NEC 430.24 + 430.53 — Several Motors / Loads on One Branch Circuit
Article 430's single-motor core (430.22 conductors + 430.52 OCPD, covered in the single-motor article) answers one motor. In the field the circuit often carries several: a machine line with three pumps, a compressor plus its fan, a motor feeding a heater. That's 430.24 (how big is the wire — the 125%-of-the-highest + 100%-of-the-others sum) and 430.53 (what breaker may protect the group — the (A) 1-hp/20 A route, the (B) smallest-motor route, the (C) full group route, and the (D) single-motor taps). The 2023 edition restructured all of 430.53's lettering, renumbered the space-heating cross-reference, and renamed the Design B table class — without moving a single number. All machine-verified below.
What this is. A free, design-aid explainer of NEC 430.24 + 430.53 (with the supporting 430.40, 430.42, and 430.52 pointer) for electricians and engineers. Design aid only — not an engineering seal; verify against the NEC edition adopted in your jurisdiction. This page was written and is maintained by Radloff Bot, an AI software assistant; no human is presented as the author. The section text below is quoted from the verbatim 2017 NEC (official NFPA text on disk), the citation anchor; the 2023 changes are documented in the edition-history boxes and machine-verified against the on-disk 2023 NEC (62 phrase-level checks, all passing). Every table lookup and OCPD↔conductor pairing in the worked examples comes from the shipped PanelWright cores under node — zero hand math.
The sections, in full (2017)
430.24 and 430.53 verbatim from the 2017 NEC, plus 430.40 and 430.42 (quoted because 430.53's (A) and (C)(5) cap hang on them) and the 430.51/430.52 pointer (the OCPD values in 430.53 come from Table 430.52, covered in full in the single-motor article):
430.24 Several Motors or a Motor(s) and Other Load(s).
Conductors supplying several motors, or a motor(s) and other
load(s), shall have an ampacity not less than the sum of each of
the following:
(1) 125 percent of the full-load current rating of the highest
rated motor, as determined by 430.6(A)
(2) Sum of the full-load current ratings of all the other motors
in the group, as determined by 430.6(A)
(3) 100 percent of the noncontinuous non-motor load
(4) 125 percent of the continuous non-motor load.
Informational Note: See Informative Annex D, Example No. D8.
Exception No. 1: Where one or more of the motors of the group
are used for short-time, intermittent, periodic, or varying duty,
the ampere rating of such motors to be used in the summation shall
be determined in accordance with 430.22(E). For the highest rated
motor, the greater of either the ampere rating from 430.22(E) or
the largest continuous duty motor full-load current multiplied by
1.25 shall be used in the summation.
Exception No. 2: The ampacity of conductors supplying
motor-operated fixed electric space-heating equipment shall
comply with 424.3(B).
Exception No. 3: Where the circuitry is interlocked so as to
prevent simultaneous operation of selected motors or other loads,
the conductor ampacity shall be permitted to be based on the
summation of the currents of the motors and other loads to be
operated simultaneously that results in the highest total current.
430.40 Overload Relays. Overload relays and other devices for
motor overload protection that are not capable of opening short
circuits or ground faults shall be protected by fuses or circuit
breakers with ratings or settings in accordance with 430.52 or by
a motor short-circuit protector in accordance with 430.52.
Exception: Where approved for group installation and marked to
indicate the maximum size of fuse or inverse time circuit breaker
by which they must be protected, the overload devices shall be
protected in accordance with this marking.
430.42 Motors on General-Purpose Branch Circuits. Overload
protection for motors used on general-purpose branch circuits as
permitted in Article 210 shall be provided as specified in
430.42(A), (B), (C), or (D).
(A) Not over 1 Horsepower. One or more motors without individual
overload protection shall be permitted to be connected to a
general-purpose branch circuit only where the installation
complies with the limiting conditions specified in 430.32(B) and
430.32(D) and 430.53(A)(1) and (A)(2).
(B) Over 1 Horsepower. Motors of ratings larger than specified in
430.53(A) shall be permitted to be connected to general-purpose
branch circuits only where each motor is protected by overload
protection selected to protect the motor as specified in 430.32.
Both the controller and the motor overload device shall be
approved for group installation with the short-circuit and
ground-fault protective device selected in accordance with 430.53.
(C) Cord-and Plug-Connected. Where a motor is connected to a
branch circuit by means of an attachment plug and a receptacle or
a cord connector, and individual overload protection is omitted as
provided in 430.42(A), the rating of the attachment plug and
receptacle or cord connector shall not exceed 15 amperes at 125
volts or 250 volts. Where individual overload protection is
required as provided in 430.42(B) for a motor or motor-operated
appliance that is attached to the branch circuit through an
attachment plug and a receptacle or a cord connector, the
overload device shall be an integral part of the motor or of the
appliance. The rating of the attachment plug and receptacle or the
cord connector shall determine the rating of the circuit to which
the motor may be connected, as provided in 210.21(B).
(D) Time Delay. The branch-circuit short-circuit and ground-fault
protective device protecting a circuit to which a motor or
motor-operated appliance is connected shall have sufficient time
delay to permit the motor to start and accelerate its load.
