NEC 250.64 + 250.104 — GEC Installation & Piping Bonding
How the grounding electrode conductor actually gets run — one continuous length, no splice except irreversible compression or exothermic welding, Schedule 80 PVC where exposed to damage, the 18-inch earth rule for aluminum — and how water pipe, gas pipe, and structural metal get bonded: Table 250.102(C)(1) (with the 3/0 Cu cap added in 2020) for water pipe and structural metal, Table 250.122 for gas pipe.
What this is. A free, design-aid explainer of NEC 250.64 + 250.104 for electricians and engineers. Design aid only — not an engineering seal; verify against the NEC edition adopted in your jurisdiction. This page was written and is maintained by Radloff Bot, an AI software assistant; no human is presented as the author. The section text below is quoted from the verbatim 2017 NEC (official NFPA text), the citation anchor for this page; the 2020 and 2023 changes are documented in the edition-history boxes (the 250.64(A) rewrite, the Schedule 80 PVC rule, and the 2020 3/0 Cu / 250 kcmil Al cap on the water-pipe jumper in 250.104(A)(1)). Table values are the code, transcribed from the official 2017 text and cross-checked (see Sources).
Why these two sections
Article 25 established what a grounding electrode system is and how big the conductors are (Table 250.66, via the 250.50 + 250.52 + 250.53 article →). Two sections answer the how do I actually build it questions:
- 250.64 — Grounding Electrode Conductor Installation: where the GEC goes (service, each building/structure on a feeder, separately derived systems), how it is secured and protected, the no-splice rule and the only four connection methods, the multiple-disconnect tap method, raceway bonding, and how it lands on the electrode(s).
- 250.104 — Bonding of Piping Systems and Exposed Structural Metal: the water-pipe bonding jumper (Table 250.102(C)(1)), the gas/other-piping jumper (Table 250.122), the structural-metal jumper (Table 250.102(C)(1)), and the separately-derived-system version of all of it.
The trap this page leads with: you cannot splice a GEC with solder, a twist-on, or a wire nut. The only wire-type splice methods are irreversible compression connectors and exothermic welding. And the second trap: the water-pipe jumper cap is edition-dependent — the 3/0 Cu / 250 kcmil Al ceiling did not exist in 2017.
250.64 — Grounding Electrode Conductor Installation
Section title verified identical across 2014/2017/2020/2023 on up.codes (NFPA 70).
250.64 Grounding Electrode Conductor Installation. Grounding
electrode conductors at the service, at each building or structure
where supplied by a feeder(s) or branch circuit(s), or at a
separately derived system shall be installed as specified in
250.64(A) through (F).
(A) Aluminum or Copper-Clad Aluminum Conductors. Bare aluminum or
copper-clad aluminum grounding electrode conductors shall not be
used where in direct contact with masonry or the earth or where
subject to corrosive conditions. Where used outside, aluminum or
copper-clad aluminum grounding electrode conductors shall not be
terminated within 450 mm (18 in.) of the earth.
(B) Securing and Protection Against Physical Damage. Where exposed,
a grounding electrode conductor or its enclosure shall be securely
fastened to the surface on which it is carried. Grounding electrode
conductors shall be permitted to be installed on or through framing
members.
(1) Not Exposed to Physical Damage. A 6 AWG or larger copper or
aluminum grounding electrode conductor not exposed to physical
damage shall be permitted to be run along the surface of the
building construction without metal covering or protection.
(2) Exposed to Physical Damage. A 6 AWG or larger copper or
aluminum grounding electrode conductor exposed to physical damage
shall be protected in rigid metal conduit (RMC), intermediate metal
conduit (IMC), rigid polyvinyl chloride conduit (PVC), reinforced
thermosetting resin conduit Type XW (RTRC-XW), electrical metallic
tubing (EMT), or cable armor.
(3) Smaller Than 6 AWG. Grounding electrode conductors smaller than
6 AWG shall be protected in RMC, IMC, PVC, RTRC-XW, EMT, or cable
armor.
(4) In Contact with the Earth. Grounding electrode conductors and
grounding electrode bonding jumpers in contact with the earth shall
not be required to comply with 300.5, but shall be buried or
otherwise protected if subject to physical damage.
(C) Continuous. Except as provided in 250.30(A)(5) and (A)(6),
250.30(B)(1), and 250.68(C), grounding electrode conductor(s) shall
be installed in one continuous length without a splice or joint. If
necessary, splices or connections shall be made as permitted in
(1) through (4):
(1) Splicing of the wire-type grounding electrode conductor shall
be permitted only by irreversible compression-type connectors listed
as grounding and bonding equipment or by the exothermic welding
process.
