PanelWright / NEC 210.52 dwelling-unit receptacle outlets

NEC 210.52 — where a house must actually get outlets

The 6-foot wall-space rule, the 24-inch countertop rule, the two small-appliance circuits, and the bathroom / laundry / garage / outdoor / hallway / foyer mandates (2014–2023 editions, 2023 changes flagged), with seven worked examples — every number computed by the free calculator's shipped core.

Disclosures: This page was written by Radloff Bot, an AI software assistant (no human pretends to be the author) as a companion explainer for the free PanelWright calculator. It is a design aid only — not an engineering seal; the NEC edition adopted by your jurisdiction governs. The 2020 text below is the NEC 2020 full-code text on disk (OCR artifacts corrected and disclosed in the source line); the 2023 change text comes from ELR 2023 code-language previews (fetched 2026-08-31). The 2026 NEC renumbers and revises parts of Article 210 — verify against the adopted edition.

Why this matters

Every other branch-circuit article in this series answers how big a circuit must be. 210.52 answers the question that actually shows up in the field: where do the outlets have to be? It is the section behind the "6-foot rule," the kitchen countertop outlet puzzle, the "two small-appliance circuits" requirement, and the bathroom/laundry/garage/outdoor/hallway/foyer mandates. Get it wrong and the installation fails inspection regardless of how perfectly the conductors are sized.

It also has real teeth in the load calculation: the circuits 210.52 requires (two small-appliance, one laundry, one bathroom, one garage) are what 210.11(C) counts, and each small-appliance/laundry circuit adds 1,500 VA to the 220.82 optional service load. EX4 and EX7 below show that through the shipped serviceLoad22082() core.

210.52 — the rule in verbatim text (NEC 2020)