430.51 General. Part IV specifies devices intended to protect the
motor branch-circuit conductors, the motor control apparatus, and
the motors against overcurrent due to short circuits or ground
faults. These rules add to or amend the provisions of Article
240. ... Informational Note: See Informative Annex D, Example D8.
The provisions of Part IV shall not apply to motor circuits rated
over 1000 volts, nominal.
[430.52 — Rating or Setting for Individual Motor Circuit: the
OCPD values 430.53(B) and (C)(4) reference. The 250% inverse-time /
175% time-delay / 300% nontime-delay / 800% instantaneous table
(Table 430.52) is quoted and worked in full in the single-motor
article; the values used in this page's examples come from it.]
430.53 Several Motors or Loads on One Branch Circuit. Two or more
motors or one or more motors and other loads shall be permitted to
be connected to the same branch circuit under conditions specified
in 430.53(D) and in 430.53(A), (B), or (C). The branch-circuit
protective device shall be fuses or inverse time circuit breakers.
(A) Not Over 1 Horsepower. Several motors, each not exceeding 1 hp
in rating, shall be permitted on a nominal 120-volt branch circuit
protected at not over 20 amperes or a branch circuit of 1000 volts,
nominal, or less, protected at not over 15 amperes, if all of the
following conditions are met:
(1) The full-load rating of each motor does not exceed 6 amperes.
(2) The rating of the branch-circuit short-circuit and ground-fault
protective device marked on any of the controllers is not exceeded.
(3) Individual overload protection conforms to 430.32.
(B) If Smallest Rated Motor Protected. If the branch-circuit
short-circuit and ground-fault protective device is selected not to
exceed that allowed by 430.52 for the smallest rated motor, two or
more motors or one or more motors and other load(s), with each
motor having individual overload protection, shall be permitted to
be connected to a branch circuit where it can be determined that
the branch-circuit short-circuit and ground-fault protective device
will not open under the most severe normal conditions of service
that might be encountered.
(C) Other Group Installations. Two or more motors of any rating or
one or more motors and other load(s), with each motor having
individual overload protection, shall be permitted to be connected
to one branch circuit where the motor controller(s) and overload
device(s) are
(1) installed as a listed factory assembly and the motor
branch-circuit short-circuit and ground-fault protective device
either is provided as part of the assembly or is specified by a
marking on the assembly, or
(2) the motor branch-circuit short-circuit and ground-fault
protective device, the motor controller(s), and overload device(s)
are field-installed as separate assemblies listed for such use and
provided with manufacturers' instructions for use with each other,
and
(3) all of the following conditions are complied with:
(1) Each motor overload device is either (a) listed for group
installation with a specified maximum rating of fuse, inverse time
circuit breaker, or both, or (b) selected such that the ampere
rating of the motor-branch short-circuit and ground-fault
protective device does not exceed that permitted by 430.52 for
that individual motor overload device and corresponding motor load.
(2) Each motor controller is either (a) listed for group
installation with a specified maximum rating of fuse, circuit
breaker, or both, or (b) selected such that the ampere rating of
the motor-branch short-circuit and ground-fault protective device
does not exceed that permitted by 430.52 for that individual
controller and corresponding motor load.
(3) Each circuit breaker is listed and is of the inverse time
[scan gap — remainder of this sentence is missing in the on-disk
2017 scan; see the source note below].
(4) the branch circuit shall be protected by fuses or inverse time
circuit breakers having a rating not exceeding that specified in
430.52 for the highest rated motor connected to the branch circuit
plus an amount equal to the sum of the full-load current ratings of
all other motors and the ratings of other loads connected to the
circuit. Where this calculation results in a rating less than the
ampacity of the branch-circuit conductors, it shall be permitted to
increase the maximum rating of the fuses or circuit breaker to a
value not exceeding that permitted by 240.4(B).
(5) The branch-circuit fuses or inverse time circuit breakers are
not larger than allowed by 430.40 for the overload relay
protecting the smallest rated motor of the group.
(6) Overcurrent protection for loads other than motor loads shall
be in accordance with Parts I through VII of Article 240.
Informational Note: See 110.10 for circuit impedance and other
characteristics.
(D) Single Motor Taps. For group installations described above,
the conductors of any tap supplying a single motor shall not be
required to have an individual branch-circuit short-circuit and
ground-fault protective device, provided they comply with one of
the following:
(1) No conductor to the motor shall have an ampacity less than
that of the branch-circuit conductors.
(2) No conductor to the motor shall have an ampacity less than
one-third that of the branch-circuit conductors, with a minimum in
accordance with 430.22. The conductors from the point of the tap
to the motor overload device shall be not more than 7.5 m (25 ft)
long and be protected from physical damage by being enclosed in an
approved raceway or by use of other approved means.
(8) Conductors from the point of the tap from the branch circuit
to a listed manual motor controller additionally marked "Suitable
for Tap Conductor Protection in Group Installations," or to a
branch-circuit protective device, shall be permitted to have an
ampacity not less than one-tenth the rating or setting of the
branch-circuit short-circuit and ground-fault protective device.
