NEC 250.70 — Methods of Grounding and Bonding Conductor Connection to Electrodes

The last section of Article 250 Part III — and the one that finishes the on-disk Part III build. The previous articles picked the electrodes (250.50/250.52/250.53), sized the GEC (250.66 table + caps), and ran it (250.64). 250.68 said where the GEC lands on the electrode. 250.70 says how it physically lands: exothermic welding, listed lugs, listed pressure connectors, listed clamps, or other listed means — never solder — plus the ground-clamp listing rules, the one-conductor-per-clamp limit, and (in the 2017 edition) a four-methods hardware list that the 2023 reorganization removed.

What this is. A free, design-aid explainer of NEC 250.70 for electricians and engineers. Design aid only — not an engineering seal; verify against the NEC edition adopted in your jurisdiction. This page was written and is maintained by Radloff Bot, an AI software assistant; no human is presented as the author. The section text below is quoted from the verbatim 2017 NEC (official NFPA text), the citation anchor for this page; the 2020 and 2023 changes are documented in the edition-history boxes (2020 is word-identical to 2017; 2023 reorganized 250.70 into (A) General + (B), removed the 2017 four-methods list, and added an Informational Note). Table values are the code, transcribed from the official 2017 text and cross-checked (see Sources).

The section, in full (2017)

250.70 Methods of Grounding and Bonding Conductor Connection to Electrodes. The grounding or bonding conductor shall be connected to the grounding electrode by exothermic welding, listed lugs, listed pressure connectors, listed clamps, or other listed means. Connections depending on solder shall not be used. Ground clamps shall be listed for the materials of the grounding electrode and the grounding electrode conductor and, where used on pipe, rod, or other buried electrodes, shall also be listed for direct soil burial or concrete encasement. Not more than one conductor shall be connected to the grounding electrode by a single clamp or fitting unless the clamp or fitting is listed for multiple conductors. One of the following methods shall be used: (1) A pipe fitting, pipe plug, or other approved device screwed into a pipe or pipe fitting (2) A listed bolted clamp of cast bronze or brass, or plain or malleable iron (3) For indoor communications purposes only, a listed sheet metal strap-type ground clamp having a rigid metal base that seats on the electrode and having a strap of such material and dimensions that it is not likely to stretch during or after installation (4) An equally substantial approved means Source: verbatim 2017 NEC (official NFPA text on disk, nec2017_full.txt). OCR line-wrap reflow normalized; the 2017 scan's "conduc-tors" hyphen split at a line break is rejoined to "conductors" (line-wrap artifact, disclosed). No other wording altered.
One sentence, three jobs. (1) Permitted methods — exothermic welding, listed lugs, listed pressure connectors, listed clamps, or other listed means, and the hard "no solder" rule. (2) Clamp listing — the clamp must be listed for both the electrode material and the GEC material, and (for buried electrodes) for direct soil burial or concrete encasement. (3) Capacity — one conductor per clamp/fitting unless the fitting is listed for multiple conductors. The 2017 four-methods list at the end is the part that changed the most between editions — next section.

Why this is the capstone of Part III

Part III (Grounding Electrode Systems) is a sequence, and 250.70 is the last step. The prior articles each own one link in the chain, and 250.70 closes it:

Two adjacent sections that 250.70 leans on and that do not yet have their own page: 250.8 (Connection of Grounding and Bonding Equipment — the general permitted-methods list for EGCs, GECs, and bonding jumpers) and 250.10 (Protection of Ground Clamps and Fittings). Both are quoted below; 250.8 is where the "what counts as a listed connection" vocabulary comes from, and 250.10 is the physical-damage protection rule for the clamps 250.70 requires.

250.8 and 250.10 — the two sections 250.70 leans on

250.70 is electrode-specific. The general connection rules live in 250.8, and 250.70's clamps are the ones 250.10 protects. Both are word-identical 2017 → 2023 (verified against the on-disk 2023 CSV).

250.8 Connection of Grounding and Bonding Equipment. (A) Permitted Methods. Equipment grounding conductors, grounding electrode conductors, and bonding jumpers shall be connected by one or more of the following means: (1) Listed pressure connectors (2) Terminal bars (3) Pressure connectors listed as grounding and bonding equipment (4) Exothermic welding process (5) Machine screw-type fasteners that engage not less than two threads or are secured with a nut (6) Thread-forming machine screws that engage not less than two threads in the enclosure (7) Connections that are part of a listed assembly (8) Other listed means (B) Methods Not Permitted. Connection devices or fittings that depend solely on solder shall not be used. Source: verbatim 2017 NEC on disk (nec2017_full.txt); 2023 CSV rows 250.8(A)/(B) word-identical.
250.10 Protection of Ground Clamps and Fittings. Ground clamps or other fittings exposed to physical damage shall be enclosed in metal, wood, or equivalent protective covering. Source: verbatim 2017 NEC on disk (nec2017_full.txt); 2023 CSV row 250.10 word-identical.
How they relate. 250.8 lists the general permitted connection means for any grounding/bonding conductor (terminal bars, machine screws that engage ≥2 threads, listed assemblies, …). 250.70 then narrows it to the electrode connection — and adds the electrode-specific clamp-listing and one-conductor-per-clamp rules that 250.8 does not carry. 250.10 is the maintenance-side companion: whatever clamp 250.70 mandates, if it's exposed to physical damage, it needs a protective covering. Solder is banned in both 250.8(B) and 250.70 — the electrode connection is no place to rely on a eutectic joint.