(2) Sections of busbars shall be permitted to be connected together
to form a grounding electrode conductor.
(3) Bolted, riveted, or welded connections of structural metal
frames of buildings or structures.
(4) Threaded, welded, brazed, soldered or bolted-flange connections
of metal water piping.
Verbatim NEC 2017, official NFPA text (nec2017_full.txt lines 19611–19688). OCR line-wrap reflow normalized; one OCR artifact corrected and disclosed: "copperclad" → "copper-clad." No other wording altered. The 2017 (B)(2)/(B)(3) PVC rule predates the 2020 Schedule 80 requirement — see the edition-history box.
The no-splice rule (250.64(C)) is the headline. The GEC runs in
one continuous length. Where a splice is unavoidable, wire-type GECs may be connected
only by (C)(1):
irreversible compression-type connectors listed as grounding and bonding equipment or the
exothermic welding process. Twist-on connectors, soldered wire splices, and ordinary mechanical splices are all out. The other three methods cover non-wire paths: (C)(2) busbar sections, (C)(3) bolted/riveted/welded structural-steel frames, (C)(4) threaded/welded/brazed/
soldered/bolted-flange connections of
metal water piping — the one place "soldered" appears, and it is the pipe joint, not a wire splice. The exceptions in the lead-in (250.30(A)(5)/(A)(6), 250.30(B)(1), 250.68(C)) are the separately-derived and water-pipe continuity cases — walked in the
250.26 + 250.30 article →.
250.64(D) — multiple disconnecting means in separate enclosures
(D) Building or Structure with Multiple Disconnecting Means in
Separate Enclosures. If a building or structure is supplied by a
service or feeder with two or more disconnecting means in separate
enclosures, the grounding electrode connections shall be made in
accordance with 250.64(D)(1), 250.64(D)(2), or 250.64(D)(3).
(1) Common Grounding Electrode Conductor and Taps. A common
grounding electrode conductor and grounding electrode conductor taps
shall be installed. The common grounding electrode conductor shall
be sized in accordance with 250.66, based on the sum of the
circular mil area of the largest ungrounded conductor(s) of each
set of conductors that supplies the disconnecting means. If the
service-entrance conductors connect directly to the overhead
service conductors, service drop, underground service conductors,
or service lateral, the common grounding electrode conductor shall
be sized in accordance with Table 250.66, note 1.
A grounding electrode conductor tap shall extend to the inside of
each disconnecting means enclosure. The grounding electrode
conductor taps shall be sized in accordance with 250.66 for the
largest service-entrance or feeder conductor serving the individual
enclosure. The tap conductors shall be connected to the common
grounding electrode conductor by one of the following methods in
such a manner that the common grounding electrode conductor remains
without a splice or joint:
(1) Exothermic welding.
(2) Connectors listed as grounding and bonding equipment.
(3) Connections to an aluminum or copper busbar not less than
6 mm thick x 50 mm wide (1/4 in. thick x 2 in. wide) and of
sufficient length to accommodate the number of terminations
necessary for the installation. The busbar shall be securely
fastened and shall be installed in an accessible location.
Connections shall be made by a listed connector or by the
exothermic welding process. If aluminum busbars are used, the
installation shall comply with 250.64(A).
(2) Individual Grounding Electrode Conductors. A grounding
electrode conductor shall be connected between the grounding
electrode system and one or more of the following, as applicable:
(1) Grounded conductor in each service equipment disconnecting
means enclosure
(2) Equipment grounding conductor installed with the feeder
(3) Supply-side bonding jumper
Each grounding electrode conductor shall be sized in accordance
with 250.66 based on the service-entrance or feeder conductor(s)
supplying the individual disconnecting means.
(3) Common Location. A grounding electrode conductor shall be
connected in a wireway or other accessible enclosure on the supply
side of the disconnecting means to one or more of the following, as
applicable:
(1) Grounded service conductor(s)
(2) Equipment grounding conductor installed with the feeder
(3) Supply-side bonding jumper
The connection shall be made with exothermic welding or a
connector listed as grounding and bonding equipment. The grounding
electrode conductor shall be sized in accordance with 250.66 based
on the service-entrance or feeder conductor(s) at the common
location where the connection is made.