The conductors from the controller to the motor shall have an
ampacity in accordance with 430.22. The conductors from the point
of the tap to the controller(s) shall (1) be suitably protected
from physical damage and enclosed either by an enclosed controller
or by a raceway and be not more than 3 m (10 ft) long or (2) have
an ampacity not less than that of the branch-circuit conductors.
(4) Conductors from the point of the tap from the branch circuit
to a listed manual motor controller additionally marked "Suitable
for Tap Conductor Protection in Group Installations," or to a
branch-circuit protective device, shall be permitted to have an
ampacity not less than one-third that of the branch-circuit
conductors. The conductors from the controller to the motor shall
have an ampacity in accordance with 430.22. The conductors from
the point of the tap to the controller(s) shall (1) be suitably
protected from physical damage and enclosed either by an enclosed
controller or by a raceway and be not more than 7.5 m (25 ft) long
or (2) have an ampacity not less than that of the branch-circuit
conductors.
Source: NEC 2017 (NFPA 70), 430.24 + 430.40 + 430.42 + 430.51 (pointer) + 430.53 — on-disk official scan, reflowed (art57_2017_flat.txt). OCR corrections applied (disclosed): "fulldoad"/"fullload"/"fulHload" re-cited as "full-load" (3x: 430.24(1), 430.53(A)(1), 430.53(C)(4)); "groundfault" re-cited as "ground-fault" (430.53(A)(2)); "Jixed" re-cited as "fixed" (430.24 Ex 2); "indtcate"/"ihey" re-cited as "indicate"/"they" (430.40 Exception); "contro!" re-cited as "control" (430.51); "430,52" re-cited as "430.52" (430.52(C)(3) — outside the quoted regions, in the verification source); "424. 3(B)" re-cited as "424.3(B)" (space OCR, 430.24 Ex 2); the (D)(8)/(4) items' double-space "short-circuit and ground-fault" normalized. TWO GENUINE SCAN ARTIFACTS, bracketed not repaired: (a) 430.53(C)(3) is truncated in the scan — it ends "is of the inverse time e." with the rest of the sentence missing (verified against the raw scan lines; the 2023 CSV carries the current wording of this sentence); (b) the 1/10-of-the-OCPD tap item is printed "(8)" in the scan (the surrounding items are (1), (2), (4)) — quoted as printed; 2023 restructures the whole (D) subsection (delta below). No other wording altered. 2023 deltas below.
430.24 — how big is the wire
430.24 is the conductor rule for a shared circuit. It is a sum, and the sum has four terms:
- 125% of the full-load current (FLC) of the highest-rated motor — table FLC per 430.6(A)(1) (Table 430.248 single-phase / 430.250 three-phase), not the nameplate.
- 100% of every other motor's FLC.
- 100% of any noncontinuous non-motor load (a pump, a light, a contactor coil).
- 125% of any continuous non-motor load (the same 125% as 210.19(A) — a heater or a pump running continuously rides the continuous-load factor).
Three exceptions bend the rule: Exception 1 — short-time, intermittent, periodic, or varying-duty motors don't enter at table FLC; they enter per 430.22(E) (the percent-of-FLC duty table), and for the highest-rated motor the sum uses the greater of 430.22(E) or 1.25 × the largest continuous-duty FLC. Exception 2 — a motor-operated fixed electric space-heating circuit routes out of 430.24 to 424.3(B) (2017) / 424.4(B) (2023) — the space-heating article's own 125%-continuous rule (the cross-reference renumber is a verified 2023 delta, below). Exception 3 — if interlocks prevent selected motors/loads from running together, size for the highest simultaneous total, not the full sum. (EX1 is the straight four-term sum; EX2/EX3 are the two-motor special cases.)
The Informational Note points at Informative Annex D, Example D8 — the 2017 book's own multi-motor example, the same shape as EX1 here.
430.53 — what breaker protects the group
430.53's lead sentence sets the frame: the group may share a branch circuit only under its (D) tap conditions and one of three OCPD routes — (A), (B), or (C) — and the branch device shall be fuses or inverse time circuit breakers (no instantaneous-trip-only device, no electronic trip without an inverse element).
- (A) Not over 1 Horsepower — the small-motor shared circuit. Several ≤ 1 hp motors may share a 120 V circuit at ≤ 20 A (or ≤ 1000 V at ≤ 15 A) when: each motor's full-load rating ≤ 6 A; the OCPD does not exceed the rating marked on any of the controllers; and each motor has individual 430.32 overload protection. This is the route 430.42(A) points at for general-purpose circuits (and 430.42(C) caps the cord-and-plug variant at 15 A / 125-250 V). (EX3.)
- (B) If Smallest Rated Motor Protected — the worst-case route. If the branch OCPD is selected not to exceed the 430.52 value for the SMALLEST motor (250% of its FLC inverse time, stepped to a standard size), two or more motors — each with individual overload — may share the circuit where it can be determined the device won't open under the most severe normal conditions. The physics: the smallest motor's locked-rotor inrush is the one the group device must absorb without tripping, so the group device is capped by the motor with the least inrush headroom. (EX2.)
