How to size the breaker (or fuse) on a branch circuit — the (A) 125% continuous-load floor, the (B) conductor hand-off to 240.4, the (C) Table 240.3 equipment cap, and the (D) 210.21 outlet-device cap. Verbatim 2017 + 2020 code (word-identical), the 2023 posture, and eight worked examples computed with the shipped PanelWright cores.
210.20 answers one question: how big is the breaker (or fuse) that protects this branch circuit? It is the OCPD-sizing twin of 210.19(A), which sizes the conductors. 210.19(A) sets the conductor ampacity; 210.20 sets the overcurrent device that protects those conductors and the equipment on the circuit.
The section has four constraints, and they are not symmetric. One is a floor and three are ceilings:
The practical rule: 210.20(A) tells you the breaker can't be smaller than X; (C) and (D) tell you it can't be bigger than Y. The answer is the smallest standard breaker size (240.6) that is at least X and not more than Y.
| Subsection | Direction | Rule (2017 = 2020, word-identical) |
|---|---|---|
| (A) | FLOOR (min) | OCPD rating ≥ noncontinuous load + 125% of continuous load. Exception: if the assembly (including the OCPD) is listed for operation at 100% of its rating, the 125% requirement is dropped — rating ≥ sum of the loads. |
| (B) | Hand-off | Conductors protected per 240.4; flexible cords + fixture wires per 240.5. (This is where the 240.4(D) small-conductor OCPD caps live — 14 AWG Cu → 15 A, 12 AWG Cu → 20 A, 10 AWG Cu → 30 A.) |
| (C) | CEILING (max) | OCPD rating ≤ the value specified in the applicable article referenced by Table 240.3 for the equipment (motors → 430, AC → 440, heating → 424, welders → 630, etc.). |
| (D) | CEILING (max) | OCPD rating ≤ the value specified in 210.21 for the outlet devices (the Table 210.21(B)(3) receptacle-rating table, the (B)(2) max cord-and-plug load). |
Why the asymmetry matters: a light load never shrinks your breaker (210.20(A) is a floor, not a target). A heavy equipment rating or a small conductor caps your breaker (240.4(D) / 210.21). The two 125% and 80% numbers people confuse — 210.20(A)'s 125% (breaker floor) vs 210.21(B)(2)'s 80% (receptacle load ceiling) — come from two different sections doing two different jobs.
This is the rare edition where the answer is "it didn't change." The four-constraint structure — the (A) floor, the (B) 240.4 hand-off, the (C) Table 240.3 cap, the (D) 210.21 cap — is identical in 2017 and 2020. The value of this article is therefore the mechanism (how the floor + ceilings combine to pick a breaker) and the 2023 posture (what changed around 210.20 even though 210.20 itself did not).
Edition posture: 2017 and 2020 bodies are verbatim on disk (diffed programmatically — word-identical). 2023/2026 are change-log + reference-print claims only (the 2023/2026 bodies are not on disk). The 210.20 number is stable 2014–2023 (the two on-disk 2023 prints confirm; the 2014 edition is not on disk, so no 2014 claim is made). The 2026 NEC renumbers Article 210 (flagged site-wide).
For a given load, the working sequence is:
The trap in most real problems is step 1 — mislabeling a continuous load as noncontinuous (or vice versa) changes the floor. And the second trap is forgetting that 210.20(A) only ever sets the floor; a light load does not shrink the breaker, and a small conductor / heavy equipment caps it from the other side.