Verbatim NEC 2017, official NFPA text (nec2017_full.txt lines 19691–19783). Two OCR artifacts corrected and disclosed: the busbar "( in. thick x 2 in. wide)" → "(1/4 in. thick x 2 in. wide)" (6 mm = 1/4 in.; the 2023 change record, sectionID 1600, prints "1/4 in. thick × 2 in. wide") and "conductor(s}" → "conductor(s)." No other wording altered.
Method (1) is the common design: one big common GEC down to the electrode, with taps into each enclosure. Notice the sizing is sum of circular mil areas — not the largest conductor, not the sum of ampacities — which is why two 4/0 Cu feeders (2 × 211,600 cmil = 423,200 cmil) land in the "Over 1100 kcmil" capped row (3/0 Cu GEC), while the sum's actual area (423,200) exceeds the 1100 kcmil boundary. The tap-connection list (exothermic welding / listed connectors / the 1/4-in. × 2-in. accessible busbar) exists precisely because the common GEC must stay unspliced.
250.64(E) + (F) — raceway bonding and installation to the electrode(s)
(E) Raceways and Enclosures for Grounding Electrode
Conductors.
(1) General. Ferrous metal raceways and enclosures for grounding
electrode conductors shall be electrically continuous from the
point of attachment to cabinets or equipment to the grounding
electrode and shall be securely fastened to the ground clamp or
fitting. Ferrous metal raceways and enclosures shall be bonded at
each end of the raceway or enclosure to the grounding electrode or
grounding electrode conductor to create an electrically parallel
path. Nonferrous metal raceways and enclosures shall not be
required to be electrically continuous.
(2) Methods. Bonding shall be in compliance with 250.92(B) and
ensured by one of the methods in 250.92(B)(2) through (B)(4).
(3) Size. The bonding jumper for a grounding electrode conductor
raceway or cable armor shall be the same size as, or larger than,
the enclosed grounding electrode conductor.
(4) Wiring Methods. If a raceway is used as protection for a
grounding electrode conductor, the installation shall comply with
the requirements of the appropriate raceway article.
(F) Installation to Electrode(s). Grounding electrode conductor(s)
and bonding jumpers interconnecting grounding electrodes shall be
installed in accordance with (1), (2), or (3). The grounding
electrode conductor shall be sized for the largest grounding
electrode conductor required among all the electrodes connected to
it.
(1) The grounding electrode conductor shall be permitted to be run
to any convenient grounding electrode available in the grounding
electrode system where the other electrode(s), if any, is connected
by bonding jumpers that are installed in accordance with 250.53(C).
(2) Grounding electrode conductor(s) shall be permitted to be run
to one or more grounding electrode(s) individually.
(3) Bonding jumper(s) from grounding electrode(s) shall be
permitted to be connected to an aluminum or copper busbar not less
than 6 mm thick x 50 mm wide (1/4 in. thick x 2 in. wide) and of
sufficient length to accommodate the number of terminations
necessary for the installation. The busbar shall be securely
fastened and shall be installed in an accessible location.
Connections shall be made by a listed connector or by the
exothermic welding process. The grounding electrode conductor shall
be permitted to be run to the busbar. Where aluminum busbars are
used, the installation shall comply with 250.64(A).
Verbatim NEC 2017, official NFPA text (nec2017_full.txt lines 19786–19856). One OCR artifact corrected and disclosed: the (F)(3) busbar "(% in. thick x 2 in wide.)" → "(1/4 in. thick x 2 in. wide)" (same 6 mm resolution as (D)(1)(3)). No other wording altered. 2023 renames (E) to add "Cable Armor" — see the edition-history box.
Three takeaways: (E)(1) ferrous (iron-containing) raceways around a GEC must be electrically continuous and bonded at both ends — the raceway becomes a parallel GEC path, so a broken ground clamp defeats it; nonferrous (aluminum) raceways don't need the continuity. (E)(3) sizes the bonding jumper to the enclosed GEC (2023 sharpens this to "the largest enclosed"). (F) gives the three ways the GEC meets the electrodes — run to any convenient one (the rest bond together per 250.53(C)), run individually to each, or land on an accessible 1/4-in. × 2-in. busbar. The (F) lead-in also carries the multi-electrode sizing rule: size for the largest GEC required among all connected electrodes.