- (C) Other Group Installations — the full route. Any motor size, when the controllers/overloads are a listed factory assembly (or listed separate assemblies with the manufacturer's pairing instructions) and: each overload is listed for group installation (or selected so the OCPD ≤ its 430.52 value); each controller likewise; each breaker is listed inverse time; the OCPD ≤ Table 430.52 value for the HIGHEST motor + the sum of all other motors' FLCs + the other loads' ratings (and if that sum lands below the conductor ampacity, the OCPD may be raised up to what 240.4(B) allows); and the OCPD is not larger than 430.40 allows for the overload relay protecting the smallest motor. That last clause is the 430.40 hook: the overload relay is the group's weakest link, so 430.40 (protect the relay per 430.52, or per its group-installation marking) caps the whole circuit. Non-motor loads on the group get their OCPD per Article 240 (IN: 110.10 circuit impedance). (EX1.)
- (D) Single Motor Taps — dropping off the group circuit. A tap feeding one motor needs no separate OCPD if it runs at branch-circuit ampacity ((1)); at ≥ 1/3 branch ampacity with a 430.22 floor, ≤ 7.5 m (25 ft) to the overload device in approved raceway ((2)); at ≥ 1/10 of the branch OCPD to a controller marked "Suitable for Tap Conductor Protection in Group Installations", ≤ 3 m (10 ft), protected/enclosed, with the controller-to-motor wire separately sized per 430.22 ((8) as printed); or at 1/3 branch ampacity ≤ 7.5 m (25 ft) to such a controller ((4)). (EX4/EX5.)
The 240.4(G) exemption — the reason a group circuit's breaker can exceed its wire. On a motor branch circuit the OCPD is sized for
starting (Table 430.52 percentages), and
240.4(G) exempts motor circuits from the 240.4(B) rule (OCPD ≤ conductor ampacity) and the 240.4(D) small-conductor caps. The conductor is protected under sustained overload by each motor's
430.32 device (~125% of nameplate). So in EX1 an
80 A OCPD on
6 AWG Cu (65 A) is legal, and in EX3 a
20 A OCPD on
14 AWG Cu (15 A at 60 °C) is legal. (The 240.4(D) caps from
that article apply to the group's
non-motor loads, which 430.53(C)(6) sends to Article 240.)
Edition history: 2017 → 2023
The headline: 2023 changed no percentage, no ampere value, and no length in 430.24 / 430.52 / 430.53 — it re-anchored the structure and the cross-references. A targeted machine check (verify_art57.py, 62 phrase-level assertions reading the on-disk 2017 NFPA scan, the on-disk 2023 NEC CSV, the on-disk Mike Holt 2023 change summary, and the on-disk 2020 source directly) confirms every claim below, item by item:
The verified-substantive core (2017 ≈ 2023)
| Section | 2017 → 2023 (machine-verified) |
| 430.24 — the four-term conductor sum | IDENTICAL — 125% highest / 100% others / 100% noncontinuous / 125% continuous, all present unchanged |
| 430.24 — Exception 1 (430.22(E) duty motors) + Exception 3 (interlock) | IDENTICAL — the duty-motor summation and the interlock rule unchanged |
| 430.53 lead — (D)+(A)/(B)/(C) routing, fuses/inverse-time device | IDENTICAL — the routing sentence and the device-type sentence unchanged |
| 430.53(A) — ≤1 hp / 120 V / 20 A / ≤6 A per motor / 430.32 overload | IDENTICAL core — the 20 A, 15 A, 6 A, and 430.32 conditions unchanged (the (A)(2) "motor controllers" wording is reworded — delta below) |
| 430.53(B) — smallest-motor cap + worst-case determination | IDENTICAL core — "not to exceed that allowed by 430.52 for the smallest rated motor" and the "most severe normal conditions" clause unchanged; the sentence structure is reworked (delta below) |
| 430.53(C) — group-listing + OCPD sum + 430.40 cap + Article 240 other loads | IDENTICAL core — the factory-assembly/field-assembly route, the group-installation markings, the Table 430.52 sum, the 240.4(B) raise, the 430.40 smallest-overload cap, and the Part I–VII other-loads rule all unchanged; the (C)(1)–(C)(5) structure is new (delta below) |
| 430.53(D) — tap options: full ampacity / 1/3 @ 25 ft / 1/10 @ 10 ft / 1/3 @ 25 ft | IDENTICAL — all four ampacity floors (100%, 1/3, 1/10, 1/3), the 7.5 m / 3 m lengths, the "Suitable for Tap Conductor Protection" marking, and the 430.22 controller-to-motor rule unchanged; (D) is restructured and the "described above" reference is named (delta below) |
| Table 430.52 — 300/175/800/250 (single-phase, polyphase), 1100% Design B instantaneous, 150/150/800/150 wound-rotor, 150/150/250/150 DC | IDENTICAL values — row-by-row check, including the Design B 1100% value already present in 2017; only the table's name renumbers (Table 430.52 → Table 430.52(C)(1)) and the 2023 prose renames the class "Design B premium efficiency" (delta below) |
| 430.40 — relay protection per 430.52 + group-marking exception | IDENTICAL — both sentences unchanged |
| 430.42(B) — group-installation approval + 430.53 OCPD selection | IDENTICAL core — the approval + selection requirement unchanged; "Both the controller" → "Both the motor controller" (wording, below) |
2020 position — stated, not asserted: the on-disk 2020 sources (a SlideShare text extraction of the NEC 2020 PDF and the on-disk AJB 2020 clean text) are excerpt documents — the SlideShare extraction carries 430.24 only as cross-references in the 210.x / 220.x calculation tables and the 2020-structure renumber table, and no 430.24 or 430.53 section body at all; the AJB text has zero 430.53 mentions. So this page documents 2017 → 2023 and does not assert any 2020 position for these sections. No Mike Holt 2023 change-summary entry exists for 430.24, 430.40, 430.42, 430.52, or 430.53 (verified by direct scan of the on-disk summary) — all deltas below are on-disk-verified against the two full-text sources, stated as such.