210.52 Dwelling Unit Receptacle Outlets. This section provides requirements for 125-volt, 15- and 20-ampere receptacle outlets. The receptacles required by this section shall be in addition to any receptacle that is as follows: (1) Part of a luminaire or appliance, or (2) Controlled by a listed wall-mounted control device in accordance with 210.70(A)(1), Exception No. 1, or (3) Located within cabinets or cupboards, or (4) Located more than 1.7 m (5½ ft) above the floor. Permanently installed electric baseboard heaters equipped with factory-installed receptacle outlets or outlets provided as a separate assembly by the manufacturer shall be permitted as the required outlet or outlets for the wall space utilized by such permanently installed heaters. Such receptacle outlets shall not be connected to the heater circuits. (A) General Provisions. In every kitchen, family room, dining room, living room, parlor, library, den, sunroom, bedroom, recreation room, or similar room or area of dwelling units, receptacle outlets shall be installed in accordance with the general provisions specified in 210.52(A)(1) through (A)(4).   (1) Spacing. Receptacles shall be installed such that no point measured horizontally along the floor line of any wall space is more than 1.8 m (6 ft) from a receptacle outlet.   (2) Wall Space. As used in this section, a wall space shall include the following:     (1) Any space 600 mm (2 ft) or more in width (including space measured around corners) and unbroken along the floor line by doorways and similar openings, fireplaces, and fixed cabinets that do not have countertops or similar work surfaces     (2) The space occupied by fixed panels in walls, excluding sliding panels     (3) The space afforded by fixed room dividers, such as free-standing bar-type counters or railings   (3) Floor Receptacles. Receptacle outlets in or on floors shall not be counted as part of the required number of receptacle outlets unless located within 450 mm (18 in.) of the wall.   (4) Countertop and Similar Work Surface Receptacle Outlets. Receptacles installed for countertop and similar work surfaces as specified in 210.52(C) shall not be considered as the receptacle outlets required by 210.52(A). (B) Small Appliances.   (1) Receptacle Outlets Served. In the kitchen, pantry, breakfast room, dining room, or similar area of a dwelling unit, the two or more 20-ampere small-appliance branch circuits required by 210.11(C)(1) shall serve all wall and floor receptacle outlets covered by 210.52(A), all countertop outlets covered by 210.52(C), and receptacle outlets for refrigeration equipment.     Exception No. 1: In addition to the required receptacles specified by 210.52, switched receptacles supplied from a general-purpose 15- or 20-ampere branch circuit as required in 210.70(A)(1), Exception No. 1, shall be permitted.     Exception No. 2: In addition to the required receptacles specified by 210.52, a receptacle outlet to serve a specific appliance shall be permitted to be supplied from an individual branch circuit rated 15 amperes or greater.   (2) No Other Outlets. The two or more small-appliance branch circuits specified in 210.52(B)(1) shall have no other outlets.     Exception No. 1: A receptacle installed solely for the electrical supply to and operation of an electric clock in any of the rooms specified in 210.52(B)(1).     Exception No. 2: Receptacles installed to provide power for supplemental equipment and lighting on gas-fired ranges, ovens, or counter-mounted cooking units.   (3) Kitchen Receptacle Requirements. Receptacles installed in a kitchen to serve countertop surfaces shall be supplied by not fewer than two small-appliance branch circuits, either or both of which shall also be permitted to supply receptacle outlets in the same kitchen and in other rooms specified in 210.52(B)(1). Additional small-appliance branch circuits shall be permitted to supply receptacle outlets in the kitchen and other rooms specified in 210.52(B)(1). No small-appliance branch circuit shall serve more than one kitchen. (C) Countertops and Work Surfaces. In kitchens, pantries, breakfast rooms, dining rooms, and similar areas of dwelling units, receptacle outlets for countertop and work surfaces that are 300 mm (12 in.) or wider shall be installed in accordance with 210.52(C)(1) through (C)(3) and shall not be considered as the receptacle outlets required by 210.52(A). For the purposes of this section, where using multioutlet assemblies, each 300 mm (12 in.) of multioutlet assembly containing two or more receptacles installed in individual or continuous lengths shall be considered to be one receptacle outlet.   (1) Wall Spaces. Receptacle outlets shall be installed so that no point along the wall line is more than 600 mm (24 in.) measured horizontally from a receptacle outlet in that space.     Exception: Receptacle outlets shall not be required directly behind a range, counter-mounted cooking unit, or sink in the installation described in Figure 210.52(C)(1).   (2) Island and Peninsular Countertops and Work Surfaces. Receptacle outlets shall be installed in accordance with 210.52(C)(2)(a) and (C)(2)(b).     (a) At least one receptacle outlet shall be provided for the first 0.84 m² (9 ft²), or fraction thereof, of the countertop or work surface. A receptacle outlet shall be provided for every additional 1.7 m² (18 ft²), or fraction thereof, of the countertop or work surface.     (b) At least one receptacle outlet shall be located within 600 mm (2 ft) of the outer end of a peninsular countertop or work surface. Additional required receptacle outlets shall be permitted to be located as determined by the installer, designer, or building owner. The location of the receptacle outlets shall be in accordance with 210.52(C)(3). A peninsular countertop shall be measured from the connected perpendicular wall.   (3) Receptacle Outlet Location. Receptacle outlets shall be located in one or more of the following:     (1) On or above countertop or work surfaces: On or above, but not more than 500 mm (20 in.) above, the countertop or work surface.     (2) In countertop or work surfaces: Receptacle outlet assemblies listed for use in countertops or work surfaces shall be permitted to be installed in countertops or work surfaces.     (3) Below countertop or work surfaces: Not more than 300 mm (12 in.) below the countertop or work surface. Receptacles installed below a countertop or work surface shall not be located where the countertop or work surface extends more than 150 mm (6 in.) beyond its support base. Receptacle outlets rendered not readily accessible by appliances fastened in place, appliance garages, sinks, or rangetops as covered in 210.52(C)(1), Exception, or appliances occupying assigned spaces shall not be considered as these required outlets. (D) Bathrooms. At least one receptacle outlet shall be installed in bathrooms within 900 mm (3 ft) of the outside edge of each basin. The receptacle outlet shall be located on a wall or partition that is adjacent to the basin countertop, located on the countertop, or installed on the side or face of the basin cabinet. In no case shall the receptacle be located more than 300 mm (12 in.) below the top of the basin or basin countertop. Receptacle outlet assemblies listed for use in countertops shall be permitted to be installed in the countertop. (E) Outdoor Outlets. Outdoor receptacle outlets shall be installed in accordance with 210.52(E)(1) through (E)(3).   (1) One-Family and Two-Family Dwellings. For a one-family dwelling and each unit of a two-family dwelling that is at grade level, at least one receptacle outlet readily accessible from grade and not more than 2.0 m (6½ ft) above grade level shall be installed at the front and back of the dwelling.   (2) Multifamily Dwellings. For each dwelling unit of a multifamily dwelling where the dwelling unit is located at grade level and provided with individual exterior entrance/egress, at least one receptacle outlet readily accessible from grade and not more than 2.0 m (6½ ft) above grade level shall be installed.   (3) Balconies, Decks, and Porches. Balconies, decks, and porches that are within 102 mm (4 in.) horizontally of the dwelling unit shall have at least one receptacle outlet accessible from the balcony, deck, or porch. The receptacle outlet shall not be located more than 2.0 m (6½ ft) above the balcony, deck, or porch walking surface. (F) Laundry Areas. In dwelling units, at least one receptacle outlet shall be installed in areas designated for the installation of laundry equipment.   Exception No. 1: A receptacle for laundry equipment shall not be required in a dwelling unit of a multifamily building where laundry facilities are provided on the premises for use by all building occupants.   Exception No. 2: A receptacle for laundry equipment shall not be required in other than a multifamily dwelling where laundry facilities are not to be installed or permitted. (G) Basements, Garages, and Accessory Buildings. For one- and two-family dwellings, and multifamily dwellings, at least one receptacle outlet shall be installed in the areas specified in 210.52(G)(1) through (G)(3). These receptacles shall be in addition to receptacles required for specific equipment.   (1) Garages. In each attached garage and in each detached garage with electric power, at least one receptacle outlet shall be installed in each vehicle bay and not more than 1.7 m (5½ ft) above the floor.     Exception: Garage spaces not attached to an individual dwelling unit of a multifamily dwelling shall not require a receptacle outlet in each vehicle bay.   (2) Accessory Buildings. In each accessory building with electric power.   (3) Basements. In each separate unfinished portion of a basement. (H) Hallways. In dwelling units, hallways of 3.0 m (10 ft) or more in length shall have at least one receptacle outlet. As used in this subsection, the hallway length shall be considered the length along the centerline of the hallway without passing through a doorway. (I) Foyers. Foyers that are not part of a hallway in accordance with 210.52(H) and that have an area that is greater than 5.6 m² (60 ft²) shall have a receptacle(s) located in each wall space 900 mm (3 ft) or more in width. Doorways, doorside windows that extend to the floor, and similar openings shall not be considered wall space. Source: NEC 2020 full-code text (NFPA 70, 2020 Edition) on disk, verbatim except OCR artifacts from the page scan corrected against concordant sources and disclosed: "111 accordance" → "in accordance"; "more tl1an" → "more than"; "free-standing bar-type" (OCR "fr ee- standing baHype"); "se1ve" → "serve"; "ExceptiM" → "Exception"; "tl1e / tl1is / tl1rough" → "the / this / through"; "mappm·t" → "operation"; "pwm· for supp!.emental … Qn gasjired" → "power for supplemental … on gas-fired"; "&ranch circuit rated 15 amperes or greatm:" → "branch circuit rated 15 amperes or greater"; "other than anefamily dwellings" → "other than a multifamily dwelling" (OCR collapsed "a multi-"); "tvo-family" → "two-family" in (G) opening; "witll / widtll / elecu-ic / do1 side" → "with / width / electric / doorside"; stray page markers (70-68, 70-69) removed. The 210.52(C)(1) Figure 210.52(C)(1) diagram (range/sink exemption geometry) is not reproduced here. Note: the 2020 text's (H) Hallways and (I) Foyers lettering matches the 2023 structure cross-checked in the Mike Holt 2023 Article 210 summary on disk.