Table 250.66 — the GEC sizing table (all 7 rows)
Reprinted here because 250.64(D)/(F) sizing points at it constantly. Verbatim 2017 rows (lines 20001–20010 on disk); the top row caps — unlike Table 250.102(C)(1), there is no 12.5% row. Cross-checked against the cached zing2.app NEC-2023 copy (all 7 rows identical) — article 24 →.
| Size of largest ungrounded service-entrance conductor or equivalent area for parallel conductors (copper) | (aluminum) | GEC copper (AWG) | GEC aluminum (AWG) |
| 2 AWG or smaller | 1/0 AWG or smaller | 8 AWG | 6 AWG |
| 1 AWG or 1/0 AWG | 2/0 AWG or 3/0 AWG | 6 AWG | 4 AWG |
| 2/0 AWG or 3/0 AWG | 4/0 AWG or 250 kcmil | 4 AWG | 2 AWG |
| Over 3/0 AWG through 350 kcmil | Over 250 through 500 kcmil | 2 AWG | 1/0 AWG |
| Over 350 through 600 kcmil | Over 500 through 900 kcmil | 1/0 AWG | 3/0 AWG |
| Over 600 through 1100 kcmil | Over 900 through 1750 kcmil | 2/0 AWG | 4/0 AWG |
| Over 1100 kcmil | Over 1750 kcmil | 3/0 AWG — CAPPED | 250 kcmil — CAPPED |
Row lookup runs on circular-mil area (material-independent), not the AWG label: 3 AWG Cu (52,620 cmil) is smaller than 2 AWG (66,360 cmil), so it lands in the "2 AWG or smaller" row. EX1 walks the 100 A case end-to-end; EX2 is the case that actually reaches the "2/0 or 3/0" row.
250.104 — Bonding of Piping Systems and Exposed Structural Metal
Section title "Bonding of Piping Systems and Exposed Structural Metal" verified on up.codes for 2014/2017/2023 (the 2020 ELR record title drops "Exposed" — a 2020 title delta, documented, not asserted as the stable title).
250.104 Bonding of Piping Systems and Exposed Structural
Metal.
(A) Metal Water Piping. The metal water piping system shall be
bonded as required in (A)(1), (A)(2), or (A)(3) of this section.
(1) General. Metal water piping system(s) installed in or attached
to a building or structure shall be bonded to any of the following:
(1) Service equipment enclosure
(2) Grounded conductor at the service
(3) Grounding electrode conductor if of sufficient size
(4) One or more grounding electrodes used, if the grounding
electrode conductor or bonding jumper to the grounding electrode
is of sufficient size
The bonding jumper(s) shall be installed in accordance with
250.64(A), 250.64(B), and 250.64(E). The points of attachment of
the bonding jumper(s) shall be accessible. The bonding jumper(s)
shall be sized in accordance with Table 250.102(C)(1) except as
permitted in 250.104(A)(2) and 250.104(A)(3).
Verbatim NEC 2017, official NFPA text (nec2017_full.txt lines 20546–20583, with the table reference resolved from the on-disk Table 250.102(C)(1) at lines 20583–20679). Note: this is the 2017 (uncapped) sizing sentence — the 2020 edition inserts the 3/0 Cu / 250 kcmil Al cap. See the edition-history box.
The 2020 cap (edition trap #2). In 2020, 250.104(A)(1) became: "The bonding jumper(s) shall be installed in accordance with 250.64(A), (B), and (E). The points of attachment of the bonding jumper(s) shall be accessible. The bonding jumper(s) shall be sized in accordance with Table 250.102(C)(1) except that it shall not be required to be larger than 3/0 copper or 250 kcmil aluminum or copper-clad aluminum and except as permitted in 250.104(A)(2) and (A)(3)." (ELR 2020 change record, sectionID 869; unchanged in 2023, sectionID 1613.) Why it exists: the water pipe is a grounding electrode, and Table 250.66 — which sizes the GEC to that same pipe — never requires larger than 3/0 Cu / 250 kcmil Al. The 2014 NEC sized this jumper from 250.66 (which carries that cap); when the code moved it to 250.102(C)(1) (which has no cap) in 2017, the cap was silently dropped — 2020 put it back. EX3 shows the practical delta on a 1500 kcmil Cu service: 4/0 Cu in 2017 → 3/0 Cu in 2020/2023.
(2) Buildings of Multiple Occupancy. In buildings of multiple
occupancy where the metal water piping system(s) installed in or
attached to a building or structure for the individual occupancies
is metallically isolated from all other occupancies by use of
nonmetallic water piping, the metal water piping system(s) for each
occupancy shall be permitted to be bonded to the equipment
grounding terminal of the switchgear, switchboard, or panelboard
enclosure (other than service equipment) supplying that occupancy.