Every number below was computed by the real shipped PanelWright code (nextStdBreaker on the verified 240.6 standard list, pickConductor31016 on Table 310.16 (2023-verified 0/168 cells), smallConductorCap for the 240.4(D) caps, derate31015 for the 310.15 corrections) under node — compute_art33.js → calc_21020_cited.json — zero hand math.
| Item | Value |
|---|---|
| Load | 16 A continuous + 8 A noncontinuous, 120 V single-phase (2,880 VA total) |
| 210.20(A) floor | 8 + (1.25 × 16) = 28 A |
| Next standard size (240.6) | 30 A (28 A is not a standard size) |
| Conductor (Table 310.16, 75 °C Cu) | 10 AWG Cu — ampacity 35 A ≥ 30 A; 240.4(D) cap 30 A (matches the OCPD) |
| Item | Value |
|---|---|
| Load | 16 A continuous + 8 A noncontinuous (same load as EX1) |
| Assembly listed for 100% | 210.20(A) Exception: FLOOR = 16 + 8 = 24 A |
| Next standard size (240.6) | 25 A |
| Conductor (Table 310.16, 75 °C Cu) | 12 AWG Cu — ampacity 25 A ≥ 25 A; 240.4(D) cap 20 A is below 25 A, so 12 AWG is rejected → 10 AWG Cu is the smallest usable. The 125% Exception saved one breaker size and one conductor size here. |
| Item | Value |
|---|---|
| Load | 2,400 W / 120 V = 20 A noncontinuous (not a continuous load → no 125%) |
| 210.20(A) floor | 20 A → next standard size = 20 A |
| Conductor walk (Table 310.16, 75 °C Cu) | 14 AWG Cu has 20 A ampacity (passes 210.19(A)) BUT 240.4(D)(3) caps its OCPD at 15 A < 20 A → REJECTED. 12 AWG Cu (25 A ampacity, 240.4(D)(5) cap 20 A) is the smallest usable. |
| Result | 20 A breaker, 12 AWG Cu |
| Item | Value |
|---|---|
| Circuit | 15 A, 14 AWG Cu (the everyday bedroom/bath wire) |
| Ampacity (75 °C) | 14 AWG Cu = 20 A |
| 240.4(D)(3) cap | 15 A — exactly the circuit rating |
| Point | 210.20(A) only ever sets a floor; the 15 A here is a ceiling from 240.4(D). A 20 A breaker is not allowed on 14 AWG Cu even though the wire carries 20 A of ampacity. |
| Item | Value |
|---|---|
| Load | 1,200 W / 120 V = 10 A noncontinuous |
| Pre-2023 OCPD | 10 A is not on the 240.6 standard list (starts at 15 A) → smallest standard = 15 A; 12 AWG Al (240.4(D)(4) cap 15 A) is the aluminum size that fits |
| 2023 (ELR 1430, 210.18) | 10-ampere branch circuits permitted, with Exception No. 2: no receptacle outlets on a 10 A circuit |
| Point | 210.20 is UNCHANGED — the 10 A allowance is a 210.18 change. 210.20(A) is a floor, so it is satisfied by either 10 A or 15 A. |
| Rule | What it limits | On a 20 A circuit |
|---|---|---|
| 210.20(A) — 125% floor | The OCPD rating for continuous loads (× 1.25) | If 16 A is continuous: floor = 125% × 16 = 20 A (the circuit rating exactly) |
| 210.21(B)(2) — 80% ceiling | The max cord-and-plug-connected load a receptacle may carry (80% of circuit rating) | 20 A receptacle circuit → max 16 A of cord-and-plug load |
| Point | Different sections, different jobs | They agree numerically on a 20 A circuit (125% × 16 = 20; 80% of 20 = 16) but one sizes the breaker up and the other limits what you plug in. |
| Item | Value |
|---|---|
| Load | 4,800 W / 240 V = 20 A noncontinuous (a water-heater-style load) on a 30 A circuit |
| 210.20(A) floor | 20 A — but the circuit is already 30 A; the floor never shrinks the breaker |
| Conductor (Table 310.16, 75 °C Cu) | 10 AWG Cu — ampacity 35 A ≥ 30 A; 240.4(D)(7) cap 30 A (matches the OCPD) |
| Point | The breaker is set by the load's continuous portion and the equipment rating, not by "match the breaker to the wattage." 210.20(A) is a floor. |
| Item | Value |
|---|---|
| Load | 60 A continuous, 240 V; 35 °C ambient; 6 current-carrying conductors; 75 °C Cu |
| 210.20(A) floor | 1.25 × 60 = 75 A → next standard size = 80 A |
| Conductor (derate31015 core) | 2 AWG Cu — base ampacity 115 A × 0.80 (6 CCC) × 0.94 (35 °C) = 86.48 A derated ≥ 80 A → passes |
| Point | The 125% floor (210.20(A)) sets the 80 A OCPD; the 310.15 corrections (310.15(C) CCC + 310.15(B) ambient) then prove the conductor survives. 210.20(A) never sees the derating — it only sets the floor; the derating core does the conductor work. |
Free, in-browser, zero tracking. Data never leaves your browser. Design aid only — verify against the adopted NEC edition.
