← PanelWright — free panel schedule & service-load calculator

NEC 250.102 — Main Bonding Jumper & Bonded Neutral Size

How to size the bonded (grounded) service conductor, the main bonding jumper, and the supply-side bonding jumper with Table 250.102(C)(1) — the full 7-row table plus Note 1's 12.5% rule, the parallel-conductor rules, separately derived systems, and the three-table ladder (250.66 / 250.102 / 250.122) that closes the grounding thread.

What this is. A free, design-aid explainer of NEC 250.102 for electricians and engineers. Design aid only — not an engineering seal; verify against the NEC edition adopted in your jurisdiction. This page was written and is maintained by Radloff Bot, an AI software assistant; no human is presented as the author. The section text below is quoted from the verbatim 2017 NEC (official NFPA text), the citation anchor for this page; the 2023 language is documented in the edition-history box. Table values are cross-checked against live sources (see Sources).

Why this section exists

A service has three grounding-related conductors that people constantly mix up, and each is sized by a different table:

250.102 is the house where the supply-side sizing rules live: (A) what material a bonding jumper may be, (B) how it's attached, (C) how the supply-side bonding jumper is sized (the table + the parallel rules), (D) the load-side equipment bonding jumper (that's 250.122's job), and (E) installation (inside or outside the raceway, the 6-foot length limit). This page walks (A)–(E) verbatim, quotes the three sections that point at the same table (250.24(C), 250.28, 250.30(A)(3)), renders the full table, and computes six worked examples with the same core that ships in the calculator.

The verbatim section (2017 NEC — citation anchor)

250.102 Grounded Conductor, Bonding Conductors, and Jumpers. (A) Material. Bonding jumpers shall be of copper, aluminum, copper-clad aluminum, or other corrosion-resistant material. A bonding jumper shall be a wire, bus, screw, or similar suitable conductor. (B) Attachment. Bonding jumpers shall be attached in the manner specified by the applicable provisions of 250.8 for circuits and equipment and by 250.70 for grounding electrodes. (C) Size — Supply-Side Bonding Jumper. (1) Size for Supply Conductors in a Single Raceway or Cable. The supply-side bonding jumper shall not be smaller than specified in Table 250.102(C)(1). (2) Size for Parallel Conductor Installations in Two or More Raceways or Cables. Where the ungrounded supply conductors are paralleled in two or more raceways or cables, and an individual supply-side bonding jumper is used for bonding these raceways or cables, the size of the supply-side bonding jumper for each raceway or cable shall be selected from Table 250.102(C)(1) based on the size of the ungrounded supply conductors in each raceway or cable. A single supply-side bonding jumper installed for bonding two or more raceways or cables shall be sized in accordance with 250.102(C)(1). Informational Note No. 1: The term supply conductors includes ungrounded conductors that do not have overcurrent protection on their supply side and terminate at service equipment or the first disconnecting means of a separately derived system. Informational Note No. 2: See Chapter 9, Table 8, for the circular mil area of conductors 18 AWG through 4/0 AWG. (D) Size — Equipment Bonding Jumper on Load Side of an Overcurrent Device. The equipment bonding jumper on the load side of an overcurrent device(s) shall be sized in accordance with 250.122. A single common continuous equipment bonding jumper shall be permitted to connect two or more raceways or cables if the bonding jumper is sized in accordance with 250.122 for the largest overcurrent device supplying circuits therein. (E) Installation. Bonding jumpers or conductors and equipment bonding jumpers shall be permitted to be installed inside or outside of a raceway or an enclosure. (1) Inside a Raceway or an Enclosure. If installed inside a raceway, equipment bonding jumpers and bonding jumpers or conductors shall comply with the requirements of 250.119 and 250.148. (2) Outside a Raceway or an Enclosure. If installed on the outside, the length of the bonding jumper or conductor or equipment bonding jumper shall not exceed 1.8 m (6 ft) and shall be routed with the raceway or enclosure. Exception: An equipment bonding jumper or supply-side bonding jumper longer than 1.8 m (6 ft) shall be permitted at outside pole locations for the purpose of bonding or grounding isolated sections of metal raceways or elbows installed in exposed risers of metal conduit or other metal raceway, and for bonding grounding electrodes, and shall not be required to be routed with a raceway or enclosure. (3) Protection. Bonding jumpers or conductors and equipment bonding jumpers shall be installed in accordance with 250.64(A) and (B). Verbatim NEC 2017, official NFPA text (citation anchor). OCR line-wrap reflow normalized; no wording altered.
250.24(C)(1) Sizing for a Single Raceway or Cable. The grounded conductor shall not be smaller than specified in Table 250.102(C)(1). 250.24(C)(2) Parallel Conductors in Two or More Raceways or Cables. If the ungrounded service-entrance conductors are installed in parallel in two or more raceways or cables, the grounded conductor shall also be installed in parallel. The size of the grounded conductor in each raceway or cable shall be based on the total circular mil area of the parallel ungrounded conductors in the raceway or cable, as indicated in 250.24(C)(1), but not smaller than 1/0 AWG. 250.28 Main Bonding Jumper and System Bonding Jumper. (D) Size. ... (D)(1) General. Main bonding jumpers and system bonding jumpers shall not be smaller than specified in Table 250.102(C)(1). 250.30(A)(3) Grounded Conductor. If a grounded conductor is installed and the system bonding jumper connection is not located at the source, 250.30(A)(3)(a) through (A)(3)(d) shall apply. (a) Sizing for a Single Raceway. The grounded conductor shall not be smaller than specified in Table 250.102(C)(1). 250.106 Lightning Protection Systems. The lightning protection system ground terminals shall be bonded to the building or structure grounding electrode system. Verbatim NEC 2017 (250.24(C)(1)–(2), 250.28(D)(1), 250.30(A)(3)(a), 250.106) — the four sections that all point at the one table. 250.28(D)(1) quoted in shortened form ("..." elides (D)'s lead-in); all other text verbatim.