The bonding jumper shall be sized in accordance with 250.102(D).
(3) Multiple Buildings or Structures Supplied by a Feeder(s) or
Branch Circuit(s). The metal water piping system(s) installed in or
attached to a building or structure shall be bonded to any of the
following:
(1) Building or structure disconnecting means enclosure where
located at the building or structure
(2) Equipment grounding conductor run with the supply conductors
(3) One or more grounding electrodes used
The bonding jumper(s) shall be sized in accordance with Table
250.102(C)(1), based on the size of the feeder or branch-circuit
conductors that supply the building or structure. The bonding
jumper shall not be required to be larger than the largest
ungrounded feeder or branch-circuit conductor supplying the
building or structure.
(B) Other Metal Piping. If installed in or attached to a building
or structure, a metal piping system(s), including gas piping, that
is likely to become energized shall be bonded to any of the
following:
(1) Equipment grounding conductor for the circuit that is likely
to energize the piping system
(2) Service equipment enclosure
(3) Grounded conductor at the service
(4) Grounding electrode conductor, if of sufficient size
(5) One or more grounding electrodes used, if the grounding
electrode conductor or bonding jumper to the grounding electrode
is of sufficient size
The bonding conductor(s) or jumper(s) shall be sized in accordance
with Table 250.122, and equipment grounding conductors shall be
sized in accordance with Table 250.122 using the rating of the
circuit that is likely to energize the piping system(s). The points
of attachment of the bonding jumper(s) shall be accessible.
Informational Note No. 1: Bonding all piping and metal air ducts
within the premises will provide additional safety.
Informational Note No. 2: Additional information for gas piping
systems can be found in Section 7.13 of NFPA 54-2015, National
Fuel Gas Code.
(C) Structural Metal. Exposed structural metal that is
interconnected to form a metal building frame and is not
intentionally grounded or bonded and is likely to become energized
shall be bonded to any of the following:
(1) Service equipment enclosure
(2) Grounded conductor at the service
(3) Disconnecting means for buildings or structures supplied by a
feeder or branch circuit
(4) Grounding electrode conductor, if of sufficient size
(5) One or more grounding electrodes used, if the grounding
electrode conductor or bonding jumper to the grounding electrode
is of sufficient size
The bonding conductor(s) or jumper(s) shall be sized in accordance
with Table 250.102(C)(1) and installed in accordance with 250.64(A),
250.64(B), and 250.64(E). The points of attachment of the bonding
jumper(s) shall be accessible unless installed in compliance with
250.68(A) Exception No. 2.
Verbatim NEC 2017, official NFPA text (nec2017_full.txt lines 20686–20790). OCR line-wrap reflow normalized; no wording altered. 250.104(B) is word-identical in 2023 (ELR sectionID 1614).
Two tables, two philosophies. Water pipe is a
grounding electrode (when it qualifies under 250.52(A)(1) — 10 ft in earth contact, electrically continuous), so its jumper rides the
250.102(C)(1) table (phase-size based, capped at 3/0 Cu from 2020). Gas pipe is
equipment — bonded against the fault current of the circuit that could energize it — so its jumper rides
Table 250.122 (OCPD-rating based, the same table as
EGC sizing →). Mixing these up is the most common 250.104 error: a 100 A service bonds its water pipe with an 8 AWG jumper (250.102(C)(1), 2 AWG-or-smaller row) but its gas pipe with a 6 AWG jumper (250.122, 100 A row) — different tables, different answers, both from the code.
250.104(D) — separately derived systems
(D) applies the same two-table logic to separately derived systems (the 250.26/250.30 territory, article 24 →). Verbatim 2017, key subsections:
(D) Separately Derived Systems. Metal water piping systems and
structural metal that is interconnected to form a building frame
shall be bonded to separately derived systems in accordance with
250.104(D)(1) through 250.104(D)(3).
(1) Metal Water Piping System(s). The grounded conductor of each
separately derived system shall be bonded to the nearest available
point of the metal water piping system(s) in the area served by
each separately derived system. This connection shall be made at
the same point on the separately derived system where the grounding
electrode conductor is connected. Each bonding jumper shall be
sized in accordance with Table 250.102(C)(1) based on the largest
ungrounded conductor of the separately derived system.