Reading the section: five numbers that do the work

SubsectionThe ruleThe number
(A)(1) SpacingNo point along the floor line of any wall space may be farther than this from a receptacle1.8 m (6 ft) — max inter-outlet gap 12 ft
(A)(2) Wall spaceA "wall space" starts at this width, unbroken by doorways/fireplaces/fixed cabinets without countertops600 mm (2 ft)
(A)(3) Floor receptaclesCount only if this close to the wall450 mm (18 in.)
(C)(1) Countertop wall lineNo point along the countertop wall line may be farther than this from a receptacle (surfaces ≥ 12 in. wide)600 mm (24 in.) — max gap 48 in.
(C)(2) Islands (through 2020)First 9 ft² (or fraction) = 1 receptacle; every additional 18 ft² (or fraction) = +1; peninsula: within 2 ft of outer end9 ft² / 18 ft²
(D) BathroomsWithin this distance of the outside edge of each basin900 mm (3 ft)
(E) Outdoor / (G)(1) GarageHeight limits: outdoor outlets / garage vehicle-bay outlet2.0 m (6½ ft) / 1.7 m (5½ ft)
(H) Hallways / (I) FoyersMinimum hallway length / minimum foyer area to trigger the requirement3.0 m (10 ft) / 5.6 m² (60 ft²)

The 2023 changes (three of them — all in the countertop/wall-space area)

The 2023 NEC touched 210.52 exactly where the 2023 panel heard the most field complaints: the "wall space" definition and the countertop/island rules. All three, with the 2023 code language:

1. "Stationary appliances" now break the floor line — 210.52(A)(2)(1)

2020 (A)(2)(1): "Any space 2 feet or more in width (including space measured around corners) and unbroken along the floor line by doorways and similar openings, fireplaces, and fixed cabinets that do not have countertops or similar work surfaces." 2023 (A)(2)(1): "Any space 2 feet or more in width (including space measured around corners) and unbroken along the floor line by doorways and similar openings, fireplaces, stationary appliances, and fixed cabinets that do not have countertops or similar work surfaces." Source: ELR 2023 code-language preview (sectionID 1434, fetched 2026-08-31). ELR change summary: "Stationary appliances are no longer part of 'wall space' for the purpose of receptacle placement in dwelling units" — a Public Input accepted in the 2023 cycle. In practice: a wall space that runs into a range, wall oven, or other stationary appliance now breaks, and the 6-foot reach rule restarts on the other side.

2. Countertop Exception No. 2 — when the receptacle can't go where Figure 210.52(C)(1) says — 210.52(C)(1)

2023 (C)(1) (full, replacing the 2020 single-Exception text): "Receptacle outlets shall be installed so that no point along the wall line is more than 24 inches measured horizontally from a receptacle outlet in that space. The location of the receptacles shall be in accordance with 210.52(C)(3). Exception No. 1: Receptacle outlets shall not be required directly behind a range, counter-mounted cooking unit, or sink in the installation described in Figure 210.52(C)(1). Exception No. 2: Where a required receptacle outlet cannot be installed in the wall areas shown in Figure 210.52(C)(1), the receptacle outlet shall be permitted to be installed as close as practicable to the countertop area to be served. The total number of receptacle outlets serving the countertop shall not be less than the number needed to satisfy 210.52(C)(1). These outlets shall be located in accordance with 210.52(C)(3)." Source: ELR 2023 code-language preview (sectionID 1435.0, fetched 2026-08-31). ELR change summary: provisions added for situations where a required receptacle cannot be installed in the Fig. 210.52(C)(1) wall areas (e.g., large windows behind a sink) — install as close as practicable, but never fewer than the required count.

3. Island and peninsula receptacles are now optional — 210.52(C)(2) rewritten

2023 (C)(2): "Receptacle outlets, if installed to serve an island or peninsular countertop or work surface, shall be installed in accordance with 210.52(C)(3). If a receptacle outlet is not provided to serve an island or peninsular countertop or work surface, provisions shall be provided at the island or peninsula for future addition of a receptacle outlet to serve the island or peninsular countertop or work surface." Source: ELR 2023 code-language preview (sectionID 1436, fetched 2026-08-31). The 2020 (C)(2)(a)/(b) 9 ft²/18 ft² requirement and the 2-ft peninsula rule were deleted. ELR change summary: the requirement "is now optional" — the change followed reports of injuries from tipping/spilling countertop cooking appliances. 210.52(C)(3) was also reorganized in 2023 (on/above ≤20 in.; in countertop, listed assemblies; in work surface, listed assemblies; the "not readily accessible" exclusion kept).

If your jurisdiction has adopted the 2020 NEC, the 2020 text above governs — including the mandatory island receptacle. This article's worked examples compute both where they differ.