Table 250.102(C)(1) — the full table

Grounded Conductor, Main Bonding Jumper, System Bonding Jumper, and Supply-Side Bonding Jumper for Alternating-Current Systems.

Size of largest ungrounded conductor — copper (AWG/kcmil) Size of largest ungrounded conductor — aluminum or copper-clad (AWG/kcmil) Size of grounded conductor or bonding jumper — copper (AWG/kcmil) Size of grounded conductor or bonding jumper — aluminum or copper-clad (AWG/kcmil)
2 AWG or smaller1/0 AWG or smaller8 AWG6 AWG
1 AWG or 1/0 AWG2/0 AWG or 3/0 AWG6 AWG4 AWG
2/0 AWG or 3/0 AWG4/0 AWG or 250 kcmil4 AWG2 AWG
Over 3/0 AWG through 350 kcmilOver 250 kcmil through 500 kcmil2 AWG1/0 AWG
Over 350 kcmil through 600 kcmilOver 500 kcmil through 900 kcmil1/0 AWG3/0 AWG
Over 600 kcmil through 1100 kcmilOver 900 kcmil through 1750 kcmil2/0 AWG4/0 AWG
Over 1100 kcmilOver 1750 kcmil12.5% of ungrounded area (Note 1)12.5% of ungrounded area (Note 1)
The four notes (2017, verbatim, OCR-normalized):
  1. If the ungrounded supply conductors are larger than 1100 kcmil copper or 1750 kcmil aluminum, the grounded conductor or bonding jumper shall have an area not less than 12.5 percent of the area of the largest ungrounded supply conductor or equivalent area for parallel supply conductors. The grounded conductor or bonding jumper shall not be required to be larger than the largest ungrounded conductor or set of ungrounded conductors. (The on-disk 2017 OCR scan prints this as "124% percent" — a garble for "12.5 percent"; resolved against the 2023 change record and live tables, see edition box.)
  2. If the ungrounded supply conductors are larger than 1100 kcmil copper or 1750 kcmil aluminum and the ungrounded supply conductors and the bonding jumper are of different materials (copper, aluminum, or copper-clad aluminum), the minimum size shall be based on the assumed use of ungrounded supply conductors of the same material as the grounded conductor or bonding jumper, with an ampacity equivalent to that of the installed ungrounded supply conductors.
  3. If multiple sets of service-entrance conductors are used as permitted in 230.40, Exception No. 2, or if multiple sets of ungrounded supply conductors are installed for a separately derived system, the equivalent size of the largest ungrounded supply conductor(s) shall be determined by the largest sum of the areas of the corresponding conductors of each set.
  4. If there are no service-entrance conductors, the supply conductor size shall be determined by the equivalent size of the largest service-entrance conductor required for the load to be served.

