How to size the bonded (grounded) service conductor, the main bonding jumper, and the supply-side bonding jumper with Table 250.102(C)(1) — the full 7-row table plus Note 1's 12.5% rule, the parallel-conductor rules, separately derived systems, and the three-table ladder (250.66 / 250.102 / 250.122) that closes the grounding thread.
A service has three grounding-related conductors that people constantly mix up, and each is sized by a different table:
250.102 is the house where the supply-side sizing rules live: (A) what material a bonding jumper may be, (B) how it's attached, (C) how the supply-side bonding jumper is sized (the table + the parallel rules), (D) the load-side equipment bonding jumper (that's 250.122's job), and (E) installation (inside or outside the raceway, the 6-foot length limit). This page walks (A)–(E) verbatim, quotes the three sections that point at the same table (250.24(C), 250.28, 250.30(A)(3)), renders the full table, and computes six worked examples with the same core that ships in the calculator.
Grounded Conductor, Main Bonding Jumper, System Bonding Jumper, and Supply-Side Bonding Jumper for Alternating-Current Systems.
| Size of largest ungrounded conductor — copper (AWG/kcmil) | Size of largest ungrounded conductor — aluminum or copper-clad (AWG/kcmil) | Size of grounded conductor or bonding jumper — copper (AWG/kcmil) | Size of grounded conductor or bonding jumper — aluminum or copper-clad (AWG/kcmil) |
|---|---|---|---|
| 2 AWG or smaller | 1/0 AWG or smaller | 8 AWG | 6 AWG |
| 1 AWG or 1/0 AWG | 2/0 AWG or 3/0 AWG | 6 AWG | 4 AWG |
| 2/0 AWG or 3/0 AWG | 4/0 AWG or 250 kcmil | 4 AWG | 2 AWG |
| Over 3/0 AWG through 350 kcmil | Over 250 kcmil through 500 kcmil | 2 AWG | 1/0 AWG |
| Over 350 kcmil through 600 kcmil | Over 500 kcmil through 900 kcmil | 1/0 AWG | 3/0 AWG |
| Over 600 kcmil through 1100 kcmil | Over 900 kcmil through 1750 kcmil | 2/0 AWG | 4/0 AWG |
| Over 1100 kcmil | Over 1750 kcmil | 12.5% of ungrounded area (Note 1) | 12.5% of ungrounded area (Note 1) |
Like 250.122's (A) ceiling, Note 1 caps the 12.5% result: the bonded neutral is never required to be larger than the largest ungrounded conductor. For the table rows (not the 12.5% band) the ceiling never binds — the table's output is always smaller than its input.
Section title "Grounded Conductor, Bonding Conductors, and Jumpers" (250.102) verified on the up.codes section index for the 2023 NEC this session; "Lightning Protection Systems" (250.106) likewise. 2023 (A) verbatim, from the change record (ELR 2023 Grounding & Bonding course, sectionID 1611, fetched this session): "250.102 Grounded Conductor, Bonding Conductors, and Jumpers. (A) Material. Bonding jumpers shall be of copper, aluminum, copper-clad aluminum, or other corrosion-resistant material. A bonding jumper shall be a wire, bus, screw, or similar suitable conductor." — word-for-word identical to the 2017 text quoted above.
The table's current values, 2023, from the change record (sectionID 1612, fetched this session): the 2023 record describes the table as "used for sizing the grounded conductor, main bonding jumper, system bonding jumper, and supply-side bonding jumper," and — decisively — "Note 1 under Table 250.102(C)(1) contains the 12.5% rule to be used when the largest ungrounded conductor or equivalent area for parallel conductors is over 1100 kcmil copper or 1750 kcmil aluminum." The OCR trap, resolved: the on-disk 2017 OCR scan prints Note 1's factor as "124% percent" — a mangled "12.5 percent" (a "1" lost and a "2" doubled). The 2023 change record + zing2.app's three edition tabs (2020/2023/2026 all print "12.5% of Phase Area") settle it: 12.5%.