Section text. Verbatim NEC 2017 (official NFPA text on disk, nec2017_full.txt): 210.20 lines 10189–10222 (lead-in + (A)–(D), full section). Verbatim NEC 2020 (full-code scan on disk, slideshare_nec2020.txt): 210.20 chars 358636–359858 (lead-in + (A)–(D), full section). A programmatic word-level diff (verify_art33_diff.py) confirms the 2017 and 2020 bodies are word-identical; a byte-level verbatim audit (verify_art33_verbatim.py) re-derives both article code blocks from the on-disk sources and confirms they match modulo the disclosed OCR corrections (2017: 3 hyphen line-wrap reflows + header drop; 2020: 9 OCR artifact tokens + 1 page footer, machine-counted from the scan window).
Edition verification. 2020 change log (ELR) probed for a 210.20 record — none exists (the fetched Article 210 2020 records are sectionIDs 807–816, 818, 819, 821, 822, all other sections). 2023 change log (ELR) probed for a 210.20 record — none exists (the fetched Article 210 2023 records are 1428, 1430, 1431, 1432, 1433, 1434, 1435; 1430 is the 210.18 10-ampere change, quoted from the on-disk record art33_elr_1430.html). Two on-disk 2023-based reference prints (the SunCam 2023 NEC overview, codeelec_2023.txt; the 2023 exam-prep print, mh_2023_art210.txt) both reproduce the 210.20(A) "noncontinuous load plus 125% of the continuous load" floor.
Supporting sections quoted or referenced: 240.4 (2017 on disk, lines 15790–15990 — the (B) 800 A-or-less next-higher rule, (D) small-conductor caps (D)(1)–(D)(7), (G) Table 240.4(G) specific applications), Table 240.3 (2017 on disk, lines 15804–15860 — the equipment→article routing table, 31 rows), 240.6 (standard OCPD sizes, the verified STD_BREAKERS list 15…6000 A), 210.18 (2017 on disk, lines 10015–10025 — the rating list "15, 20, 30, 40, and 50 amperes" for other-than-individual branch circuits; the 2023 10-ampere change per ELR 1430), 210.21 (2017 on disk, lines 10223ff — the outlet-device caps), 210.19(A) (2017 on disk, lines 10036ff — the conductor-sizing twin).
Worked examples. All breaker picks (nextStdBreaker on the verified 240.6 list), conductor picks (pickConductor31016 on Table 310.16, 2023-verified 0/168 cells), the 240.4(D) caps (smallConductorCap), and the EX8 derating (derate31015: 115 A × 0.80 × 0.94 = 86.48 A) were computed by the shipped cores under node — no hand math.
Honesty flags. (1) The 2023/2026 210.20-specific claims are absence-of-change claims from the change log + two on-disk 2023 reference prints — the 2023/2026 bodies are not on disk. (2) The 2014 edition is not on disk, so no 2014 claim is made; the 210.20 number is stable 2017–2023 per the two on-disk 2023 prints + the change log. (3) The 2023 10-ampere allowance is a 210.18 change (ELR 1430), not a 210.20 change — this article does not claim 210.20 was modified for it. (4) The 2026 NEC renumbers Article 210 (site-wide flag); the 210.20 number is expected to carry forward (secondary-source flag). (5) This page is a design aid, not legal or code-authority advice — the adopted edition in your jurisdiction governs.