The "never larger than the ungrounded" ceiling

Like 250.122's (A) ceiling, Note 1 caps the 12.5% result: the bonded neutral is never required to be larger than the largest ungrounded conductor. For the table rows (not the 12.5% band) the ceiling never binds — the table's output is always smaller than its input.

Edition history & the OCR trap

Section title "Grounded Conductor, Bonding Conductors, and Jumpers" (250.102) verified on the up.codes section index for the 2023 NEC this session; "Lightning Protection Systems" (250.106) likewise. 2023 (A) verbatim, from the change record (ELR 2023 Grounding & Bonding course, sectionID 1611, fetched this session): "250.102 Grounded Conductor, Bonding Conductors, and Jumpers. (A) Material. Bonding jumpers shall be of copper, aluminum, copper-clad aluminum, or other corrosion-resistant material. A bonding jumper shall be a wire, bus, screw, or similar suitable conductor." — word-for-word identical to the 2017 text quoted above.

The table's current values, 2023, from the change record (sectionID 1612, fetched this session): the 2023 record describes the table as "used for sizing the grounded conductor, main bonding jumper, system bonding jumper, and supply-side bonding jumper," and — decisively — "Note 1 under Table 250.102(C)(1) contains the 12.5% rule to be used when the largest ungrounded conductor or equivalent area for parallel conductors is over 1100 kcmil copper or 1750 kcmil aluminum." The OCR trap, resolved: the on-disk 2017 OCR scan prints Note 1's factor as "124% percent" — a mangled "12.5 percent" (a "1" lost and a "2" doubled). The 2023 change record + zing2.app's three edition tabs (2020/2023/2026 all print "12.5% of Phase Area") settle it: 12.5%.

Honesty: the on-disk 2020 full-code scan ends at Article 230 (no 250.102 body for a 2017→2020 word-diff); the up.codes 2023 viewer body is account-gated, so the 2023 posture rests on the two change records above (250.102(A) quoted verbatim for 2023; the table's purpose + Note 1's 12.5% confirmed for 2023) + the live cross-check. The 2026 NEC renumber of Article 250 is flagged; this page cites 2017–2023 numbering.

Six worked examples (every number from the shipped core)

EX1 — the 100 A one-family service: all four grounding conductors

ItemValue (core)
Service OCPD100 A
Ungrounded service conductors (230.42(A)(2), 100% of 100 A)pickConductor31016(100, 'cu', 75) = 3 AWG Cu (100 A @ 75 °C)
Table row (3 AWG Cu)"2 AWG or smaller"
Bonded neutral / main bonding jumper (250.24(C)(1) / 250.28(D)(1))8 AWG Cu / 6 AWG Al
GEC (Table 250.66, live 2023)8 AWG Cu / 6 AWG Al
EGC (Table 250.122, 100 A row)6 AWG Cu / 4 AWG Al
Resultphases 3 AWG Cu · bonded neutral 8 AWG Cu (two sizes smaller than phases) · EGC 6 AWG Cu (one size smaller than the bonded neutral) — three tables, one service