Honesty: the on-disk 2020 full-code scan ends at Article 230 (no 250.102 body for a 2017→2020 word-diff); the up.codes 2023 viewer body is account-gated, so the 2023 posture rests on the two change records above (250.102(A) quoted verbatim for 2023; the table's purpose + Note 1's 12.5% confirmed for 2023) + the live cross-check. The 2026 NEC renumber of Article 250 is flagged; this page cites 2017–2023 numbering.
| Item | Value (core) |
|---|---|
| Service OCPD | 100 A |
| Ungrounded service conductors (230.42(A)(2), 100% of 100 A) | pickConductor31016(100, 'cu', 75) = 3 AWG Cu (100 A @ 75 °C) |
| Table row (3 AWG Cu) | "2 AWG or smaller" |
| Bonded neutral / main bonding jumper (250.24(C)(1) / 250.28(D)(1)) | 8 AWG Cu / 6 AWG Al |
| GEC (Table 250.66, live 2023) | 8 AWG Cu / 6 AWG Al |
| EGC (Table 250.122, 100 A row) | 6 AWG Cu / 4 AWG Al |
| Result | phases 3 AWG Cu · bonded neutral 8 AWG Cu (two sizes smaller than phases) · EGC 6 AWG Cu (one size smaller than the bonded neutral) — three tables, one service |
| Item | Value (core) |
|---|---|
| Service OCPD | 200 A |
| Ungrounded conductors | pickConductor31016(200, 'cu', 75) = 3/0 Cu (200 A @ 75 °C) |
| Table row (3/0 Cu) | "2/0 AWG or 3/0 AWG" |
| Bonded neutral / main bonding jumper | 4 AWG Cu / 2 AWG Al |
| GEC (250.66) / EGC (250.122, 200 A row) | 4 AWG Cu / 2 AWG Al · 4 AWG Cu / 2 AWG Al |
| Result | at 3/0 phases the bonded neutral, GEC, and EGC all converge on 4 AWG Cu — a size-dependent coincidence, not a rule |
| Item | Value (core) |
|---|---|
| Ungrounded service conductors | 400 kcmil Cu (335 A @ 75 °C via T31016) |
| Table row | "Over 350 kcmil through 600 kcmil" |
| Bonded neutral / main bonding jumper | 1/0 AWG Cu / 3/0 AWG Al |
| GEC (250.66) | 1/0 AWG Cu / 3/0 AWG Al |
| Result | reproduces the 2023 change-record quiz (400 kcmil Cu ungrounded → options 4 AWG / 2 AWG / 1/0 / 2/0 → 1/0 AWG Cu) |
| Item | Value (core: Ch. 9 Table 8 cmil) |
|---|---|
| 1500 kcmil Cu phases × 12.5% | 1,500,000 × 0.125 = 187,500 cmil required |
| Smallest standard size ≥ 187,500 cmil | 4/0 Cu (211,600 cmil) — 3/0 (167,800) falls 19,700 cmil short |
| 1750 kcmil Al phases × 12.5% | 1,750,000 × 0.125 = 218,750 cmil required |
| Smallest standard size ≥ 218,750 cmil | 250 kcmil (250,000 cmil) |
| The ceiling | Note 1: never required larger than the largest ungrounded — does not bind in either case |
| GEC contrast | Table 250.66 has no 12.5% row — "Over 1100 / 1750" caps at 3/0 Cu / 250 kcmil Al (live 2023). The bonded neutral keeps scaling; the GEC does not. |
| Item | Value (core) |
|---|---|
| Installed sets (230.40, Exception No. 2) | 2 × 3/0 Cu (167,800 cmil each) + 2 × 4/0 Cu (211,600 cmil each) |
| Equivalent area (Note 3: largest sum of corresponding conductors) | 2 × 211,600 = 423,200 cmil |
| Single jumper (250.102(C)(2), second sentence) | one 2 AWG Cu / 1/0 AWG Al ("Over 3/0 through 350 kcmil" row on the equivalent) |
| Per-raceway jumpers (250.102(C)(2), first sentence) | 3/0 raceway → 4 AWG Cu / 2 AWG Al · 4/0 raceway → 2 AWG Cu / 1/0 AWG Al |
| Parallel grounded conductors (250.24(C)(2)) | grounded conductor in each raceway from its own ungrounded area, not smaller than 1/0 AWG (the 3/0 raceway's 4 AWG pick is overridden up to 1/0 AWG) |
| Item | Value (core) |
|---|---|
| Transformer | 100 kVA, 3∅, 240/208 V (system bonding jumper on the source side of the first disconnect) |
| Secondary full-load current | 100,000 VA ÷ (√3 × 208 V) = 277.6 A |
| Ungrounded conductors (310.16 @ 75 °C) | pickConductor31016(278, 'cu', 75) = 300 kcmil Cu (285 A; 250 kcmil Cu = 255 A is not enough) |
| Table row (300 kcmil Cu) | "Over 250 kcmil through 500 kcmil" |
| System bonding jumper (250.30(A)(3)(a) → 250.28(D)(1)) | 2 AWG Cu / 1/0 AWG Al |