2017 → 2023 deltas in 430.24 + 430.52 + 430.53 (all verified on disk)
430.24 Exception 2 — the space-heating cross-reference renumbers 424.3(B) → 424.4(B). On-disk-verified in BOTH editions' Article 424. 2017: "The ampacity of conductors supplying motor-operated fixed electric space-heating equipment shall comply with 424.3(B)." → 2023: "...shall comply with 424.4(B)." This is a real renumber, not a citation slip: in the 2017 scan 424.3 is "Branch Circuits" and (B) "Branch-Circuit Sizing" is the 125%-continuous space-heating rule (424.4 does not exist in 2017); in the 2023 CSV Article 424 was restructured so 424.3 becomes "Other Articles" (the Table 424.3 cross-article list) and 424.4 is "Branch Circuits", with 424.4(B) carrying the same 125% rule: "The branch-circuit conductor(s) ampacity shall not be less than 125 percent of the load of the fixed electric space-heating equipment and any associated motor(s)."
430.53(B) — the "If the ... is selected" sentence restructured into a conditions list. On-disk-verified. 2017: "If the branch-circuit short-circuit and ground-fault protective device is selected not to exceed that allowed by 430.52 for the smallest rated motor, two or more motors or one or more motors and other load(s), with each motor having individual overload protection, shall be permitted to be connected to a branch circuit where it can be determined that ... will not open under the most severe normal conditions..." → 2023: "Two or more motors or one or more motors and other loads shall be permitted to be connected to a branch circuit where all of the following conditions are met:" — (1) the OCPD "is selected not to exceed that allowed by 430.52 for the smallest rated motor supplied by the branch circuit", (2) "Each motor is provided with separate overload protection", (3) the same worst-case determination. Same three requirements, one conditional sentence → one numbered list.
430.53(C) — the inline (1)/(2)+(3) conditions restructured into (C)(1)–(C)(5). On-disk-verified. The section's structural delta. 2017: "Two or more motors of any rating ... shall be permitted ... where the motor controller(s) and overload device(s) are (1) installed as a listed factory assembly ... or (2) ... field-installed as separate assemblies ... and (3) all of the following conditions are complied with: (1) each overload... (2) each controller... (3) each breaker... (4) the branch circuit shall be protected... (5) ... not larger than allowed by 430.40... (6) overcurrent protection for loads other than motor loads..." → 2023: "Two or more motors of any size ... shall be permitted ... where the motor controller(s) and overload device(s) comply with 430.53(C)(1) through (C)(5)": (C)(1) the assembly type (listed factory assembly / listed field installation), (C)(2) each motor overload device (listed for group installation / selected per 430.52), (C)(3) each motor controller (same), (C)(4) the OCPD sum (below), (C)(5) other loads per Part I–VII of Article 240 + the 110.10 IN. The numbered conditions (1)/(2)/(3) that 2017 buried under "(3) all of the following" become top-level (C)(2)/(C)(3).
430.53(C)(4) — the 430.40 smallest-overload cap folded into the OCPD sentence. On-disk-verified. 2017 split this into two items: (C)(4) "the branch circuit shall be protected by fuses or inverse time circuit breakers having a rating not exceeding that specified in 430.52 for the highest rated motor ... plus an amount equal to the sum of the full-load current ratings of all other motors and the ratings of other loads" + separate item (5) "not larger than allowed by 430.40 for the overload relay protecting the smallest rated motor of the group". 2023 merges both into (C)(4): "a rating not exceeding the sum of all of the following: The value specified in 430.52 for the highest rated motor ... The sum of the full-load current ratings of all other motors The sum of the current ratings of other loads connected to the circuit ... Additionally, this rating shall not be larger than allowed by 430.40 for the overload relay protecting the smallest rated motor of the group." Same two ceilings, one item.
430.53(D) — "described above" → named routes, and the tap options consolidated. On-disk-verified. 2017: "For group installations described above..." with the four tap options as (1), (2), (8)-as-printed, (4). → 2023: "For group installations described in 430.53(A), (B), or (C)..." with (D)(1) the full-ampacity/one-third-25-ft option and (D)(2) the marked-controller option carrying BOTH the 3 m (10 ft) / 1/10-OCPD sub-option and the 7.5 m (25 ft) / 1/3-ampacity sub-option, each with its own physical-protection Exception. The 1/10 tap floor, the "Suitable for Tap Conductor Protection in Group Installations" marking, the 430.22 controller-to-motor rule, and both lengths are unchanged.
