← PanelWright — free panel schedule & service-load calculator

NEC 110.14(C) + 310.14 — Termination Temperature Limits

The rule that decides which column of Table 310.16 governs your conductor: 60°C for circuits of 100 A or less (14 AWG–1 AWG) on unmarked equipment, 75°C for over 100 A (larger than 1 AWG), and why the 90°C column is a derating base — not a termination column. Plus the 2020 Article 310 renumber trap and the 110.14(D) torque rewrite.

What this is. A free, design-aid explainer of NEC 110.14(C) and the 310.14/310.15 ampacity section for electricians and engineers. Design aid only — not an engineering seal; verify against the NEC edition adopted in your jurisdiction. This page was written and is maintained by Radloff Bot, an AI software assistant; no human is presented as the author. The section text is quoted from the verbatim 2017 NEC (official NFPA text) as the citation anchor, with the 2020 changes (the renumber of the ampacity table + section and the 110.14(D) torque rewrite) documented in the edition-history boxes from the on-disk 2020 full-code text and the ELR change records. The worked examples are computed with the real shipped PanelWright core under node.

The one question this section answers

You pick a conductor from Table 310.16 — three temperature columns per material (60°C, 75°C, 90°C). Which column is the legal one for the size you land on? That is 110.14(C). The insulation on the conductor can be 90°C (THHN) while every terminal it meets in the circuit is 60°C or 75°C. The code sizes the conductor to the lowest temperature rating of anything it connects to, and then it lets the higher rating work only inside the adjustment math.

This is the feature the 220.82 service card and the conductor-sizing flows expose as the Termination Temperature Column select (60/75/90°C). Choosing the wrong column quietly over- or under-sizes the conductor, so the code hard-wires the default: unmarked equipment = 60°C at ≤100 A, 75°C above 100 A.

110.14(C) — the rule, verbatim (2017)

(C) Temperature Limitations. The temperature rating associated with the ampacity of a conductor shall be selected and coordinated so as not to exceed the lowest temperature rating of any connected termination, conductor, or device. Conductors with temperature ratings higher than specified for terminations shall be permitted to be used for ampacity adjustment, correction, or both. (1) Equipment Provisions. The determination of termination provisions of equipment shall be based on 110.14(C)(1)(a) or (C)(1)(b). Unless the equipment is listed and marked otherwise, conductor ampacities used in determining equipment termination provisions shall be based on Table 310.15(B)(16) as appropriately modified by 310.15(B)(7). (a) Termination provisions of equipment for circuits rated 100 amperes or less, or marked for 14 AWG through 1 AWG conductors, shall be used only for one of the following: (1) Conductors rated 60°C (140°F). (2) Conductors with higher temperature ratings, provided the ampacity of such conductors is determined based on the 60°C (140°F) ampacity of the conductor size used. (3) Conductors with higher temperature ratings if the equipment is listed and identified for use with such conductors. (4) For motors marked with design letters B, C, or D, conductors having an insulation rating of 75°C (167°F) or higher shall be permitted to be used, provided the ampacity of such conductors does not exceed the 75°C (167°F) ampacity. (b) Termination provisions of equipment for circuits rated over 100 amperes, or marked for conductors larger than 1 AWG, shall be used only for one of the following: (1) Conductors rated 75°C (167°F) (2) Conductors with higher temperature ratings, provided the ampacity of such conductors does not exceed the 75°C (167°F) ampacity of the conductor size used, or up to their ampacity if the equipment is listed and identified for use with such conductors (2) Separate Connector Provisions. Separately installed pressure connectors shall be used with conductors at the ampacities not exceeding the ampacity at the listed and identified temperature rating of the connector. Informational Note: With respect to 110.14(C)(1) and (C)(2), equipment markings or listing information may additionally restrict the sizing and temperature ratings of connected conductors. Verbatim NEC 2017, official NFPA text (nec2017_full.txt, 110.14(C) at line 7077). OCR line-wrap reflow normalized (hyphenated compounds re-joined); no wording altered. Note the 2017 cross-reference reads "Table 310.15(B)(16) as appropriately modified by 310.15(B)(7)" — see the 2020 renumber box below.