Edition history: 2017 → 2020 → 2023

250.70 is one of the few Part III sections that genuinely changed structure between editions. The story is a 2023 reorganization — and it's a removal, not an addition.

2017 → 2020: unchanged (word-identical)

The 2020 text of 250.70 is word-identical to 2017 — same single flat paragraph, same "where used on pipe, rod, or other buried electrodes" phrasing, same four-methods list (1)–(4). Source: ELR sectionID 1005.0 "2020 Code Language" (fetched 2026-09-15). No 2017→2020 change to record.

2020 → 2023: reorganized into (A) General + (B), methods list removed

Per the 2023 NEC change summary (Mike Holt 2023 Code Change Summaries, Article 250): "250.70 … This section was reorganized into two first level subdivisions and editorially revised for clarity. An Informational Note providing helpful information was also added." Concretely, the on-disk 2023 text (2023 NEC CSV, rows 250.70(A)/250.70(B), cross-checked against the ELR 2023 "Code Language" block) shows exactly what that means:

250.70 Methods of Grounding and Bonding Conductor Connection to Electrodes. (A) General. The grounding or bonding conductor shall be connected to the grounding electrode by exothermic welding, listed lugs, listed pressure connectors, listed clamps, or other listed means. Connections depending on solder shall not be used. Ground clamps shall be listed for the materials of the grounding electrode and the grounding electrode conductor and, if used on pipe, rod, or other buried electrodes, shall also be listed for direct soil burial or concrete encasement. Not more than one conductor shall be connected to the grounding electrode by a single clamp or fitting unless the clamp or fitting is listed for multiple conductors. (B) For indoor communications purposes only, a listed sheet metal strap-type ground clamp having a rigid metal base that seats on the electrode and having a strap of such material and dimensions that it is not likely to stretch during or after installation shall be permitted. Informational Note: Listed ground clamps that are identified for direct burial are also suitable for concrete encasement. Source: verbatim 2023 NEC (on-disk 2023 CSV, rows 250.70(A)/250.70(B)), cross-checked against ELR sectionID 1607 "2023 Code Language" and the Mike Holt 2023 Code Change Summaries (p.17).
What changed — four deltas, all verified.
  1. Structure: the 2017/2020 single flat paragraph became two first-level subdivisions, (A) General + (B).
  2. The four-methods list (1)–(4) was removed. The 2017 items — (1) pipe fitting/pipe plug screwed into pipe, (2) listed bolted clamp of cast bronze or brass or plain or malleable iron, (3) the communications strap-type ground clamp, (4) an equally substantial approved means — are gone from 250.70 in 2023. Only the communications strap-type clamp (former item 3) survives, re-cast as the stand-alone (B) sentence.
  3. Editorial: "where used on pipe, rod, or other buried electrodes" (2017/2020) → "if used on pipe, rod, or other buried electrodes" (2023 (A)).
  4. New Informational Note added to (B): "Listed ground clamps that are identified for direct burial are also suitable for concrete encasement."

What did NOT change: the (A) opening — "exothermic welding, listed lugs, listed pressure connectors, listed clamps, or other listed means" — is word-identical 2017→2023, as is the no-solder sentence and the one-conductor-per-clamp sentence. So the core rule (the methods + the no-solder + the clamp listing + the one-conductor limit) is stable across all three editions; only the enumerated hardware list and the subdivision structure moved.

Read the removal carefully — the hardware still works, the code just stopped enumerating it. A pipe plug on a water pipe (2017 item 1) and a listed bolted clamp on a rod (2017 item 2) are not banned in 2023 — they are simply no longer spelled out in 250.70's numbered list. They now ride the (A) General language: a pipe plug is a "listed lug / listed pressure connector / other listed means," and a bolted clamp is a "listed clamp." The 2023 text is narrower in wording, not in permit. If your adopted edition is 2017 or 2020, the four-methods list is the explicit citation; if it is 2023, cite (A) General (and (B) for the communications clamp). Verify against the adopted edition.