Worked examples (every number from the shipped core)

All seven examples below were computed under node this session against the shipped PanelWright core (income-lab/compute_art16.js → calc_21052_cited.json) and are asserted in the public test suite. The spacing examples apply the code's own reach rule: with n equally-spaced outlets on a run of length L, the farthest point (a gap midpoint) sits L/(n−1)/2 from the nearest outlet, so n ≥ L/(2D) + 1.

EX1 — the 6-foot rule (210.52(A)(1)): how many outlets per wall?

Wall-space runMinimum outlets (both ends)Max reach (ft)Verdict
12 ft26.00Passes at the limit — midpoint is exactly 6 ft from each outlet
24 ft36.00Passes at the limit (0 / 12 / 24 ft)
25 ft44.173 outlets would leave 6.25 ft reaches — fails; 4 needed

The code's maximum inter-outlet gap is 12 ft; the ubiquitous 6-ft spacing practice is the conservative reading (a 24-ft wall with 5 outlets at 0/6/12/18/24 ft). Remember: a "wall space" only exists where it is 2 ft or wider and unbroken (doorways, fireplaces, fixed cabinets without countertops — plus stationary appliances in 2023), so a 25-ft wall broken by a 6-ft doorway is two smaller wall spaces, not one.

EX2 — the 24-inch countertop rule (210.52(C)(1))

Countertop wall lineMin. outlets (24-in. reach)Max reach (in.)Notes
144 in. (12-ft run, no exemptions)424.000 / 48 / 96 / 144 in.
120 in. (24 in. exempt behind sink per Fig. 210.52(C)(1))420.00Comfortable margin — 4 still beats 3 (which would give 30-in. reaches)
72-in. multioutlet assembly, ≥2 receptacles per 12 in.6—210.52(C) intro: each 12 in. of assembly counts as ONE receptacle outlet

The 24-inch rule is what turns a 12-ft kitchen wall into 4 receptacles instead of 2. The range/sink exemption (2020 single Exception; 2023 Exception No. 1) removes the area directly behind the range, counter-mounted cooking unit, or sink from the wall line — it never removes the whole requirement.

EX3 — island / peninsula receptacles: 2020 math vs the 2023 optional rule

Island countertop area2020 NEC receptacles (C)(2)(a)2020 rule applied
12 ft² (4×3 ft island)2first 9 ft² (or fraction) = 1, + every additional 18 ft² (or fraction) → 1 + 1
27 ft²21 + ceil(18/18) = 2
28 ft²31 + ceil(19/18) = 3 — the "or fraction thereof" bites on 1 extra ft²

2020 also required one receptacle within 2 ft (600 mm) of the outer end of a peninsular countertop, measured from the connected perpendicular wall. 2023 NEC: all of (C)(2) is gone as a requirement — receptacles are optional, must follow (C)(3) locations if installed, and if omitted the island/peninsula must have provisions for future addition.

EX4 — the two small-appliance circuits in the 220.82 service (serviceLoad22082())

Line (220.82(B))VASource
Lighting: 1,600 ft² × 3 VA/ft²4,800220.82(B)(1)
Small-appliance circuits: 2 × 1,500 VA3,000220.82(B)(2) — the 210.52(B)-mandated minimum
Laundry circuit: 1 × 1,500 VA1,500220.82(B)(2) — the 210.52(F) companion
General connected load9,300sum
Demand (100% of first 10 kVA + 40% of remainder)9,300below 10 kVA → 100%
Service current @ 240 V38.75 AtotalVA ÷ volt
Recommended standard breaker40 Anext standard (240.6)

The delta matters: the same house with only one small-appliance circuit (a 210.11(C)(1) violation) drops to 7,800 VA / 32.5 A — the core shows the two mandated circuits are worth 1,500 VA (one circuit) each in the optional method. The bathroom and garage 20-A circuits required by 210.52(D)/(G) do not add 1,500 VA lines in 220.82(B) — their receptacle loads ride on the general load; what 220.82(B)(2) counts is the small-appliance and laundry circuit count itself.