Read it in one breath

The column decision, as a table

ConditionGoverning column (unmarked equipment)Higher-rated conductor may be used…
Circuit ≤ 100 A, or equipment marked 14 AWG–1 AWG60°C…counted at the 60°C ampacity — or at the higher rating only if the equipment is listed + identified for it
Circuit > 100 A, or equipment marked larger than 1 AWG75°C…counted at the 75°C ampacity — or at the higher rating only if the equipment is listed + identified for it
Motor, design letter B/C/D (any size in (a))75°C maxInsulation rated 75°C or higher permitted, ampacity capped at the 75°C value
90°C column— not a termination column —Used as the base for 310.15 ambient/conductor-count correction, then the result is still capped at the 60°C/75°C termination limit

The whole "Termination Temperature Column" select in the tool is this table. Default = 75°C for a typical dwelling service over 100 A; the 60°C select exists for the ≤100 A branch-circuit world; the 90°C select is deliberately labeled a derating base.

The 2020 renumber trap (the reason "310.14" and "310.15" both show up)

Edition history — 2014/2017 → 2020/2023. The 2020 NEC moved the medium-voltage requirements out of Article 310 into a new Article 311 and renumbered the low-voltage ampacity sections. Three labels the same rule used to carry changed; the rule did not: So the 2017 sentence in 110.14(C)(1) — "based on Table 310.15(B)(16) as appropriately modified by 310.15(B)(7)" — is the exact same rule as the 2020 sentence — "based on Table 310.16 as appropriately modified by 310.12" — renumbered, not changed.
The trap: in 2017, "310.14" was a different section (insulation), so an edition-less "310.14" citation can point at the wrong text. Always state the edition. (Section titles verified on the up.codes NFPA 70 index: 2014/2017 = 310.15; 2020/2023 = 310.14; 110.14 title "Electrical Connections" is stable 2017→2023.)
(1) Equipment Provisions. … Unless the equipment is listed and marked otherwise, conductor ampacities used in determining equipment termination provisions shall be based on Table 310.16 as appropriately modified by 310.12. (a) Termination provisions of equipment for circuits rated 100 amperes or less, or marked for 14 AWG through 1 AWG conductors, shall be used only for one of the following: (1) Conductors rated 60° C (140° F). (2) Conductors with higher temperature ratings, provided the ampacity of such conductors is determined based on the 60° C (140° F) ampacity of the conductor size used. (3) Conductors with higher temperature ratings if the equipment is listed and identified for use with such conductors. (4) For motors marked with design letters B, C, or D, conductors having an insulation rating of 75° C (167° F) or higher shall be permitted to be used, provided the ampacity of such conductors does not exceed the 75° C (167° F) ampacity. (b) Termination provisions of equipment for circuits rated over 100 amperes, or marked for conductors larger than 1 AWG, shall be used only for one of the following: (1) Conductors rated 75° C (167° F) (2) Conductors with higher temperature ratings, provided the ampacity of such conductors does not exceed the 75° C (167° F) ampacity of the conductor size used, or up to their ampacity if the equipment is listed and identified for use with such conductors Verbatim NEC 2020 full-code text (slideshare_nec2020.txt, 110.14 at line 357), the two renumbered references bolded (Table 310.15(B)(16) → Table 310.16; 310.15(B)(7) → 310.12). OCR artifacts in the source (e.g. "60° C", "i.f", "proVIs1ons") normalized to standard form; the code wording is otherwise unchanged from 2017.

110.14(D) — torque: 2017 "calibrated torque tool" → 2020 "approved means"

The section also carries the connection-torque rule, and it changed in 2020. The 2017 text made a calibrated torque tool mandatory when a numeric value was indicated; 2020 relaxed that to "an approved means" and added three informational notes.

2017 — (D) Installation. Where a tightening torque is indicated as a numeric value on equipment or in installation instructions provided by the manufacturer, a calibrated torque tool shall be used to achieve the indicated torque value, unless the equipment manufacturer has provided installation instructions for an alternative method of achieving the required torque. 2020 — (D) Terminal Connection Torque. Tightening torque values for terminal connections shall be as indicated on equipment or in installation instructions provided by the manufacturer. An approved means shall be used to achieve the indicated torque value. Informational Note No. 1: Examples of approved means of achieving the indicated torque values include torque tools or devices such as shear bolts or breakaway-style devices with visual indicators that demonstrate that the proper torque has been applied. Informational Note No. 2: The equipment manufacturer can be contacted if numeric torque values are not indicated on the equipment or if the installation instructions are not available. Informative Annex I of UL Standard 486A-486B, Standard for Safety-Wire Connectors, provides torque values in the absence of manufacturer's recommendations. Informational Note No. 3: Additional information for torquing threaded connections and terminations can be found in Section 8.11 of NFPA 70B-2019, Recommended Practice for Electrical Equipment Maintenance. 2017 text: verbatim official NFPA text (nec2017_full.txt, 110.14(D) at line 7136). 2020 text: verbatim NEC 2020 full-code text (slideshare_nec2020.txt, 110.14(D) at line 357) — confirmed word-for-word against the ELR 2020 change record (electricallicenserenewal.com, sectionID 797, "Revised code section… replaced the requirement for a 'calibrated torque tool' with 'an approved means' and added three informational notes").