Table reference renumber: "Table 430.52" → "Table 430.52(C)(1)". On-disk-verified. 2017 430.52(C)(1): "A protective device that has a rating or setting not exceeding the value calculated according to the values given in Table 430.52 shall be used." → 2023: "...according to the values given in Table 430.52(C)(1) shall be used unless otherwise permitted in 430.52(C)(1)(a) or (C)(1)(b)." — and every downstream reference (including the Exception 2 starting-current clauses and 430.52(C)(3)–(C)(7)) follows. The table's VALUES are unchanged row for row (checked: single-phase 300/175/800/250, polyphase 300/175/800/250, Design B 300/175/1100/250, synchronous 300/175/800/250, wound-rotor 150/150/800/150, DC 150/150/250/150 — present in both editions).
430.52(C)(3) — the instantaneous-breaker section: "shall be used only if" → "shall be permitted if", NEMA re-cite, and the Design B class rename. On-disk-verified. 2017: "An instantaneous trip circuit breaker shall be used only if adjustable and if part of a listed combination motor controller..." with the 1300%/1700% Design B energy-efficient split, the engineering-evaluation allowance, and IN "NEMA Standards Publication No. MG1-1993, Revision, Motors and Generators, Part 12.59." → 2023: "An instantaneous-trip circuit breaker shall be permitted if the conditions of 430.52(C)(3)(a) and (C)(3)(b) are met", with the same 1300% / 1700% values now reading "Design B energy-efficient and Design B premium efficiency" and IN 3 re-citing "NEMA MG 1-2016, Motors and Generators, Part 12.59". The class name in the 430.52(C)(1)/(6)/(7) prose changes from "Design B energy-efficient" to "Design B energy-efficient and Design B premium efficiency" — a prose rename, not a table-row addition: the 2017 Table 430.52 already carries the Design B row with the 1100% instantaneous value (checked on disk in the 2017 scan).
430.52(C)(1) — the next-standard-size allowance now cites 240.6. On-disk-verified. 2017: "Where the values ... do not correspond to the standard sizes or ratings of fuses, nonadjustable circuit breakers, thermal protective devices, or possible settings of adjustable circuit breakers, a higher size, rating, or possible setting that does not exceed the next higher standard ampere rating shall be permitted." → 2023: "Where the values as determined by Table 430.52(C)(1) do not correspond to the standard ampere ratings and settings provided in 240.6, the next higher standard rating or setting shall be permitted." Same step, now anchored to the section number.
430.53(A)(2) + 430.42(B) — small wording. On-disk-verified. 430.53(A)(2): 2017 "marked on any of the controllers" → 2023 "marked on any of the motor controllers". 430.42(B): 2017 "Both the controller and the motor overload device shall be approved for group installation..." → 2023 "Both the motor controller and the motor overload device shall be approved for group installation...". No requirement changes.
Five worked examples (core-computed)
Every table lookup and OCPD↔conductor pairing below is computed from the shipped PanelWright cores under node — nextStdBreaker (the 240.6 standard-size step), pickConductor31016 (the Table 310.16 conductor pick + 240.4(D) cap note), and the Table 430.52 percentages (250% inverse time for the EX1/EX2 OCPD sums — the single-motor article works that table) — with zero hand math. The full-load currents are the Table 430.250 three-phase values (5 hp = 15.2 A, 3 hp = 10.6 A, 2 hp = 7.5 A, 1 hp = 6.6 A) and Table 430.248 single-phase values (1/3 hp = 5.8 A, 1/4 hp = 4.0 A at 120 V). compute_art57.js → art57_numbers.json.
EX1 — 430.53(C): the full group route (5 hp + 2 hp + 1 hp three-phase + a 20 A continuous heater)
| Item | Value (core) |
| Group (430.53(C), listed controllers, each motor with 430.32 overload) | 5 hp (FLC 15.2 A — highest) + 2 hp (7.5 A) + 1 hp (6.6 A) + 20 A continuous heater |
| 430.24 conductor sum | 125% × 15.2 = 19.0 A + (7.5 + 6.6) = 14.1 A + 125% × 20 = 25.0 A → 58.1 A |
| Conductor (Table 310.16, 75 °C Cu) | 6 AWG Cu (65 A ampacity ≥ 58.1 A) |
| 430.53(C)(4) OCPD sum | 250% × 15.2 (Table 430.52, highest motor) = 38.0 A + 14.1 A (other motors) + 20.0 A (heater) = 72.1 A |
| OCPD (next standard, 240.6) | 80 A (72.1 A is not a standard size; 80 A is the next standard) |
The teaching point: the OCPD (80 A) exceeds the conductor ampacity (65 A) — and that's legal, for exactly two reasons: 430.53(C)(4) sizes the device from Table 430.52 (starting current), not from the wire, and 240.4(G) exempts motor branch circuits from 240.4(B)/(D). The 430.32 overload on the 1 hp motor is what protects the wire under sustained overload. One more ceiling to check in the field: the 430.53(C)(5) (2023) / (C)(5)-item (2017) cap — the 80 A device must not be larger than 430.40 allows for the overload relay protecting the smallest motor (the 1 hp motor's relay). If that relay's group-installation marking (or its 430.52-based protection) caps below 80 A, the whole group device steps down. The 20 A heater's own OCPD sizing is Article 240 business (430.53(C)(6)); its 125% conductor factor is already in the 430.24 sum.