| Result | sized on the derived system's own ungrounded conductors (300 kcmil Cu), not the kVA nameplate — same table as the main bonding jumper |
| Largest ungrounded | GEC — Table 250.66 | Bonded neutral / bonding jumper — Table 250.102(C)(1) | EGC — Table 250.122 |
|---|---|---|---|
| 2 AWG or smaller Cu | 8 AWG Cu / 6 AWG Al | 8 AWG Cu / 6 AWG Al | keyed to OCPD rating, not size (15 A → 14 AWG Cu) |
| 3/0 Cu / 500 kcmil Al band | 4 AWG Cu / 2 AWG Al | 4 AWG Cu / 2 AWG Al | 200 A device → 4 AWG Cu / 2 AWG Al |
| Over 600–1100 kcmil Cu | 2/0 Cu / 4/0 Al | 2/0 Cu / 4/0 Al | 800 A device → 1/0 Cu / 4/0 Al |
| Over 1100 kcmil Cu | 3/0 Cu / 250 kcmil Al — CAPPED, no further row | 12.5% of ungrounded area — keeps scaling (Note 1) | 4000 A device → 500 kcmil Cu (table end) |
For the first six size bands, Tables 250.66 and 250.102(C)(1) carry identical values — the same numbers, different conductors. The divergence is at the top: the GEC stops at 3/0 Cu while the bonded neutral keeps scaling with the 12.5% rule. (250.122's values are shown for the corresponding OCPD ratings — a reminder it is keyed to the device, not the conductor.)
Free, in-browser, zero tracking. Data never leaves your browser. Design aid only — verify against the adopted NEC edition.
Section text. Verbatim NEC 2017 (official NFPA text on disk, nec2017_full.txt): 250.102(A)–(E) (line 20450), Table 250.102(C)(1) + Notes 1–4 (line 20583), 250.24(C)(1) (line 18443), 250.28 (heading, line 18520), 250.30(A)(3)(a) (line 18703), 250.106 (line 20869). OCR line-wrap reflow normalized; the "250,30" and "shali/shail" OCR artifacts in the source corrected to "250.30"/"shall" (standard OCR class, disclosed); 250.28(D)(1) quoted in shortened form (elided lead-in marked). No other wording altered.
Table values (7 rows + 12.5% top row). The on-disk 2017 OCR interleaves the table's columns (row labels wrap to their own lines), so the rows were parsed from the OCR layout row-by-row and cross-checked this session against zing2.app (nec-250-102-c-1-bonding, all three edition tabs — 2020, 2023, 2026 — fetched 2026-09-01: identical 7 rows, top row "12.5% of Phase Area") and against the ELR 2023 change record (sectionID 1612, which states the table's purpose and Note 1's 12.5% rule verbatim). The 2017 OCR's "124% percent" (Note 1) is documented as a garble for "12.5 percent" (resolved per the record + zing2); its "lor 1/0" row label = "1 or 1/0 AWG." No other source was reachable this session (electricalcode.net 404 across the site; conduit.site URL structure changed; electricianu.com table URLs 404) — the provenance is 2017-OCR-parsed + zing2 ×3 editions + ELR ×2 records, all agreed.
Edition history. Section titles verified on the up.codes section index this session (2023 NEC: 250.102 "Grounded Conductor, Bonding Conductors, and Jumpers"; 250.106 "Lightning Protection Systems"). 250.102(A): 2023 code language quoted verbatim from the change record (ELR sectionID 1611) — identical to 2017. The on-disk 2020 scan ends at Art. 230 (no 2017→2020 word-diff claimed); the up.codes 2023 viewer body is account-gated (no 2023 full-body word-diff claimed beyond the two change records). 2026 renumber flagged.
Worked numbers. Every cmil / size / ampacity value computed by the shipped cores under node (compute_art23.js → calc_250102_cited.json): Ch. 9 Table 8 cmil via ch9Row/CH9_T8, Table 310.16 picks via pickConductor31016, column ampacities via T31016/T31016_COLS. The EX4 12.5% picks are the smallest standard size ≥ 12.5% of the ungrounded cmil area (the EX1/EX2/EX3/EX5/EX6 table-row lookups are the code itself, transcribed once and asserted by the public test suite). Zero hand math.