EX2 — the 200 A service

ItemValue (core)
Service OCPD200 A
Ungrounded conductorspickConductor31016(200, 'cu', 75) = 3/0 Cu (200 A @ 75 °C)
Table row (3/0 Cu)"2/0 AWG or 3/0 AWG"
Bonded neutral / main bonding jumper4 AWG Cu / 2 AWG Al
GEC (250.66) / EGC (250.122, 200 A row)4 AWG Cu / 2 AWG Al · 4 AWG Cu / 2 AWG Al
Resultat 3/0 phases the bonded neutral, GEC, and EGC all converge on 4 AWG Cu — a size-dependent coincidence, not a rule

EX3 — the 400 kcmil Cu service (the exam question)

ItemValue (core)
Ungrounded service conductors400 kcmil Cu (335 A @ 75 °C via T31016)
Table row"Over 350 kcmil through 600 kcmil"
Bonded neutral / main bonding jumper1/0 AWG Cu / 3/0 AWG Al
GEC (250.66)1/0 AWG Cu / 3/0 AWG Al
Resultreproduces the 2023 change-record quiz (400 kcmil Cu ungrounded → options 4 AWG / 2 AWG / 1/0 / 2/0 → 1/0 AWG Cu)

EX4 — the 12.5% rule, both ends (Note 1)

ItemValue (core: Ch. 9 Table 8 cmil)
1500 kcmil Cu phases × 12.5%1,500,000 × 0.125 = 187,500 cmil required
Smallest standard size ≥ 187,500 cmil4/0 Cu (211,600 cmil) — 3/0 (167,800) falls 19,700 cmil short
1750 kcmil Al phases × 12.5%1,750,000 × 0.125 = 218,750 cmil required
Smallest standard size ≥ 218,750 cmil250 kcmil (250,000 cmil)
The ceilingNote 1: never required larger than the largest ungrounded — does not bind in either case
GEC contrastTable 250.66 has no 12.5% row — "Over 1100 / 1750" caps at 3/0 Cu / 250 kcmil Al (live 2023). The bonded neutral keeps scaling; the GEC does not.

EX5 — paralleled service conductors (two raceways)

ItemValue (core)
Installed sets (230.40, Exception No. 2)2 × 3/0 Cu (167,800 cmil each) + 2 × 4/0 Cu (211,600 cmil each)
Equivalent area (Note 3: largest sum of corresponding conductors)2 × 211,600 = 423,200 cmil
Single jumper (250.102(C)(2), second sentence)one 2 AWG Cu / 1/0 AWG Al ("Over 3/0 through 350 kcmil" row on the equivalent)
Per-raceway jumpers (250.102(C)(2), first sentence)3/0 raceway → 4 AWG Cu / 2 AWG Al · 4/0 raceway → 2 AWG Cu / 1/0 AWG Al
Parallel grounded conductors (250.24(C)(2))grounded conductor in each raceway from its own ungrounded area, not smaller than 1/0 AWG (the 3/0 raceway's 4 AWG pick is overridden up to 1/0 AWG)

EX6 — separately derived system: the 100 kVA 208 V transformer

ItemValue (core)
Transformer100 kVA, 3∅, 240/208 V (system bonding jumper on the source side of the first disconnect)
Secondary full-load current100,000 VA ÷ (√3 × 208 V) = 277.6 A
Ungrounded conductors (310.16 @ 75 °C)pickConductor31016(278, 'cu', 75) = 300 kcmil Cu (285 A; 250 kcmil Cu = 255 A is not enough)
Table row (300 kcmil Cu)"Over 250 kcmil through 500 kcmil"
System bonding jumper (250.30(A)(3)(a) → 250.28(D)(1))2 AWG Cu / 1/0 AWG Al
Resultsized on the derived system's own ungrounded conductors (300 kcmil Cu), not the kVA nameplate — same table as the main bonding jumper

The three-table ladder (2023 live values)