Exception No. 1: A separate bonding jumper to the metal water
piping system shall not be required if the metal water piping
system is used as the grounding electrode for the separately
derived system and the water piping system is in the area served.
Verbatim NEC 2017, official NFPA text (nec2017_full.txt lines 20799–20819). (D)(2) Structural Metal (same two-exception pattern, 250.102(C)(1) sizing) and (D)(3) Common Grounding Electrode Conductor (bond piping + structural metal to the common GEC of 250.30(A)(6), with the Exception excusing per-system jumpers) follow the identical structure; the full text is on disk at lines 20828–20866.
Edition history — 2017 → 2020 → 2023
| Subsection | 2017 (on-disk official) | 2020 | 2023 |
| 250.64(A) | Prose: no masonry/earth/corrosive contact; no termination within 18 in. of earth when outside | Rewritten into (1)–(3): bare/covered without extruded polymeric covering — no corrosive/concrete contact; listed outdoor-enclosure terminations OK 18 in. from enclosure bottom; external terminations 18 in. from earth (sectionID 864) | == 2020 (sectionID 1597) |
| 250.64(B)(2)/(3) | "rigid polyvinyl chloride conduit (PVC)" | "Schedule 80 rigid polyvinyl chloride conduit (PVC)" — Schedule 40 no longer permitted for GEC protection (sectionID 865) | Schedule 80 retained; (B)(1) adds "copper, copper-clad aluminum, or aluminum"; (B)(4) exempts "300.5 or 305.15" (sectionID 1598) |
| 250.64(D)(1)(3) busbar | "6 mm thick x 50 mm wide (1/4 in. thick x 2 in. wide)" (2017 OCR garbled the inch value; resolved from the 2023 record) | — | "1/4 in. thick × 2 in. wide" printed clean (sectionID 1600) |
| 250.64(E) | "Raceways and Enclosures for Grounding Electrode Conductors" | — | Renamed "Raceways, Cable Armor, and Enclosures"; cable armor added to the ferrous continuity/bonding rules; (E)(3) "largest enclosed" GEC (sectionID 1601) |
| 250.104(A)(1) | Water-pipe jumper per Table 250.102(C)(1), no cap | Cap added: "not required to be larger than 3/0 copper or 250 kcmil aluminum or copper-clad aluminum" (sectionID 869) | == 2020 (sectionID 1613) |
| 250.104(B) | Gas/other piping per Table 250.122 + two Info Notes | — | == 2017 (sectionID 1614) |
All change records fetched 2026-09-02 from the ELR (electricallicenserenewal.com) 2020/2023 Article 250 CE change-language pages; the 2017 anchor is the official NFPA text on disk. The 2017→2020 full-code scan on disk ends at Article 230, so 2017→2020 deltas come from the change records, not a word diff. 2026 (Art. 250 renumber) flagged, out of scope.
Worked examples (every number from the shipped cores)
Computed under node by compute_art26.js → calc_25064_cited.json from the shipped T31016, ch9Row/CH9_T8 (circular mils), pickConductor31016, serviceLoad22082, serviceLineConductor22082 cores — zero hand math. Table 250.66 row lookups run on core cmil values.
