smaller" row)8 AWG Cu / 6 AWG Al — from the enclosure to the electrode
Resultungrounded derived system: the GEC is the only grounding piece — it bonds the metal enclosures to the electrode, sized on the largest derived ungrounded conductor

EX5 — two transformers, one common GEC (250.30(A)(6))

ItemValue (core)
System A100 kVA, 3∅ 208 V → 277.6 A → 300 kcmil Cu (285 A @ 75 °C) → "Over 3/0 through 350 kcmil" → tap 2 AWG Cu
System B25 kVA, 3∅ 208 V → 69.4 A → 4 AWG Cu (85 A @ 75 °C; 6 AWG = 65 A is not enough) → "2 AWG or smaller" → tap 8 AWG Cu
Common GEC minimum (250.30(A)(6)(a)(1))3/0 AWG Cu / 250 kcmil Al (wire type) — or a qualifying water pipe (250.68(C)(1)) / structural steel (250.68(C)(2))
Tap connections (250.30(A)(6)(c))accessible location; listed G&B equipment, listed connections to ≥ 6 mm × 50 mm busbars, or exothermic welding — common GEC stays without a splice
Resultthe common GEC is a FLOOR (≥ 3/0 Cu regardless of the taps); each tap is sized by 250.66 on its own system's ungrounded conductors — a 2 AWG and an 8 AWG tap both hang off the same 3/0 Cu common

EX6 — the sub-1 kVA exception: 1 kVA control transformer

ItemValue (core)
Transformer1 kVA, 120/240 V, supplying Class 1/2/3 circuits
Secondary full-load current1,000 VA ÷ 240 V = 4.17 A
Derived ungrounded conductors (310.16 @ 75 °C)pickConductor31016(5, 'cu', 75) = 14 AWG Cu (20 A column value; 240.4(D) caps its OCPD at 15 A)
System bonding jumper (250.30(A)(1) Exception No. 3)≥ 14 AWG Cu / 12 AWG Al, not smaller than the derived ungrounded conductors
GEC (250.30(A)(5) Exception No. 3)NOT REQUIRED — grounded conductor bonded to the transformer frame, frame grounded per 250.134
Resultbelow 1000 VA the whole grounding-electrode apparatus drops out of the requirement — one small jumper from the grounded conductor to the frame does the job

Where 250.26/250.30 fit

Open the free PanelWright calculator — size the panel, the service, the neutral, the derating, and the voltage drop in your browser

Free, in-browser, zero tracking. Data never leaves your browser. Design aid only — verify against the adopted NEC edition.

Method, sources & honesty notes

Section text. Verbatim NEC 2017 (official NFPA text on disk, nec2017_full.txt): 250.26 (line 18501), 250.30(A)–(C) including all exceptions (lines 18571–18944), 250.66 + (A)–(C) (lines 19859–19892). OCR line-wrap reflow normalized; OCR artifacts corrected to standard wording where the scan garbled them ("250,30"→"250.30", "shali/shail"→"shall", "ts"→"is", "vated"→"rated", the (c)(2) inch conversion printed as a garbled "( in. thick x 2 in." = 1/4 in.) — the standard OCR class, disclosed in the source note. No other wording altered.

Table 250.66 values (7 rows, capped top). The on-disk 2017 OCR interleaves the table's columns (row labels wrap to their own lines), so the rows were parsed from the OCR layout row-by-row (nec2017_full.txt lines 19960–20028) and cross-checked this session against a cached zing2.app NEC-2023 table (parsed by parse_art24_zing2_25066.py: identical 7 rows, 0 disagreements) and against the ELR change record 1603's description (keyed on the size of the largest ungrounded conductor). The on-disk OCR garbles the row label "lor 1/0" (= "1 or 1/0 AWG") — same OCR class as article 23's "124% percent", disclosed here rather than propagated.

Edition history. Section titles verified on up.codes this session (fetched 2026-09-01 via fetch_art24_up.py). Five ELR change records fetched this session (fetched 2026-09-01 via fetch_art24_elr.py): sectionID 1590 (250.30 intro — the one documented 2017→2023 wording change, quoted above), 1591 (250.30(A)(4) 2023 — verbatim-identical to 2017), 1592 (250.30(A)(6)(a) 2023 — common-GEC options identical), 1602 (250.66(A) caps — 6 AWG Cu / 4 AWG Al, 4 AWG Cu), 1603 (Table 250.66 purpose + Note 2). The on-disk 2020 full-code scan ends at Article 230 (no 2017→2020 word-diff claimed); the up.codes 2023 viewer body is account-gated (no 2023 full-body word-diff claimed beyond the records above). 2026 renumber flagged.

Worked numbers. Every cmil / size / ampacity value computed by the shipped cores under node (compute_art24.js → calc_25066_cited.json): Ch. 9 Table 8 cmil via ch9Row/CH9_T8, Table 310.16 picks via pickConductor31016, column ampacities via T31016/T31016_COLS, standard OCPD steps via nextStdBreaker. The table-row lookups are the code itself, transcribed once and asserted by the public test suite. Zero hand math.