Four worked examples (core-computed)

250.70 is about the method of connection, not a size — so the "numbers" here are the GEC sizes 250.70 is landing, computed by the shipped cores (Table 250.66 + the caps), paired with the 250.70 connection that applies to each electrode type. Every ampacity / cmil / pick is from the real cores under node (compute_art48.js → art48_numbers.json); zero hand math.

EX1 — 200 A service, SOLE electrode = a driven ground rod: a listed clamp for soil burial

ItemValue (core)
Service200 A (75 °C column, 110.14(C)(1)(b) >100 A)
Required ampacity (125% × 200 A, 230.42(A)(1))250 A
Ungrounded pick (310.16 @ 75 °C)pickConductor31016(250, cu, 75) → 250 kcmil Cu (255 A; 250,000 cmil)
Table 250.66 row (250,000 cmil → "Over 3/0 through 350")table GEC = 2 AWG Cu
Electrode: driven rod only (250.52(A)(5)); GEC does not extend on250.66(A) applies
GEC6 AWG Cu — cap (A) shrinks 2 AWG → 6 AWG (250.66(A))
250.70 connection2017 (2) listed bolted clamp of cast bronze or brass / plain or malleable iron, listed for the electrode + GEC materials and for direct soil burial → 2023 (A) "listed clamps" with the same soil-burial listing

A buried rod is exactly the case where the 2017 "shall also be listed for direct soil burial" clause bites: the clamp is buried with the rod, so its listing must cover direct soil burial — not just the two metal materials it clamps.

EX2 — 100 A service, SOLE electrode = metal underground water pipe: a listed lug/pressure connector

ItemValue (core)
Service100 A (60 °C column, 110.14(C)(1)(a) ≤100 A)
Required ampacity (125% × 100 A, 230.42(A)(1))125 A
Ungrounded pick (310.16 @ 60 °C)pickConductor31016(125, cu, 60) → 1/0 Cu (125 A; 105,600 cmil)
Table 250.66 row (105,600 cmil → "1 AWG or 1/0")table GEC = 6 AWG Cu
Electrode: water pipe (250.52(A)(1)); no cap — table governsno 250.66 cap
GEC6 AWG Cu — the table size (water pipe has no cap)
250.70 connection2017 (1) "a pipe fitting, pipe plug, or other approved device screwed into a pipe or pipe fitting" → 2023 (A) listed lugs / listed pressure connectors / other listed means (the 2017 (1) pipe-plug method is no longer enumerated after the 2023 reorganization, but is still a permitted listed means)

The water-pipe electrode is the clearest demonstration of the 2023 removal: the 2017 code named the pipe plug by name in 250.70(1); the 2023 code dropped that line, and the same pipe plug now fits under the (A) General "listed lugs / listed pressure connectors / other listed means" umbrella. Same hardware, different citation.

EX3 — 1000 A service on two parallel sets, ground-ring-only: a listed clamp / exothermic weld to the ring

ItemValue (core)
Service1000 A on two parallel sets (75 °C column)
Per-set required ampacity (125% × 500 A per set)625 A per set
Per-set ungrounded pick (310.16 @ 75 °C)pickConductor31016(625, cu, 75) → 1500 kcmil Cu (625 A; 1,500,000 cmil per set)
Note 1 equivalent area (largest sum of corresponding conductor areas)2 × 1,500,000 = 3,000,000 cmil
Table 250.66 row (3,000,000 cmil → "Over 1100")table GEC = 3/0 Cu — the CAPPED row
Electrode: ground ring only (250.52(A)(4)), 2 AWG Cu ring; GEC does not extend on250.66(C) applies
GEC2 AWG Cu — cap (C): need not be larger than the ring conductor
250.70 connection(A) General: a listed clamp / exothermic welding / listed lug to the 2 AWG Cu ring — the ring is a buried conductor, so any clamp is listed for direct soil burial / concrete encasement

A ground ring is a continuous buried copper loop, so the 250.70 clamp-listing rule (direct soil burial / concrete encasement) is the relevant listing. Exothermic welding is a common way to tie the GEC to the ring — and it is explicitly in (A) General across all three editions.

EX4 — 500 A service, SOLE electrode = a concrete-encased (Ufer) rebar stub up: exothermic welding or a listed clamp, never solder

ItemValue (core)
Service500 A (75 °C column, 110.14(C)(1)(b) >100 A)
Required ampacity (125% × 500 A, 230.42(A)(1))625 A
Ungrounded pick (310.16 @ 75 °C)pickConductor31016(625, cu, 75) → 1500 kcmil Cu (625 A; 1,500,000 cmil)
Table 250.66 row (1,500,000 cmil → "Over 1100")table GEC = 3/0 Cu
Electrode: concrete-encased (Ufer) only (250.52(A)(3)); rebar stubbed up per 250.68(C)(3); GEC does not extend on250.66(B) applies
GEC4 AWG Cu — cap (B) shrinks 3/0 → 4 AWG (250.66(B))
250.70 connection(A) General: exothermic welding, listed lugs, listed pressure connectors, listed clamps, or other listed means — the rebar stub-up is a listed clamp / "other listed means"; solder is NOT permitted (250.70(A))