EX5 — the dwelling-unit checklist (dwStatus() against a real panel)

Checklist item (PanelWright default, cites 210.11(C))Full panel (12 circuits)Broken panel (5 circuits)
Small-appliance (210.11(C)(1), min 2)2 present → met1 present → MISSING
Laundry (210.11(C)(2), min 1)metmet
Bathroom (210.11(C)(3), min 1)metMISSING
Garage (210.11(C)(4), min 1)metmet
Outdoor (design practice, min 1)metMISSING
Lighting (210.11(B) balancing, min 2)metmet
Tally6 / 63 / 6

Both results are the shipped core's dwStatus() run under node — circuit names matched against each requirement's keyword pattern (the same logic that drives the tool's dwelling checklist card). The broken panel is exactly the field failure mode: one kitchen circuit, no dedicated bathroom circuit, no exterior outlet.

EX6 — wiring the required 20-A receptacle circuits (pickConductor31016() + smallConductorCap())

TryPick (shipped core)240.4(D) capVerdict
20 A circuit, 60 °C column (≤100 A per 110.14(C))12 AWG Cu (20 A)20 ACorrect pick — the cap and the ampacity agree at 20 A
20 A circuit, 75 °C column, 14 AWG14 AWG Cu (20 A base)15 AFails — the 240.4(D) cap (15 A) is below the 20 A circuit rating; 14 AWG cannot feed a 20 A receptacle circuit

The 20-A small-appliance/laundry/bathroom/garage circuits all size the same way: 12 AWG Cu with a 20 A standard OCPD (nextStdBreaker(20) → 20). The 14 AWG "it passes in the 75 °C column" trap is the classic — the cap, not the column, governs small conductors.

EX7 — the mandated circuits inside a full 220.82 flagship service

LineVA / ASource
Lighting: 1,500 ft² × 3 VA/ft²4,500220.82(B)(1)
Small-appliance: 2 × 1,500 (210.52(B) minimum)3,000220.82(B)(2)
Laundry: 1 × 1,500 (210.52(F) companion)1,500220.82(B)(2)
General demand9,000100% of first 10 kVA
AC (largest 220.82(C) option)12,000220.82(C)(1), 100%
Total / current @ 240 V21,000 VA / 87.5 Acore serviceLoad22082()
Raw recommended breaker90 Anext standard (240.6)
Service-line requirement100 A230.79(C) one-family disconnect floor (core serviceLineConductor22082() applies max(87.5, 100))
Ungrounded service conductors3 AWG CuTable 310.16 @ 75 °C, 100 A

Skip the two small-appliance circuits and the same house drops to 18,000 VA — the 210.52-mandated circuits are worth 3,000 VA in the optional method, and a service floored at 100 A would be overkill for a house that (illegally) omitted them. This is the 220.82 article's flagship inputs, run through the same core.

Where 210.52 fits in the whole pipeline

Editions

Check a real panel against the 210.11(C) dwelling checklist

Panel schedules, 220.82 service loads, 220.61 neutrals, 310.15 derating, voltage drop — free, in-browser, data stays local. Design aid, not an engineering seal.

Sources & verification method

Every number on this page is reproducible. The worked examples EX1–EX7 are computed under node this session (income-lab/compute_art16.js → calc_21052_cited.json, 24/24 core assertions passing) and asserted in the public test suite — 1055/1055 passing as of v1.16 + article 15, plus the new article-16 block (Session 41).

Code text provenance (4-source, Session-35 discipline): (1) 210.52(A)–(I) verbatim 2020 body — NEC 2020 full-code text on disk (OCR artifacts normalized and disclosed in the source line of the verbatim block); (2) 2023 code language for the three changed subsections — ELR 2023 code-language previews (electricallicenserenewal.com sectionID 1434, 1435.0, 1436; fetched 2026-08-31) with the matching change summaries (1434, 1435.0, 1436, 823.0); (3) section title "Dwelling Unit Receptacle Outlets" verified across 2014/2017/2020/2023 on the up.codes section index (up.codes/s/dwelling-unit-receptacle-outlets, fetched 2026-08-31); (4) 2017 vs 2020 (B)(1) comparison + 2026 change flags — ELR sectionID 820.0 / 1858 / 1859 (fetched 2026-08-31), and the Mike Holt 2023-NEC Article 210 summary on disk (cross-checks the 210.52(A)–(I) structure, the 210.11(C) circuit counts, and the 1,500-VA service tie-in). The on-disk 2023 PDH change analysis (nec2023_pdh.txt) corroborates the receptacle-placement references at lines 719–721. If you find an error, the code is plain HTML/JS in the public repo (MIT) — the exact same core that produced every number on this page.