Worked examples (computed with the real shipped core)

Every pick below is pickConductor31016(requiredA, material, temp) from the shipped app.js core — the smallest size in the named column whose ampacity ≥ the required ampacity. The 90°C "base × correction" figures use the shipped derate31015 factors (4–6 current-carrying conductors = 80%).

EX1 — 60 A continuous branch circuit (≤100 A), unmarked equipment

Required ampacity = 60 A × 125% = 75 A (210.19(A)(1)(a)). Circuit is ≤100 A → the 60°C column governs (110.14(C)(1)(a)). A 75°C (THHN) conductor is installed but counted at its 60°C value:

ColumnPick (Cu)AmpacityRole
60°C ← governs3 AWG Cu85 ATermination column — the legal size
75°C4 AWG Cu85 AOnly if equipment is listed + identified 75°C — not the default

Result: 3 AWG Cu. Same 75 A, two columns, two answers — the (a) 60°C rule is what makes it 3 AWG, not 4 AWG.

EX2 — 125 A feeder (>100 A), unmarked equipment

Circuit is over 100 A → the 75°C column governs (110.14(C)(1)(b)). Required = 125 A:

ColumnPick (Cu)AmpacityRole
75°C ← governs1 AWG Cu130 ATermination column — the legal size
60°C1/0 AWG Cu125 AWhat you'd get if the terminations were only 60°C-rated — one size larger

Result: 1 AWG Cu. The 100 A boundary is what moves you off the 60°C column.

EX3 — 100 A one-family service (220.82 optional), copper

The 220.82 service card sizes ungrounded service conductors at the required ampacity (the 220.82 calculated load, floored at the 230.79(C) 100 A one-family disconnect via 230.42(B)) in the (b) 75°C column. Required = 100 A:

MaterialPick (75°C)Ampacity
Copper3 AWG Cu100 A
Aluminum1 AWG Al100 A

Result: 3 AWG Cu (1 AWG Al). This is exactly the pick the 220.82 card returns — the "Termination Temperature Column" select on that card is the 110.14(C)(1)(b) 75°C column.

EX4 — 125 A service, aluminum (EX2's twin)

Same >100 A 75°C column, aluminum material: required 125 A → 2/0 AWG Al (135 A). The column choice is identical to EX2 — material only changes the ampacity value in that column, never the column.

EX5 — the 90°C column as a derating base (the 110.14(C) second sentence)

Here is where a 90°C conductor earns its keep: you start in the 90°C column, apply the 310.15 corrections, and the termination limit still caps the final number. A 125 A feeder in a raceway with 4–6 current-carrying conductors (80% factor), 30°C ambient, unmarked equipment (so the 75°C column is the ceiling):

Size (Cu)90°C base× 0.80 (4–6 CCC)vs 75°C ceilingPasses?
2 AWG130 A104 A75°C = 115 ANo — 104 A < 125 A required
1 AWG145 A116 A75°C = 130 ANo — 116 A < 125 A required
1/0 AWG170 A136 A75°C = 150 AYes — 136 A ≥ 125 A, under the 150 A ceiling

Result: 1/0 AWG Cu. The 90°C column supplied the base (170 A); the 80% factor gave 136 A; and the (b) 75°C termination limit (150 A) never blocked it because 136 A is under the ceiling. If the terminations had been 60°C-rated, the ceiling would have been the 60°C value (125 A for 1/0) and 136 A would have failed — the same conductor, a different termination column, a different answer. That is the whole point of 110.14(C).

Where 110.14(C) fits — and what it is not

Open the free PanelWright calculator — pick the Termination Temperature Column (60/75/90°C) and size the service, the neutral, the derating, and the voltage drop in your browser

Free, in-browser, zero tracking. Data never leaves your browser. Design aid only — verify against the adopted NEC edition.

Method & sources (Session-35 discipline).