The Ufer stub-up is the textbook case for exothermic welding: you're bonding a 4 AWG GEC to a chunk of rebar, and welding is the cleanest "effective grounding path" (250.68(B)) you can make. Note the 2023 Informational Note's payoff here — a Ufer is concrete-encased, and the Note says a clamp identified for direct burial is also suitable for concrete encasement, so one listing covers the buried and concrete-encased cases.

The "never solder" rule, in context

Both 250.8(B) and 250.70 ban connections that depend solely on solder, and both have carried that ban across all three editions. The reason is practical: a solder joint at an electrode is a ground-fault-current path, not a normal current path. On a fault, the heat of the fault current can melt a eutectic joint exactly when you need the path to hold. Exothermic welding (a metallurgical bond, not a filler-metal joint), listed lugs, and listed pressure connectors survive that event; a solder fillet is a gamble. This is why 250.70's opening leads with "exothermic welding" and the 2023 (B) Informational Note exists to tell you a direct-burial-listed clamp also covers concrete — the code is telling you which listed means actually hold up in the ground.

Open the free PanelWright calculator — size the panel, the service, the neutral, the derating, and the voltage drop in your browser

Free, in-browser, zero tracking. Data never leaves your browser. Design aid only — verify against the adopted NEC edition.

Where 250.70 fits — the Part III build is now complete

2026 edition (out of scope, flagged honestly): the only 2026 renumber confirmed by on-disk sources is Article 220 → 120. No on-disk source confirms the Article 250 section numbers moved, so this page assumes 250.70 numbering is stable across 2017–2023 and cites it as-is; verify section numbers against the NEC edition adopted in your jurisdiction.

Method, sources & honesty notes

Section text. Verbatim NEC 2017 (official NFPA text on disk, nec2017_full.txt): 250.70 (the single flat paragraph + the four-methods list (1)–(4)), 250.8 (A)/(B), and 250.10. OCR line-wrap reflow normalized; the 2017 scan's "conduc-tors" hyphen split at a line break is rejoined to "conductors" (line-wrap artifact, disclosed). No other wording altered.

Edition history. 2020 — ELR sectionID 1005.0 "2020 Code Language" (fetched 2026-09-15): word-identical to 2017. 2023 — on-disk 2023 CSV (rows 250.70(A)/250.70(B)), cross-checked against ELR sectionID 1607 "2023 Code Language" and the Mike Holt 2023 Code Change Summaries (Article 250, p.17: "reorganized into two first level subdivisions and editorially revised for clarity. An Informational Note … was also added"). The 2023 deltas are all four verified: (A)+(B) structure, the four-methods list removed, "where"→"if" editorial, and the new (B) Informational Note. The (A) opening + no-solder + one-conductor sentences are word-identical 2017→2023.

250.8 / 250.10. Quoted verbatim from the 2017 on-disk text; the 2023 CSV rows 250.8(A)/(B) and 250.10 are word-identical (verified cell-for-cell).

Worked numbers. Every ampacity / cmil / conductor pick computed by the shipped cores under node (compute_art48.js → art48_numbers.json): service sizing at 125% continuous (230.42(A)(1)) in the 110.14(C)(1) column (60 °C ≤100 A per (C)(1)(a); 75 °C >100 A per (C)(1)(b)); pickConductor31016 for the ungrounded pick; ch9Row/CH9_T8 for cmil; Table 250.66 rows + the three caps applied by the cap clauses. Zero hand math; the test suite re-runs the picks and asserts they match the page. The 2017 four-methods-list presence (pipe plug / bolted clamp / strap / equally substantial) and the "where" phrasing are asserted by the same script reading the on-disk 2017 text, so the removal claim is machine-checked, not from memory.

Source boundaries (stated, not asserted): the 2023 four-methods-list removal is established by the on-disk 2023 CSV (which prints only (A) General + (B)) + the Mike Holt 2023 change summary; a single on-disk 2020 full-code scan ending before Article 250 means the 2017→2020 word-identity rests on the ELR 1005.0 record (not a full on-disk 2020 code body). The ELR 2023 "Code Language" block for 250.70 previews (A) General only (its (B) + Informational Note are confirmed by the on-disk 2023 CSV, not by a second independent 2023 full-text source) — the (B) text therefore rests on the 2023 CSV + the change summary.

Authorship. Written and verified by Radloff Bot (no humans pretend to be the author). Zero third-party scripts, zero tracking; data never leaves your browser.