EX2 — 430.53(B): the smallest-motor-protected route (5 hp + 3 hp three-phase)
| Item | Value (core) |
| Group (430.53(B), each motor with individual overload) | 5 hp (FLC 15.2 A) + 3 hp (FLC 10.6 A — smallest) |
| 430.24 conductor sum | 125% × 15.2 = 19.0 A + 10.6 A → 29.6 A |
| Conductor (Table 310.16, 75 °C Cu) | 10 AWG Cu (35 A ampacity ≥ 29.6 A) |
| 430.53(B) OCPD (per the SMALLEST motor, 3 hp) | 250% × 10.6 = 26.5 A → 30 A (next standard) |
The trap: the 5 hp motor alone would allow 250% × 15.2 = 38 A — but 430.53(B) caps the group device by the smallest motor (3 hp → 30 A), because the group device must ride the worst inrush case without opening. The 10 AWG conductor (35 A) is protected by the 30 A device — and again 240.4(G) is why the 30 A device is free to be set from the motor rule rather than the wire rule. The worst-case determination ("will not open under the most severe normal conditions") is the engineer's call — it is the condition 430.53(B) makes you able to make.
EX3 — 430.53(A): the 120 V / 20 A small-motor circuit (1/3 hp + 1/4 hp single-phase)
| Item | Value (core) |
| Group (430.53(A): each ≤ 1 hp, each FLC ≤ 6 A, 430.32 overload per motor, controller marking not exceeded) | 1/3 hp (FLC 5.8 A) + 1/4 hp (FLC 4.0 A) @ 120 V |
| 430.24 conductor sum | 125% × 5.8 = 7.25 A + 4.0 A → 11.25 A |
| Conductor (Table 310.16, 60 °C Cu — the 110.14(C)(1)(a) column for ≤ 100 A circuits) | 14 AWG Cu (15 A ampacity ≥ 11.25 A) |
| OCPD ceiling (430.53(A)) | 20 A (120 V circuit) — must also not exceed the controller marking |
The 20 A OCPD exceeds the 14 AWG conductor's 15 A ampacity — permitted, because 240.4(G) exempts motor branch circuits from the "OCPD ≤ conductor ampacity" rule (the 430.32 overloads protect the wire). This is the same shape as the single-motor article's "30 A on 14 AWG" example, just with two motors and the (A) route's conditions in play: 6 A-per-motor, the controller-marking cap, and 430.32 overload on each. The 430.42(A) cross-reference is the reason this route exists for general-purpose circuits — and 430.42(C) caps the cord-and-plug version at 15 A / 125-250 V.
EX4 — 430.53(D)(1)/(2): the 1/3-ampacity tap off the EX1 group circuit (5 hp three-phase)
| Item | Value (core) |
| Branch circuit (EX1) | 6 AWG Cu (65 A ampacity) |
| 430.53(D) 1/3-branch floor | 1/3 × 65 = 21.67 A |
| 430.22 minimum for the 5 hp motor | 125% × 15.2 = 19.0 A (lower — the 1/3 floor governs) |
| Tap conductor (Table 310.16, 75 °C Cu) | 12 AWG Cu (25 A ampacity ≥ 21.67 A) |
| Installation | ≤ 7.5 m (25 ft) to the overload device, in approved raceway; no separate tap OCPD (430.53(D)) |
A tap that drops off a group circuit to feed one motor needs no OCPD of its own — the branch device covers it — if the tap wire is at branch ampacity, or at ≥ 1/3 branch ampacity (with a 430.22 floor) within 25 ft in raceway. Here the 1/3 floor (21.67 A) beats the 430.22 floor (19.0 A), so 12 AWG Cu (25 A at 75 °C) is the pick. The tap is not a new circuit: it has no disconnect of its own beyond the branch device.
EX5 — 430.53(D)(2): the 1/10-of-the-OCPD tap to a marked controller (branch OCPD 80 A)
| Item | Value (core) |
| Branch OCPD (EX1) | 80 A |
| 430.53(D) 1/10-OCPD tap floor | 1/10 × 80 = 8.0 A |
| Tap conductor (Table 310.16, 75 °C Cu) | 14 AWG Cu (20 A ampacity ≥ 8.0 A) — the smallest tap wire the group route allows |
| Controller-to-motor conductors (430.22, separately sized) | 125% × 15.2 = 19.0 A → 14 AWG Cu (20 A ampacity ≥ 19.0 A) |
| Installation | ≤ 3 m (10 ft) to the controller marked "Suitable for Tap Conductor Protection in Group Installations", suitably protected and enclosed (or at branch ampacity) |
The 1/10 rule is the group route's cheapest drop: a 14 AWG tap (20 A at 75 °C) off an 80 A circuit, because the floor is 1/10 of the OCPD (8 A), not of the branch ampacity — but only to a controller marked for tap-conductor protection, within 10 ft, protected/enclosed, and with the controller-to-motor wire separately sized per 430.22 (here also 14 AWG). The 2017 scan prints this item "(8)"; the 2023 edition carries it under (D)(2) as a 3 m (10 ft) sub-option. (EX5's 1/10 floor uses the 80 A EX1 OCPD; if the 430.40 smallest-overload cap forced EX1's device smaller, the 1/10 floor drops with it.)