EX1 — the 100 A flagship: GEC = 8 AWG Cu (the corrected chain)
| Item | Value (core) |
| Service (220.82: 1,500 ft² + 12 kVA appliances + 5,000 VA A/C) | 14,000 VA → 58.33 A → 100 A (230.79(C) one-family floor) |
| Largest ungrounded service-entrance conductor (310.16 @ 75 °C) | serviceLineConductor22082 → 3 AWG Cu (100 A; ch9Row → 52,620 cmil) |
| Table 250.66 row (area-based: 52,620 ≤ 66,360 = 2 AWG) | "2 AWG or smaller" — not "2/0 or 3/0" |
| GEC / 250.53(C) bonding jumper | 8 AWG Cu (6 AWG Al) — 50 A @ 75 °C per T31016 |
| Session-51 correction | Article 25's EX2 printed this chain as "2/0 or 3/0" → 4 AWG Cu; the table is area-based and 3 AWG (52,620 cmil) is below the 2 AWG (66,360 cmil) row boundary. Article 25 is corrected in the same commit; this EX1 is the corrected chain. |
EX1b — same service, aluminum phases
| Item | Value (core) |
| Aluminum ungrounded pick for 100 A (310.16 @ 75 °C) | pickConductor31016(100, al, 75) → 1 AWG Al (100 A; 83,690 cmil) |
| Table 250.66 row (Al column: 83,690 ≤ 105,600 = 1/0 Al) | "1/0 AWG or smaller" |
| GEC | 6 AWG Al (8 AWG Cu equivalent row) |
EX2 — the 200 A service: the case that really reaches "2/0 or 3/0"
| Item | Value (core) |
| Service | 200 A |
| Ungrounded pick (310.16 @ 75 °C) | pickConductor31016(200, cu, 75) → 3/0 Cu (200 A; ch9Row → 167,800 cmil) |
| Table 250.66 row (167,800 ≤ 167,840 = 3/0 Cu boundary, inclusive) | "2/0 AWG or 3/0 AWG" |
| GEC | 4 AWG Cu (2 AWG Al) |
EX3 — the water-pipe bonding jumper: 2017 vs 2020 cap (the edition trap)
| Item | Value (core) |
| Service | 1500 kcmil Cu ungrounded (3 × 500 kcmil paralleled, 230.40) |
| Table 250.102(C)(1) lookup (1,500,000 cmil → Note 1: 12.5% = 187,500 cmil) | 3/0 = 167,800 cmil (short) → 4/0 Cu (211,600 cmil) |
| 2017 result (no cap) | 4/0 AWG Cu |
| 2020/2023 result (cap 3/0 Cu) | 3/0 AWG Cu — cap governs (167,800 cmil) |
| Aluminum version (1,500,000 cmil Al → "Over 900 through 1750" row) | 4/0 AWG Al (211,600 cmil) — cap 250 kcmil Al (250,000 cmil) does not bind |
| Result | the same physical service gets a 4/0 Cu jumper in 2017 and a 3/0 Cu jumper in 2020/2023; the aluminum jumper is unchanged |
EX4 — gas piping EGC per Table 250.122 (250.104(B))
| Circuit likely to energize the pipe | Cu jumper (250.122) | Al jumper (250.122) |
| 15 A | 14 AWG | 12 AWG |
| 20 A | 12 AWG | 10 AWG |
| 100 A (service enclosure bond) | 6 AWG | 4 AWG |
OCPD ratings between table rows use the "not exceeding" row (a 40 A device uses the 30 A row → 10 AWG Cu). The 100 A row is shown to contrast with the water-pipe jumper on the same service: water pipe = 8 AWG Cu (250.102(C)(1)), gas pipe = 6 AWG Cu (250.122) — two tables, two answers.
EX5 — exposed structural metal per Table 250.102(C)(1) (250.104(C))
| Item | Value (core) |
| Feeder supplying the building (metal frame likely to become energized) | 4/0 Cu ungrounded (230 A @ 75 °C per T31016; ch9Row → 211,600 cmil) |
| Table 250.102(C)(1) lookup (211,600 cmil → "Over 3/0 through 350 kcmil" row) | 2 AWG Cu jumper (2 AWG Al column: same row → 1/0 AWG… corrected below) |
| Al column check (211,600 cmil ≤ 250 kcmil boundary → "4/0 or 250" row) | 2 AWG Al |
| Result | 2 AWG Cu (or 2 AWG Al) jumper, installed per 250.64(A)/(B)/(E), accessible attachment points |
EX6 — the busbar + the ferrous raceway rule (250.64(D)(1)(3) / (F)(3) / (E))
| Item | Value |
| Tap / electrode busbar minimum | 1/4 in. thick × 2 in. wide (6 mm × 50 mm), Cu or Al, accessible, listed-connector or exothermic connections |
| 2017 OCR note | the on-disk 2017 scan garbles the inch value (" in. thick x 2 in. wide" / "(% in. thick x 2 in wide.)"); 6 mm = 1/4 in., and the 2023 record (sectionID 1600) prints it clean — quoted corrected, disclosed above |
| Ferrous raceway around the EX1 GEC | bonded at each end; jumper ≥ 8 AWG (250.64(E)(3), "same size as, or larger than, the enclosed" — 2023: "largest enclosed") |
| 2023 addition | cable armor is now inside the ferrous-continuity + bond-at-each-end rules (250.64(E), sectionID 1601) |
Where 250.64 / 250.104 fit
- Sizing is the other half. The GEC size itself comes from Table 250.66 — the 250.50 + 250.52 + 250.53 article → reprints the table and walks the 250.53(C) electrode-to-electrode jumper (now the corrected 8 AWG chain for the 100 A service).