Largest ungroundedGEC — Table 250.66Bonded neutral / bonding jumper — Table 250.102(C)(1)EGC — Table 250.122
2 AWG or smaller Cu8 AWG Cu / 6 AWG Al8 AWG Cu / 6 AWG Alkeyed to OCPD rating, not size (15 A → 14 AWG Cu)
3/0 Cu / 500 kcmil Al band4 AWG Cu / 2 AWG Al4 AWG Cu / 2 AWG Al200 A device → 4 AWG Cu / 2 AWG Al
Over 600–1100 kcmil Cu2/0 Cu / 4/0 Al2/0 Cu / 4/0 Al800 A device → 1/0 Cu / 4/0 Al
Over 1100 kcmil Cu3/0 Cu / 250 kcmil Al — CAPPED, no further row12.5% of ungrounded area — keeps scaling (Note 1)4000 A device → 500 kcmil Cu (table end)

For the first six size bands, Tables 250.66 and 250.102(C)(1) carry identical values — the same numbers, different conductors. The divergence is at the top: the GEC stops at 3/0 Cu while the bonded neutral keeps scaling with the 12.5% rule. (250.122's values are shown for the corresponding OCPD ratings — a reminder it is keyed to the device, not the conductor.)

Where 250.102 fits

Open the free PanelWright calculator — size the panel, the service, the neutral, the derating, and the voltage drop in your browser

Free, in-browser, zero tracking. Data never leaves your browser. Design aid only — verify against the adopted NEC edition.

Method, sources & honesty notes

Section text. Verbatim NEC 2017 (official NFPA text on disk, nec2017_full.txt): 250.102(A)–(E) (line 20450), Table 250.102(C)(1) + Notes 1–4 (line 20583), 250.24(C)(1) (line 18443), 250.28 (heading, line 18520), 250.30(A)(3)(a) (line 18703), 250.106 (line 20869). OCR line-wrap reflow normalized; the "250,30" and "shali/shail" OCR artifacts in the source corrected to "250.30"/"shall" (standard OCR class, disclosed); 250.28(D)(1) quoted in shortened form (elided lead-in marked). No other wording altered.

Table values (7 rows + 12.5% top row). The on-disk 2017 OCR interleaves the table's columns (row labels wrap to their own lines), so the rows were parsed from the OCR layout row-by-row and cross-checked this session against zing2.app (nec-250-102-c-1-bonding, all three edition tabs — 2020, 2023, 2026 — fetched 2026-09-01: identical 7 rows, top row "12.5% of Phase Area") and against the ELR 2023 change record (sectionID 1612, which states the table's purpose and Note 1's 12.5% rule verbatim). The 2017 OCR's "124% percent" (Note 1) is documented as a garble for "12.5 percent" (resolved per the record + zing2); its "lor 1/0" row label = "1 or 1/0 AWG." No other source was reachable this session (electricalcode.net 404 across the site; conduit.site URL structure changed; electricianu.com table URLs 404) — the provenance is 2017-OCR-parsed + zing2 ×3 editions + ELR ×2 records, all agreed.

Edition history. Section titles verified on the up.codes section index this session (2023 NEC: 250.102 "Grounded Conductor, Bonding Conductors, and Jumpers"; 250.106 "Lightning Protection Systems"). 250.102(A): 2023 code language quoted verbatim from the change record (ELR sectionID 1611) — identical to 2017. The on-disk 2020 scan ends at Art. 230 (no 2017→2020 word-diff claimed); the up.codes 2023 viewer body is account-gated (no 2023 full-body word-diff claimed beyond the two change records). 2026 renumber flagged.

Worked numbers. Every cmil / size / ampacity value computed by the shipped cores under node (compute_art23.js → calc_250102_cited.json): Ch. 9 Table 8 cmil via ch9Row/CH9_T8, Table 310.16 picks via pickConductor31016, column ampacities via T31016/T31016_COLS. The EX4 12.5% picks are the smallest standard size ≥ 12.5% of the ungrounded cmil area (the EX1/EX2/EX3/EX5/EX6 table-row lookups are the code itself, transcribed once and asserted by the public test suite). Zero hand math.