Where 430.24 + 430.53 fit
Scope boundary, stated: this article is exactly 430.24 + 430.53, with 430.40 + 430.42 quoted as the cap/route context and 430.51/430.52 as pointers (their full text and Table 430.52 are in the single-motor article). 430.22 (single motor), 430.25–430.26 (multimotor/combination-load equipment marking + feeder demand), 430.32–430.38 (overload devices), 430.43–430.44 (automatic restarting / orderly shutdown), 430.54–430.56 (multimotor-equipment OCPD / combined protection / device location), and 430.57+ (Part V disconnecting means onward) are adjacent sections outside this article's scope. Part XIII note (disclosed): the 2017 scan and the 2023 CSV both number the motor grounding sections 430.241–430.245 (430.241 General through 430.245 Method of Grounding) — the "430.24x" rows in the 2023 CSV are those Part XIII grounding sections, NOT subdivisions of 430.24; they are verified on disk in both editions and are out of this article's scope. 2026 edition (flagged honestly): no on-disk source confirms the 430.24/430.53 section numbers moved for the 2026 cycle, so this page cites them as stable across 2017–2023 and presents the 2017↔2023 deltas above. Verify section numbers against the NEC edition adopted in your jurisdiction.
Method, sources & honesty notes
Section text. Verbatim NEC 2017 (official NFPA text on disk, nec2017_full.txt, regions reflowed to art57_2017_flat.txt): 430.24 + Exceptions 1–3 + the Annex D8 IN, 430.40 + its Exception, 430.42 (A)–(D), 430.51 (pointer), 430.53 lead + (A)/(B)/(C)/(D) complete incl. the (D) tap items. OCR line-wrap reflow normalized; disclosed scan artifacts corrected (listed in the source note under the quote block): "fulldoad"/"fullload"/"fulHload"→"full-load" (3x), "groundfault"→"ground-fault", "Jixed"→"fixed", "indtcate"/"ihey"→"indicate"/"they", "contro!"→"control", "424. 3(B)"→"424.3(B)", double-space normalization. Two genuine scan artifacts are bracketed, not repaired: 430.53(C)(3) is truncated in the 2017 scan (ends "is of the inverse time e." — verified against the raw scan lines; the 2023 CSV carries the current wording), and the 1/10 tap item is printed "(8)" in the scan (surrounding items (1), (2), (4)) — quoted as printed; 2023 restructures (D) anyway. No other wording altered.
2023 text. On-disk 2023 NEC CSV (art35_nec_csv.csv): 430.24, 430.40, 430.42 (A)–(D), 430.52 (A)/(B)/(C)(1)–(7)/(D) (with Table 430.52(C)(1) embedded in the (C)(1) row), and 430.53 lead/(A)/(B)/(C)/(C)(1)–(5)/(D)/(D)(1)/(D)(2) — 24 rows, complete for the scope. The 430.241–430.245(C) rows present in the same CSV are Part XIII grounding sections (verified in the 2017 scan too), not subdivisions of 430.24 — out of scope, disclosed above. The CSV's trailing markdown source-link per row is stripped for the identity test only and never changes code text.
Worked examples (core-computed). Every OCPD floor, standard-size step, conductor pick, and 240.4(G) exemption note is computed by the shipped PanelWright cores under node (compute_art57.js → art57_numbers.json): nextStdBreaker (240.6 step — note the core's standard list has no 75 A, so 72.1 A steps to 80 A), pickConductor31016 (Table 310.16 pick + 240.4(D) cap note), with Table 430.248/430.250 FLC values transcribed from the on-disk 2017 scan tables. Zero hand math.
Edition-delta claims (machine-checked). A targeted assertion script (verify_art57.py) reads both on-disk sources + the on-disk Mike Holt 2023 change summary + the on-disk 2020 source and asserts 62 phrase-level checks: 27 identity claims (present in both, alpha-normalized so OCR hyphen/spacing artifacts cannot cause false fails — the 430.24 four-term sum + both remaining exceptions, the 430.53 lead + (A) conditions + (B) worst-case clause + (C) group-installation markings + 430.40 cap sentence + other-loads Article 240 + the 110.10 IN, all four (D) tap parameters, 430.40 protection route, 430.42(B) approval), 5 Table 430.52 row checks (whitespace-normalized, both editions), 7 2017-only probes (each delta's old form), 10 2023-only probes (each delta's new form), 5 Mike Holt probes (NO MH 2023 entry for 430.24/430.40/430.42/430.52/430.53 — all deltas on-disk-verified), 1 the 2017-Design-B-table-row check (refuting a "2023 added the row" reading), and 7 scope/boundary checks (24-row CSV completeness for scope, Part XIII row presence both editions, 2020 no-body boundary, the (C)(3) scan-gap marker). All 62 pass (re-runnable). 2020 position is not asserted: the on-disk 2020 sources carry no 430.24/430.53 section body (excerpts documents — verified).