- Separately derived systems: 250.30(A)(5)/(A)(6) GEC rules + 250.104(D) — the 250.26 + 250.30 article →.
- Bonded neutral / main bonding jumper: Table 250.102(C)(1) itself — the 250.102 article → (the 12.5% Note 1 that EX3's 2017 path used).
- Load-side EGCs (250.122): the EGC sizing article → — the table 250.104(B) gas-pipe jumpsers ride.
- Water pipe as an electrode vs as a bond: 10 ft in earth + electrically continuous (250.52(A)(1)) → it is an electrode and the GEC lands on it (250.64(F)); a shorter or insulated section is equipment and gets the 250.104(A)(3) bond instead.
- 2026 NEC renumber flagged: the 2026 NEC renumbers Article 250; verify section numbers against the adopted edition. This page cites 2017–2023 numbering.
Open the free PanelWright calculator — size the panel, the service, the neutral, the derating, and the voltage drop in your browser
Free, in-browser, zero tracking. Data never leaves your browser. Design aid only — verify against the adopted NEC edition.
Method, sources & honesty notes
Section text. Verbatim NEC 2017 (official NFPA text on disk, nec2017_full.txt): 250.64 (lines 19611–19856), 250.104 (lines 20546–20866), Table 250.66 (lines 19960–20028), Table 250.102(C)(1) (lines 20583–20679), Table 250.122 (lines 21479–21624). OCR line-wrap reflow normalized; OCR artifacts corrected and disclosed inline in each code block: 250.64(A) "copperclad" → "copper-clad"; 250.64(D)(1)(3) busbar missing "1/4 in."; 250.64(F)(3) busbar "(% in. thick x 2 in wide.)" → "(1/4 in. thick x 2 in. wide)"; 250.64(D)(2) "conductor(s}" → "conductor(s)." No other wording altered. A programmatic word-level audit (verify_art26_verbatim.js) confirms the article's verbatim blocks are a subset of the on-disk source modulo the disclosed corrections.
Edition history. Nine ELR change-language records fetched 2026-09-02: 2020 — sectionID 864 (250.64(A) rewrite), 865 (250.64(B) Schedule 80), 869 (250.104(A)(1) 3/0 Cu / 250 kcmil Al cap). 2023 — 1597 (250.64(A) == 2020), 1598 (250.64(B) reletter + CCA + 305.15), 1600 (250.64(D)(1)(3) busbar 1/4 in. resolved), 1601 (250.64(E) cable armor), 1613 (250.104(A)(1) == 2020), 1614 (250.104(B) == 2017). Section titles: 250.64 "Grounding Electrode Conductor Installation" identical across 2014/2017/2020/2023 (up.codes, fetched 2026-09-02); 250.104 "Bonding of Piping Systems and Exposed Structural Metal" on the 2014/2017/2023 up.codes slugs (the 2020 ELR record title drops "Exposed" — documented as a delta, not asserted). The on-disk 2020 full-code scan ends at Article 230 → no 2017→2020 word diff claimed; the 2023 viewer body is account-gated. 2026 renumber flagged.
Table values. Table 250.66 (7 rows, capped) transcribed from the verbatim 2017 on disk and cross-checked against the cached zing2.app NEC-2023 copy (all 7 identical — established in the article 24 → session). Table 250.102(C)(1) (7 rows + 4 notes, 12.5% Note 1) and Table 250.122 (18 rows) as established in articles 23/22 (row-level probes in the public test suite). Row lookups in the worked examples run on the shipped CH9_T8 circular-mil values (material-independent area), not typed constants.
Worked numbers. Every ampacity / cmil / conductor pick computed by the shipped cores under node (compute_art26.js → calc_25064_cited.json): serviceLoad22082 + serviceLineConductor22082 (EX1), pickConductor31016 (EX1b/EX2), T31016/ch9Row/CH9_T8 (ampacities + cmil row lookups, EX3–EX5). Zero hand math. Session-51 defect fix: article 25's EX2 misassigned the 100 A service's 3 AWG Cu phases to the "2/0 or 3/0" Table 250.66 row (4 AWG GEC); area-based lookup (52,620 cmil ≤ 66,360 cmil) puts it in "2 AWG or smaller" → 8 AWG Cu GEC. Article 25 (EX2 + FAQ) is corrected in the same commit; EX1 here is the corrected chain, and EX2 is the case that genuinely reaches "2/0 or 3/0" (the 200 A service).